© Galvin Engineering Pty Ltd
Product Installation Guidelines
Version 1, 11 January 2022, Page
3
of 5
ADJUSTMENT OF MIX TEMPERATURES (TAP)
.
1. Close the valve
2. Remove top cap, screw
and handle, ensure that
the cartridge is closed.
3. Remove the upper brass ring
(closure setting ring).
Make sure the
control rod doesn’t rotate.
.
4. Remove the lower brass ring
(temperature setting ring) and
rotate the brass ring clockwise
to increase temperature or anti-
clockwise to decrease.
5. Reposition the upper ring
in the same position
– up
against the stop.
6. Test the set temperature. If the
temperature is acceptable, reposition
the handle (section 6.1), the screw
and the top cap otherwise repeat
from step 3 to 6.
UPPER RING
LOWER RING