FocalPoint™ Gateway

 

Installation & Operation Manual

 - 

P/N: 52649

:

Rev: B3

  

2/11/10

IMPORTANT INFORMATION

This manual is designed for use by factory trained installers 
and operators of the Gamewell/FCI FocalPoint™ System.  
All illustrations, functional descriptions, operating and 
installation procedures, and other relevant information are 
contained in this manual.
The contents of this manual are important, and the manual 
must be kept with the system at all times.  If building 
ownership is changed, this manual, including any testing 
and maintenance information, must be passed along to the 
new owner(s).
Manuals and instructions for other devices forming part of 
the FocalPoint™ System should be kept together.  
Purchasers who install this system for use by others must 
leave the instructions with the user.  A copy of these 
instructions is included with each product and is available 
from the manufacturer.
This equipment is Listed by various listing agencies for use 
in emergency evacuation and fire alarm systems.  Use only 
components that are compatible with this FocalPoint™ 
System.  The installation MUST be in accordance with the 
instructions in this manual.
Therefore: 

DO NOT deviate from the procedures described in this 
manual.

DO NOT assume any details not shown in this manual.

DO NOT modify any electrical or mechanical features.

DO comply with all codes and standards set forth by 
the Authority Having Jurisdiction.

The term “Authority Having Jurisdiction” has become a 
standard term in the fire alarm industry.  An acceptable 
definition of “Authority Having Jurisdiction” is: 
Fire alarm systems installed in the USA fall under the 
jurisdiction of some authority.  In some areas, this may be a 
local fire department; in other areas, it may be a building 
inspector, insurance firm, etc.  Different authorities may 
have their own local requirements for the way the fire alarm 
system is installed and used.  Most local authorities based 
their requirements on the NFPA (National Fire Protection 
Association) codes, but there may be important 
differences.  You must install this system in the way in 
which the Authority Having Jurisdiction requires.  If you do 
not know which authority has jurisdiction in your area, 
contact your local fire department or building inspector for 
guidance.
It is important that you tell users to be aware of any 
requirements defined by the Authority Having Jurisdiction.
The installation MUST be in accordance with the following 
standards:

National Fire Alarm Code (NFPA 72)

National Electrical Code (NFPA 70) 

Life Safety Code (NFPA 101)

WARNING: Touching components, which are 
improperly installed, applied or operated, could be 
hazardous and possibly fatal.  Short circuits could 
cause arcing that could result in molten metal injuries.  
Therefore, only qualified technicians familiar with 
electrical hazards should perform checkout 
procedures.  Safety glasses should be worn, and test 
equipment used for voltage measurements should be 
designed for this purpose and be in good working 
order.

ENVIRONMENTAL CONSIDERATIONS

It is important that this equipment be operated within its 
specifications: Recommended operating temperature 
range: 0°C to 49°C (32°F to 120°F) and at a relative 
humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C 
(90°F ± 3°F).

INSTALLATION CONSIDERATIONS

Check that you have all the equipment you need to 
complete the installation.  Follow the field wiring diagrams 
and installation notes in this manual.
Install the equipment in a clean, dry environment (minimal 
dust).  Avoid installing the equipment where vibrations will 
occur.
Remove all electronic assemblies prior to drilling, filing, 
reaming, or punching the enclosure.  When possible, make 
all cable entries from the side, being careful to separate the 
power-limited conductors from the non power-limited 
conductors.  Before making modifications, verify that they 
will not interfere with battery, transformer, and printed circuit 
board location.
Do not over tighten screw terminals.  Over tightening may 
damage threads, resulting in reduced terminal contact 
pressure and difficulty with screw terminal removal.
Disconnect all sources of power before servicing, removing, 
or inserting any circuit board.  Control unit and associated 
equipment may be damaged by removing and/or inserting 
cards, subassemblies, or interconnecting cables while the 
unit is energized.
FocalPoint is a trademark of Honeywell International.

Содержание IF602

Страница 1: ...d CT 06472 203 484 7161 FAX 203 484 7118 www gamewell fci com FocalPoint System Utilities User s Guide FocalPoint Gateway Installation Operation Manual Copyright 2010 All Rights Reserved Published in...

