3. Installation
3.1. Heat pump indoor installation
The unit is intended for indoor installation only. The heat pump must not be installed without a sufficient service access to the compressor unit. The
minimum clearance from the wall shall be 40 cm. If the unit is installed without an air discharge duct connected to an air exhaust unit, provide a minimum
indoor ventilation air flow within 261 m
3
/h.
The minimum installation height between the air intake and the air exhaust of the ductwork must be 1.5 m!
The length of the straight runs of the air supply (suction side) and air discharge (pressure side) shall not exceed 5 m each. Each 90° duct bend
reduces the straight run by 2 m. Smooth ducts are recommended. Spiral/corrugated ducts may cause an excessive air flow resistance.
3.2. Connecting the heat pump to the DHW tank with the heat coil