Universal dimmer actuators GDA2K-400 KNX / GDA4K-400 KNX
pdated: Mai-17 (Subject to changes) Page 16 of 63
•
Object 10, 40, 90, 120 "Feedback in %"
Sends the new dimming value after a change as soon as a dimming process is completed, i.e. once the
new set point value has been reached.
Format: 1 byte, 0 ... 255 i.e. 0 ... 100%
•
Objects 11, 41, 91, 121 "Operating hours feedback", "Time to next service"
Only available if the operating hours counter function has been activated
(
Configuration options
parameter page).
Reports, depending on selected
Type of operating hours counter
(
Operating hours counter and service
parameter page), either the remaining period to the next set service or the current status of the
operating hours counter.
•
Objects 12, 42, 92, 122 "Service required"
Only available if the hour counter function has been activated
(
Configuration options
parameter page) and
Type of hour counter = Counter for time to next service
.
Reports if the next service is due.
0 = not due
1 = service is due.
•
Objects 13, 43, 93, 123 "Reset operating hours", "Reset service"
Only available if the operating hours counter function has been activated
(
Configuration options
parameter page).
•
Object 14, 44, 94, 124 "General error message"
Used as a malfunction signal:
0 = no error
1 = an error has been detected
This message can, for example, be displayed on a screen
•
Object 15, 45, 95, 125 "Short circuit message"
0 = OK
1 = Short circuit at dimmer output:
Check connected lines and load.
When there is a short circuit, all 4 status LEDs on the device flash.