Страница 2: ...ich the Authority Having Jurisdiction requires If you do not know which authority has jurisdiction in your area contact your local fire department or building inspector for guidance It is important th...

Страница 3: ...me Any smoke detector fire alarm system or any component of that system shall be repaired or replaced immediately SYSTEM RE ACCEPTANCE TEST To ensure proper system operation this product must be teste...

Страница 4: ...nd recommend a solution Smoke detectors cannot be expected to provide adequate warning of a fire caused by arson children playing with matches especially in bedrooms smoking in bed violent explosions...

Страница 5: ...Cable Connection 19 2 5 2 600 Series Panel Serial Data Connections 19 Figure 2 7 Direct Serial Data Connection Using the IF602 Supplied Cable 19 Figure 2 8 Direct Serial Data Connection Using the Gat...

Страница 6: ...Gamewell FCI 7200 Panel Cards 37 4 5 About Auto created Points 37 4 5 1 SmartProgram II Application 37 Section 5 FocalPoint Gateway Config Tool Reference Information 39 5 1 About the FocalPoint Gatew...

Страница 7: ...and E3 panels to have a two line DACT in addition to the gateway for event reporting The FPT Gateway software application resides on a PC board assembly that is installed inside a supplied cabinet It...

Страница 8: ...purpose communications network equipment For ULC applications the Internet cannot be used for either primary or ancillary functionality Gateway Workstation Other Technologies LAN WAN Internet Intranet...

Страница 9: ...Underwriters Laboratories UL 1076 In certified applications the unit shall be installed in accordance with Proprietary Burglar Alarm Units and Systems Fifth Edition Underwriters Laboratories Canada C2...

Страница 10: ...gateway with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and or the latest edition of UL 864 These applications will require approval of the local...

Страница 11: ...a UL listed FocalPoint system FocalPoint Workstation 52561 NOTE The contents of this manual are important and must be kept in close proximity of the hardware If building ownership is changed this man...

Страница 12: ...FPT Gateway Overview Related Documentation 12 FocalPoint Gateway Installation Operation Manual P N 52649 Rev B3 2 11 10...

Страница 13: ...e this insulator in the bottom of the cabinet in order to meet ULC S527 99 spacing requirements FocalPoint Gateway Config Tool FPT Gateway Manual Network Components RJ45 to RJ45 standard Ethernet netw...

Страница 14: ...s setting Press and hold the button for at least 15 seconds to return the gateway to the factory shipped state Lithium Battery The Panasonic BR2032 lithium battery P N 31007 has a factory installed fi...

Страница 15: ...r lock key to unlock the cabinet s door Step 2 Remove the cabinet s door from the back box reinstall the door when installation is complete Step 3 Mount the cabinet s back box to the wall using the ho...

Страница 16: ...upplied hex nut 6 Step 3 Install the FocalPoint PC board on the gateway cabinet standoffs using the supplied screws 4 Figure 2 3 Gateway Parts Mounting 1 Step 4 You are now ready to perform Cable Conn...

Страница 17: ...Hardware Installation FPT Gateway Installation 17 FocalPoint Gateway Installation Operation Manual P N 52649 Rev B3 2 11 10 Figure 2 4 Gateway Parts Mounting 2...

Страница 18: ...way PC board s serial connector to a 7100 7200 panel assembly required refer to Figure 2 10 Step 4 You are now ready to perform Power Connection on page 21 WARNING Serial Port Connection Unless expres...

Страница 19: ...rial Data Connection Figure 2 6 600 Series Router Serial Cable Connection 2 5 2 600 Series Panel Serial Data Connections Figure 2 7 Direct Serial Data Connection Using the IF602 Supplied Cable 1 2 3 G...

Страница 20: ...ch 600 Series panel s connectors is used for direct serial data connections between the gateway and the 600 Series panel consult your respective Gamewell FCI panel s documentation or contact Technical...

Страница 21: ...powered by any power limited source that is UL listed for use with fire protective signaling units and it meets the following specifications Connect the FPT Gateway s PC board to the respective power...

Страница 22: ...Ethernet Line Impedence 100 ohm Max Distance 100 meters NOTE All wiring connections are supervised and power limited NOTE The cable to a 7100 must be in properly sized conduit and less than 20 feet l...

