Panel Switches
Programming/Operation Instructions
4.2 Panel Switches
Figure 4.2.1 illustrates the LED Panel Switches. Table 4.2.1 lists the LED Panel Switches.
Figure 4.2.1 Led Panel Switches
Designation
Comments
Alarm Acknowledge
Silences the panel audible sounder. This switch must be pressed
once for each Alarm condition present in the system.
Trouble
Acknowledge
Silences the panel audible sounder. This switch must be pressed
once for each Trouble or Supervisory condition present in the sys-
tem.
Signal Silence
Press once and any outputs programmed as silenceable will be
deactivated.
(All applicable silence LEDs will light). A second activation will re-
activate the previously silenced outputs. This switch only functions
if an Alarm or Supervisory condition exists in the system.
Lamp Test/Reset
Press momentarily and all LEDs (including all elements in the
display) will light momentarily. Press and hold to reset the system.
Menu/Back
Used in programming. The display will prompt the operator as to
which function applies. “Menu” is pressed to initially put the 7100
into programming mode. The “Back” function will step the operator
out of the programming mode one element at a time.
BKSP/Edit
Used in programming. The display will prompt the operator as to
which function applies.
OK
Accepts any changes made in the programming field.
Alphanumeric Keys
These 12 keys allow the user to choose a specific point address
by using the numbers for point sensitivity reading, disabling an
address, etc.
Press each key the number of times necessary to display
the correct character on the display.
Example: Pressing the “2” key,
Once will display the letter “A”
Twice will display the letter “B”
Three times will display the letter “C”
Four times will display the number “2”
PK-625 Key Switch
This key switch is keyed alike with the door lock, and must
be operated in order to activate the keypad.
Table 4.2.1 LED Panel Switches