1-1.5m
Water drainage pipe
(Wrong)
(Correct) More than 1/100
slope
Sponge
(gray)
Drainage hose 1
Clamp 2
Less than 4mm
Big sponge 10
(accessory)
Clamp 2
(accessory)
Roof
1-1.5m
within 300mm
Pendant rack base
Drainage lift pipe
Ceiling
220mm
Less than 280mm
Clamp 2 (accessory)
Drainage hose 1
(
accessory)
T-coupler mix drainage hose
More than 100mm
Drainage pipe diameter should be
more than or equal to the diameter
of the connection tube. (Polyethyl-
ene; size: outer diameter 25mm,
wall thick
1.5m).
To ensure fluent drainage,drain-
age pipe should be short, the slope
should be at least 1/100.
If there is no way to ensure
enough slope for the hose, the
drainage lift pipe must be installed.
In order not to twist the drainage
hose, there must be 1~1.5m be-
tween the pendant rack.
Use auxiliary drainage hose and
clamp.
Insert drainage hose into the drain-
age plug, then tighten the clamp.
Wrap the drainage hose clamp
with big sponge. Insulate the in-
door drainage hose.
The installation height of the drain-
age lift pipe should be less than
280mm.
The drainage lift pipe should be
vertical to the unit, the distance to
the unit should be less than
300mm.
The slope of the auxiliary drainage
hose should be within 75mm,
which can alleviate the force taken
by the drainage plug.
If several drainage hoses are to
have a confluence, please install
in accordance with the following
procedures.
The specifications of the mix drain-
age hose should be suitable to the
operation capacity of the unit.
CAUTION!
1.
Install water drainage pipe