Page 16
714 / 714-P Manual
chapter entitled “
TROUBLESHOOTING GUIDE
” and the
section “
To review the sender diagnostics
” for details). If the
signal power is too low, make sure that the sender(s) is well
stuck to the side of the tank and that the tank is reasonably
clean inside, as a large buildup will reduce signal strength.
The gauge will work with maximum signal strengths as low as
5%, but it is good to have at least 12% at installation so that
there is some margin available for buildup in the tank. Note
that the system “learns” about the characteristics of the tank
with use, so the readings may be inaccurate when the tank is
empty or almost empty when the system is first tested. Once
the tank has been filled at least 1/4 full the system will be
properly “taught” and should read correctly after that.
16.
Calibrate the LPG by filling the tank and following the
instructions in the chapter entitled “
DISPLAY CALIBRATION
”
and the section “
To calibrate the LPG sender
”.
17. Connect the pump and heater switches as required.
WARNING: The pump and heater switches are rated for a
maximum of 6 amps. The use of a relay is required if more
than 6 amps is needed.
18. Verify that the battery voltage reads correctly. If it appears
low, make sure you have good wiring for the 12 volt power
and the ground.