Operation and Installation Manual
© All rights reserved - Galmet Sp. z o.o. Sp. K.
28
3. Installation
3.13. Connecting the condensate drain
The condensate drain pipe is located at the bottom of the heat pump. The condensate must be drained e.g. to a sewer water trap or a floor drain.
3.14. Installation of air ducts
The temperature of the flowing air may be lower than the temperature in the room, therefore it is recommended to insulate the pipes in order to eliminate
the condensation of steam.
max dł. przewodu 5 m
nominalny przepływ 350m³/h
ø 160 mm
max dł. przewodu 5 m
nominalny przepływ 350m³/h
ø 160 mm
45°
Ø 160 mm
Ø 200 mm
Ø 160 mm
Ø 200 mm
Maximum air duct length - 5 m
nominal flow - 261 m
3
/h
Maximum air duct length - 5 m
nominal flow - 261 m
3
/h
The length of the straight inflow and outflow ducts must not exceed 5 m. Each 90° bend shortens the length by 2 m. If the recommended
length of the duct is exceeded it is necessary to use an appropriate fan to support the air flow. It is recommended to use smooth ducts, as
corrugated dusts may cause too much air resistance.