Страница 23: ...Tool select Start All Programs Facilities Monitoring FocalPoint Gateway Config Tool Step 2 The FocalPoint Gateway Config Tool will attempt to find all FocalPoint Gateway connected to the Ethernet netw...

Страница 24: ...highest level entry in the Nodes list column hierarchy Figure 3 1 Gateway Node Selection Step 2 Select File Login to gain editing control of the selected gateway The Gateway Login window displays Fig...

Страница 25: ...our IP network c Press the keyboard enter key d Click in the Value field adjacent to Subnet Mask Property and then type in the subnet address of the FPT Gateway e Press the keyboard enter key f If the...

Страница 26: ...ct a panel in the Network Type field s list of choices Step 3 If the FocalPoint Gateway is connected to an E3 panel then make the Node Map changes that match your selection made in Network Type field...

Страница 27: ...the Time Zone Configuration fields to synchronize the gateway to GMT of the SNTP Server SNTP Configuration Step 1 Select the highest level entry in the Nodes list column hierarchy Step 2 Click on the...

Страница 28: ...fore your calculation would be 6 hours x 60 minutes 360 minutes Step 8 Click in the Value field adjacent to Observe DST and then select True if you want the gateway to automatically increment or decre...

Страница 29: ...ord window displays Figure 3 6 Gateway Login Change Password Window Step 2 Type in the current password in the Password field Step 3 Type in a new password in the New Password field Passwords are case...

Страница 30: ...eway Step 2 Connect the FPT Gateway to that same external hub Step 3 Start Microsoft Internet Explorer Step 4 In the Internet Explorer Address field type in the192 168 1 2 as IP address of the gateway...

Страница 31: ...Point system to the Workstation using PC Monitor operations Step 1 Locate and right click on the PC Monitor icon in the Windows system tray and then select Import System Data from the list of choices...

Страница 32: ...rkstation Admin admin Step 3 Launch the Configuration Tool from the Workstation s Main Menu select Configure Launch Configuration Tool The Network Configuration window displays Step 4 Select Network A...

Страница 33: ...t s information into the Point field in one of the following formats where XXX is a panel s three digit number 001 999 Step 9 Type in a Point Alias name and Point Description into their respective fie...

Страница 34: ...cognize that the panel was off line the off line event has not been reported When the gateway is powered up a ChkPANEL event is sent to the Workstation for each configured node The ChkPANEL event indi...

Страница 35: ...ommon Gamewell FCI Device Commands Panels GW Connects To Ack Silence Reset Enable Disable Comments 7200 Stand Alone Yes Yes Yes Yes 7100 Stand Alone No No No No Monitor Only 7100 on E3 Network Yes Yes...

Страница 36: ...S PA VERIFY VF DISCONNECT DI LOOP BREAK LB SHORT SH Table 4 4 FCI E3 Point ID Formats for Off Normal Events ACTION AC FIRST ALARM AL P A S PA ALARM TEST AT FAULT TEST FT SHORT SH ALARM AL FAULT FL SP...

Страница 37: ...FocalPoint system are loop devices detectors modules etc and they will include the card type and number in their device ID Some events such as Battery Fault will not include the card type and number 4...

Страница 38: ...grammed into Dictionary Item 2 For panel setup the panel s programmer has to manually select one of the factory default Dictionary Item 2 values to have the Workstation auto create the appropriate ico...

Страница 39: ...an be modified in some way 5 2 Field Descriptions 5 2 1 Gateway Field Description Figure 5 1 Version Description Version Displays the gateway s version 5 2 2 IP Configuration Fields Figure 5 2 IP Conf...

Страница 40: ...d Time Zone Reference Is used to set the time zone standard The choices are US Standard When selected the DST Begin and DST End settings are automatically populated with the appropriate settings EU St...

Страница 41: ...level 4 Is used to change a Gamewell FCI panel s IP address Node Map Refer to Node Mapping on page 34 for more information about mapping nodes 5 3 Menu Descriptions 5 3 1 File Login Is used to gain ed...

Страница 42: ...FocalPoint Gateway Config Tool Reference Information Menu Descriptions 42 FocalPoint Gateway Installation Operation Manual P N 52649 Rev B3 2 11 10...

Страница 43: ...RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHA...

Страница 44: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com...

Отзывы: