background image

7

For a stand alone wallbox, recommended address is 002.
This mode will paus the charging process if available current in 
the system is below 6A. 6A is the minimum av EV can charge 
according to standard.
Note: No need to to do any settings in the wallbox webinterface.
Modbus address 002 is the only adress that you can use if you 
dont have any Wifi-module installed in your wallbox
Modbus address 002 is only valid for stand alone wallbox 
installations.

For multiple wallboxes connected in a grid, use address #100. 
DLM settings in the webinterface are required.
Address 100 require an installed wifi-module in the Master 
Wallbox.
Note: When use of Adress 100, the wallbox will not paus the 
charging process if available current is below 6A.

If you want to monitor a 2nd mains cabinets, a 2nd DLM meter 
can be installed in the 2nd mains cabinet. The modbus address 
for the 2nd DLM meter should be 101.
Both 100 and 101 will not paus the charging process if available 
current in the system is below 6A. 
Note: DLM settings are required in the master wallbox 
webinterface.
Modbus address 100 and 101 require an installed wifi-module in 
your master wallbox.

!

!

!

Rx

!

!

!

Rx

Modbus address information

9

EN

Содержание 109385

Страница 1: ...GARO AB GARO GNM3T LP RS485 N as DLM meter Box 203 SE 335 25 Gnosj info garo se garo se Manual 380253 DLM Dynamic Loadbalancing Meter Installation and Programming Manual EN...

Страница 2: ...ICAL CONNECTION POWER CABLES 4 2P 4 3Pn 4 3P 4 DLM METER SETTINGS 5 Touch area 5 System setting 6 CT Ratio setting 7 UT Ratio setting 8 Modbus address information 9 Set the Modbus Adress 10 Set verify...

Страница 3: ...orized electrician MODBUS CONNECTION Install the DLM meter in the mains cabinet you want to monitor Use shielded twisted pair cable between the DLM meter and the wallbox Suitable cables CAT5 FTP CAT5e...

Страница 4: ...CONNECTION POWER CABLES N 1 2 3 section 4 mm torque 0 6 Nm 4 17 section 1 5 mm torque 0 4 Nm EN 4 L N F 16 17 Rx L1 L2 L3 N F N 1 2 8 4 7 9 3 5 6 L1 L2 N F N 1 2 4 7 5 6 L1 L2 L3 F 1 2 8 4 7 9 3 5 6...

Страница 5: ...DLM METER SETTINGS Rx Rx 5 EN Rx Rx Rx Touch area 1 Longpress center touch area until you see PASS...

Страница 6: ...a until SYStEn is visible If you need to change the current System setting follow below instructions 2 Longpress center touch area and PrG is visible 3 Click left or right touch area until wanted valu...

Страница 7: ...is visible Confirm by longpress center touch area and next figure starts to blink 4 Repeat step 3 until the complete value is correct Rx 7 EN CT Ratio setting CT Ratio values depending on the CT you...

Страница 8: ...area and PrG is visible 3 Click left or right touch area until wanted value is visible Confirm by longpress center touch area and next figure starts to blink 4 Repeat step 3 until the complete value i...

Страница 9: ...grid use address 100 DLM settings in the webinterface are required Address 100 require an installed wifi module in the Master Wallbox Note When use of Adress 100 the wallbox will not paus the chargin...

Страница 10: ...blink 2 Click left or right touch area to modify the figure 3 Longpress center touch area to change to next figure and repeat step 2 Rx Rx 4 When the adress is correct longpress center touch area to c...

Страница 11: ...OTE Correct Value Baudrate 9 6 Rx Click left touch area until PArIty is visible Default is no and this is correct If you need to change the parity longpress center touch area and click left or right t...

Страница 12: ...Confirm settings 1 Click left touch area until End is visible 2 Longpress center touch area when End is visible and the setting is confirmed 3 The square is blinking when DLM meter have communication...

Отзывы: