manualshive.com logo in svg
background image

6. Controller – Level 1

- 17 –

6. Controller – Level 1

switch to stop a dryer.  Closing this switch will affect
the same response as a loss of power. Both inlet-

switching valves will open and both purge-

repressurization valves will close.  A tower that is

actively purging when the power on/off button is
actuated will be subjected to a rapid repressurization

that can lead to fluidization and subsequent abrasion

of the desiccant bed. Ideally, dryers should only be

powered off during those portions of the drying cycle
when both desiccant towers are at full operating

pressure. Use of the remote start/stop connections as

described in Section 6.2.3 would be preferable in most

cases.

 

Terminals J2-7 and –8 (remote alarm reset and manual
cycle increment switch)

6.2.5 

Connections – 

RS232 

/ Net Web

RS232 and/or Net Web connections can be made at the 3-pin

connector labeled J5 and located at the upper left-hand corner

of the control board. A cable for this connection can be
purchased through your distributor.

6.3 

Control Bo

ard Jumpers

 – Level 1

Refer to Figure 6-3, Point to Point Connection Diagram – Level 1
Controller.  
In the upper left hand corner of the control board

there are four two-pin jumpers labeled J1 through J4. Only three

of the four jumper pairs are utilized. Pair J2 is not used. The

jumper is a removable bridge that is used to make or break
continuity between the two pins that form a pair. When installed

in the ON position, the jumper is placed on both pins of the pair

and continuity between the pins is established.  When installed
in the OFF position, the jumper is removed or stored on a single

pin and continuity is broken.  Jumper functions are as follows:

6.3.1 

Jumper J1 – M

aximum

 Operating Pressure

Jumper J1 is used to select the maximum operating pressure.

Installed in the OFF position when operating at inlet pressures
of 60 to 150 psig (4.2 to 10.5 kgf/cm

2

). Installed in the ON

position when operating at inlet pressures of 120 to 250 psig

(8.4 to 17.6 kgf/cm

2

). This setting will affect tower purge and

repressurization times. (Refer to serial number tag.)

6.3.2 

Jumper J2 – Un

used.

6.3.3 

Jumper J3 – Se

rvice R

eminder Interval

Jumper J3 is used to select the service reminder interval.
Installed in the OFF position when the Normal service reminder

interval is desired. Installed in the ON position when the Severe
service reminder interval is desired. Service items, check points

and time intervals appear in Table 6-2.

6.3.3.1 

Filter Service

When the service interval for filters has expired the following

LEDs will blink:

 

Service LED (amber)

 

Three filter LEDs (amber)

6.3.3.2 

Desiccant Servi

ce

When the service interval for desiccant has expired, the

following LEDs will blink:

 

Service LED (amber)

 

Both tower regenerating LEDs (amber). The service
function overrides the normal display of the tower

regenerating LEDs.

6.3.3.3 

Valve Service

When the service interval for valves has expired, the following
LEDs will blink:

 

Service LED (amber)

 

Four valve LEDs (green) The service function overrides
the normal display of the valve LEDs.

To extinguish the blinking LEDs and restart the timer for a new
service interval, press the alarm reset button. NOTE:  Time

continues to accumulate as long as power is supplied to

the controller, whether the controller is switched on or off.
Use the following sequence to manually reset the accumulated

service interval time for all timers.

 

Pause for about 1 second at each instruction.  If the
sequence is executed too quickly it will not work.

 

With the controller already on, press and hold the alarm
reset button.

 

Press and hold the on/off button.

 

Release the on/off button.

 

Release the alarm reset button.  The service interval time
is now reset; the maintenance LED flashes three times to

acknowledge the action.

Service Item

(Customer check points
are listed for each item)

Normal

Service

Interval

(J3 OFF)

Severe

Service

Interval

(J3 ON)

Filters

1. Check prefilter Delta-P
2. Ensure prefilter drain is discharging
3. Check afterfilter Delta-P

4,000

Hours

2,000

Hours

Desiccant

1. Check moisture indicator
2. Check dryer outlet dew point
3. Inspect mufflers for excessive dusting

8,000

Hours

4,000

Hours

Valves

1. Ensure valves are cycling properly
2. Check for switching failure alarms
3. Inspect valves for leaks - adjust purge
valve as needed

4,000

Hours

2,000

Hours

Table 6-2

Jumper J3 – Service Reminder Intervals

6.3.4 

Jumper J4 – Po

wer Rec

overy Mode

Jumper J4 is used to select the power recovery mode. When

power to the controller is interrupted, the position of this jumper

controls the recovery mode of the dryer when power is restored.
Installed in the OFF position when automatic power recovery is

Содержание DGH Series

Страница 1: ...FM 1130 SCFM 750 930 1130 DGH1350 DGH1550 DGH2100 1350 SCFM 1550 SCFM 2100 SCFM 1350 1550 2100 DGH3000 DGH4100 DGH5400 3000 SCFM 4100 SCFM 5400 SCFM 3000 4100 5400 Contents 1 GENERAL SAFETY INFORMATIO...

Страница 2: ...4 Noise CAUTION Do not operate dryer without mufflers installed 1 5 High Velocity Air CAUTION Do not stand near mufflers during tower depressurization 2 Receiving Moving Unpacking 2 1 Receiving This s...

Страница 3: ...as the heat of adsorption and is stored in the bed for use during regeneration Desiccant is regenerated by driving off desorbing the water collected on its surface Pressure swing also called heatless...

Страница 4: ...ge stream flow rate is controlled by the adjustable purge rate valve 6 and the two purge orifices 7 The purge flow which has been throttled to near atmospheric pressure is directed to tower 4B As the...

Страница 5: ...flow rate is controlled by the adjustable purge rate valve 6 and the single purge orifice 7 The purge flow which has been throttled to near atmospheric pressure is directed through purge check valve 5...

Страница 6: ...mperature measurement is made at position B1 After the tower has been regenerated another measurement is made at B1 The drop in temperature sensed during regeneration is an indirect measure of the wat...

Страница 7: ...esiccant air dryer 4 1 3 Prefilter s Adequate filtration is required upstream of the dryer in order to protect the desiccant bed from contamination The following filtration equipped with automatic con...

Страница 8: ...o drains and or sumps and lower piping with inlet switching and purge repressurization valves is necessary to prevent condensate from freezing If installing heat tracing observe electrical class code...

Страница 9: ...ers Exhausting compressed air directly to atmosphere will result in noise levels above OSHA permissible levels and rapidly expanding gas could potentially cause harm to persons or property 4 13 Initia...

Страница 10: ...ORT TYP PILOT AIR FILTER REGULATOR S AIR INLET RIGHT TOWER PRESSURE GAUGE RIGHT DESICCANT TOWER PURGE REPRESSURIZATION VALVE TYP INLET SWITCHING VALVE TYP S AIR OUTLET STRAINER TYP SAFETY RELIEF VALVE...

Страница 11: ...3 4 S 1 2 NPT 3 4 NPT 3 4 NPT 1 NPT 1 NPT 1 1 2 NPT 1 1 2 NPT 1 1 2 NPT WT LBS 365 445 575 685 685 1010 1215 1350 DIMENSIONS IN MILLIMETERS MODEL 40 60 90 115 165 260 370 450 A 660 660 838 838 838 111...

Страница 12: ...4 Installation 12 4 Installation Figure 4 3 continued on next page 590 5400 SCFM General Arrangement...

Страница 13: ...116 3 16 R 102 105 110 113 118 115 117 124 124 124 S 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 U 2 NPT 2 1 2 NPT 2 1 2 NPT 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE 6 FLANGE WT LBS 2205 270...

Страница 14: ...iliary power terminals See Note 2 9 9 Solenoid valve coil voltage 12 VDC 12 VDC NEMA 4 4X IP 66 electrical enclosure rating 9 9 Soft on off switch with two power recovery modes See Note 3 9 9 Tower st...

Страница 15: ...r is restored after an interruption 4 The service reminder LEDs indicate that it is time to perform preventive maintenance on the a filters and drains b valves or c desiccant The user selects between...

Страница 16: ...free common alarm contacts with a minimum 5 amp rating can be made at terminals TB2 7 through 9 Terminal TB2 9 is the common contact connection Terminal TB2 7 is the N O normally open contact connecti...

Страница 17: ...FF position when the Normal service reminder interval is desired Installed in the ON position when the Severe service reminder interval is desired Service items check points and time intervals appear...

Страница 18: ...der LED Alarm LED Reset switch for alarm and maintenance reminder Advance switch for manual cycle Operating mode LED Manual test mode not desired Installed in the ON position when automatic power reco...

