13-17-621 Page 95
4.7.1.2 Serial Number:
The
Serial Number
of the compressor will be entered in this location. This serial number is used in various
places including the data logs for the machine. The serial number is set at the factory and can be used as
a reference to the machine when needing information or replacement parts.
4.7.1.3 Design Pressure:
The
Design Pressure
setting is the pressure this machine is designed to run at. Figure 128 below shows
the setting of
Design Pressure
set to
130 psi
. Note that setting the design pressure to a value that does
not match the machine capabilities may allow dangerous operation of the compressor. The warning and
fault pressure band settings will be limited based off the design pressure setting.
Figure 128: Design Pressure
4.7.1.4 Max Volume Flow:
The
Max Volume Flow
setting is used on fixed speed machines, it should be set to the compressor rated
volume flow at the operating pressure. This value is used to calculate the current volume flow readings
throughout the user interface as well as the volume flow used for some sequencing algorithms. Figure 129
below shows setting the
Max Volume Flow
to
281 CFM
.