13-21-615 v01 Page 53
Figure 5-1 DEW POINT CHART
F
Figure 5-2 DEW POINT CHART
C
These charts are easily used by reading the ambient temperature along the bottom axis of the chart and then
reading the appropriate pressure curve to determine the corresponding dew-point temperature on the left axis of
the chart. The compressor discharge temperature must be maintained at a minimum of 10
F above this dew-
point temperature to prevent condensation accumulation in the lubricant reservoir. These charts assume 100%
relative humidity.
Содержание SAVG2-100
Страница 12: ...13 21 615 v01 Page 11 307EBD797 EA Ref Drawing Figure 1 6 AIR OIL FLOW DIAGRAM...
Страница 41: ...13 21 615 v01 Page 40 FIGURE 4 6 COMPRESSOR PACKAGE P ID 300EBF797 EB Ref Drawing...
Страница 55: ...13 21 615 v01 Page 54 300EBF797 EB Ref Drawing Figure 5 3 FLOW DIAGRAM AIR OIL SYSTEM...
Страница 56: ...13 21 615 v01 Page 55 318EBD797 00 Ref Drawing Figure 5 4 OIL FLOW DIAGRAM REMOTE MOUNTED COOLER...