Страница 19: ...ately 2 seconds The current ISO Class LED will remain illuminated and the Manual cycle mode LED will illuminate When in the Manual cycle mode the dyer can be advanced one step at a time using the rese...

Страница 20: ...9 10 01 05 03 37 06 14 09 46 00 44 02 43 05 07 08 25 t3 0 01 12 04 00 06 55 10 50 00 48 03 00 05 40 09 20 t4 all 02 00 05 00 08 00 12 00 02 00 05 00 08 00 12 00 t5 all 02 02 05 02 08 02 12 02 02 02 05...

Страница 21: ...sure d open 1 open 1 Right tower regenerating Fail to de pressurize e closed 1 Right tower regenerating Fail to re pressurizef open 2 Note Stop cycle on fault Comments 1 Check for fault condition at 1...

Страница 22: ...6 Controller Level 1 22 6 Controller Level 1 Figure 6 2 Electrical Schematic Level 1 Controller...

Страница 23: ...6 Controller Level 1 23 6 Controller Level 1 Figure 6 3 Point to Point Connection Diagram Level 1 Controller...

Страница 24: ...6 Controller Level 1 24 6 Controller Level 1 Figure 6 4 continued on next page Panel Layouts Level 1 Controller...

Страница 25: ...6 Controller Level 1 25 6 Controller Level 1 47 63 HZ 85 264 VAC 11 5 28 VDC Figure 6 4 continued from previous page Panel Layouts Level 1 Controller...

Страница 26: ...PG 9 0 599 15 2 3 SOLENOID LEFT INLET VALVE 2 18 0 181 4 6 0 312 7 9 PG 9 0 599 15 2 4 SOLENOID LEFT PURGE VALVE 2 18 0 181 4 6 0 312 7 9 PG 9 0 599 15 2 5 SOLENOID RIGHT INLET VALVE 2 18 0 181 4 6 0...

Страница 27: ...common alarm contacts with a minimum 5 amp rating can be made at terminals TB4 39 through 41 Terminal TB4 41 is the common contact connection Terminal TB4 39 is the N O normally open contact connectio...

Страница 28: ...ing Pressure Jumper JP1 is used to select the maximum operating pressure Installed in the OFF position when operating at inlet pressures of 60 to 150 psig 4 2 to 10 5 kgf cm2 Installed in the ON posit...

Страница 29: ...D On switch closed Off switch open Right tower drying LED Right purge valve LED On valve open Off valve closed Right tower regenerating LED Right inlet valve LED On valve open Off valve closed Enter s...

Страница 30: ...tart mode Program Mode Screen 2 Refer to Section 7 7 for additional information 7 4 2 2 SELECT Switch This button is located to the left of the text display window Refer to Section 7 6 for additional...

Страница 31: ...ET NO Press S to toggle between NO and YES When finished press E to acknowledge the selection and move to Screen 6 7 7 6 Program Mode Screen 6 Reset the timer for desiccant service DESICCANT SERVCE RE...

Страница 32: ...arms for each tower that are triggered by the tower pressure switches These alarms can occur in either the fixed or demand cycle Following is a brief description of each alarm 1 Left or right tower dr...

Страница 33: ...itch Circuit ALARM LEFT TOWER DRYING LOW PRESSURE 7 9 1 5 Alarm Mode Screen 2 Left Tower Regenerating High Pressure Closed Pressure Switch Circuit ALARM LEFT TOWER REGENERATING HIGH PRESSURE 7 9 1 6 A...

Страница 34: ...lter to the Level 2 Controller the controller displays the same LEDs and messages it would if the timer for filter service had expired The dryer continues to cycle normally NOTE The LEDs for the valve...

Страница 35: ...not installed INLET PRESSURE XX BARG XXX PSIG 7 10 9 Display Mode Screen 6 Dryer inlet temperature AUX3 analog input This screen is not displayed if jumper 5 is not installed INLET TEMP XX C XXX F 7...

Страница 36: ...t Mode Screen 1 Step 1 TEST MODE STEP 1 OK TO EXIT NOW No temperature display on this screen Press S to advance to screen 2 7 11 2 Test Mode Screen 2 Step 2 TEST MODE STEP 2 XX C XXX F The left tower...

Страница 37: ...n 6 7 or 8 Dryer MOP 60 150 psig 120 250 psig ISO Class 1 2 3 4 1 2 3 4 73 C 40 C 20 C 3 C 73 C 40 C 20 C 3 C Dew Point 100 F 40 F 4 F 38 F 100 F 40 F 4 F 38 F Cycle Time minutes 4 10 16 24 4 10 16 24...

Страница 38: ...nerating Fail to re pressurizef open 2 Note Stop cycle on fault Comments 1 Check for fault condition at 15 25 35 seconds into the half cycle no If the fault condition is clear for 1 cycle the alarm LE...

Страница 39: ...7 Controller Level 2 39 7 Controller Level 2 Figure 7 2 Electrical Schematic Level 2 Controller...

Страница 40: ...7 Controller Level 2 40 7 Controller Level 2 3 2 1 5 4 8 7 6 J2 RPB Figure 7 3 continued on next page Point to Point Diagram Level 2 Controller...

Страница 41: ...7 Controller Level 2 41 7 Controller Level 2 COM NC NO Figure 7 3 continued from previous page Point to Point Diagram Level 2 Controller...

Страница 42: ...7 Controller Level 2 42 7 Controller Level 2 Figure 7 4 continued on next page Panel Layout Level 2 Controller...

Страница 43: ...7 Controller Level 2 43 7 Controller Level 2 1 TB2 TB1 TB4 TB3 TB5 TB6 2 3 4 5 6 7 8 Figure 7 4 continued from previous page Panel Layout Level 2 Controller...

Страница 44: ...2 0 114 2 9 0 250 6 4 PG 7 0 492 12 5 5 THERMISTOR 3 LEFT TOWER LOWER 2 22 0 114 2 9 0 250 6 4 PG 7 0 492 12 5 6 THERMISTOR 4 RIGHT TOWER LOWER 2 22 0 114 2 9 0 250 6 4 PG 7 0 492 12 5 7 PRESSURE SWIT...

Страница 45: ...onditions listed in Section 8 1 4 Note For units with the Level 2 Controller and the Automatic Purge Saving System in the demand cycle mode use the ISO Class 2 10 min purge pressure settings only Adju...

Страница 46: ...ing lights illuminated 8 2 2 Moisture Indicator Every four hours check moisture indicator Indicator should be green The color change moisture indicator indicates the outlet relative humidity of the de...

Страница 47: ...ffler Excessive air discharge through the muffler can be associated with a leaking outlet check valve on the same side or a purge check valve of the opposite side tower Purge pressure and subsequent f...

Страница 48: ...For maximum purge flow multiply the Inlet Flow At Rated Conditions from Table 8 1 by Maximum Purge Flow Factor from Table 8 6 that corresponds to the dryer MOP Cycle Time Setting and air pressure at i...

Страница 49: ...2 5 2 5 2 3 2 2 2 2 2 2 2 1 2 0 2 0 psig 18 17 16 15 14 13 35 33 32 30 29 28 27 26 25 25 24 23 23 22 ISO CL 3 16 min kgf cm2 1 3 1 2 1 1 1 1 1 0 0 9 2 5 2 3 2 2 2 1 2 0 2 0 1 9 1 8 1 8 1 8 1 7 1 6 1 6...

Страница 50: ...25 0 125 0 125 0 125 0 125 0 125 20 0 122 0 120 0 119 0 118 0 117 0 116 0 116 0 116 0 115 0 115 0 115 0 116 0 116 0 116 30 0 110 0 108 0 107 0 106 0 106 0 106 0 105 0 105 0 105 0 106 0 106 0 106 0 107...

Страница 51: ...ght containers Keep the covers on these containers tightly closed until use to avoid moisture contamination If desiccant is exposed to air it can be heated in an oven at 400 F 204 C for four hours bef...

Страница 52: ...ilot air filter The system must be fully de pressurized before removing the bowl Remove the filter bowl by pushing up turning counterclockwise and then pulling straight down Clean the filter bowl Repl...

Страница 53: ...removal of voltage to pilot solenoid valve Verify proper actuator operation This is a spring assisted normally closed valve Check valve for obstruction or seat damage 10 4 Tower fails to re pressurize...

Страница 54: ...Additional information that may be useful when dealing with Service Location of installation address and phone number _____________________________________________________________________ Distributor...

Страница 55: ...________________________________________________________ Fixed or Demand Cycle Mode Level 2 controller only ___________________________________________________________________ Outlet pressure dew poin...

Страница 56: ...IN LIEU OF ALL OTHER WARRANTIES WRITTEN ORAL OR SATUTORY AND IS EXPRESSED IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTU...

Отзывы: