12

ACCESSORIES

KSC - Condensate removal kit

This device allows to overcome displacements
in the condensate drain.
The pump can drain water up to 8 l/h and it is
completed by a non return valve on the
discharge side.

BP - Kit batterie di post
riscaldamento

BP 1 or 2 row reheating exchangers
are designed for installation on the air
outlet of the UTN air conditioning and
thermal ventilating units.
NOTE:
The BP module has holes like those
on the machine air intake, on the extremity
turned toward the air outflow ducts. This allows you to attach all the
accessories that can be directly applied on the machine (PCOC, PCOF,
GAT, etc…).

RE - Supplementary heating elements

Useful as heating integration to the hot
water system, the RE kit is made of an
electric heater  with safety thermostat
(automatic and manual resetting) and
power relay.
The RE electric heater kit has to be matched
with the  MICROPRO-D control panel and
with the IPM power board.

PA90 - Outdoor air inlet motorized
louver

The outdoor air inlet motorized louvre
is intended for replacing the air in
the room directly from the air-
handling unit. The amount of outdoor
air that will be let into the room, after
having been filtered and treated
thermally, may be regulated
proportionally from 0 to 100% by
means of a servomotor controlled
by a rotary potentiometer that is inside the specific CSD control, which is
designed for flush wall-mounting installations.
Kit PA90, as shown in figure (1), essentially comprises the following
components:
A) Outdoor air inlet louvre made of galvanized steel sheet and setup for being
connected to the machine, at one end, and to the other required accessories.
B) Servomotor connected directly to the louvre’s baffle, with a protection
rating of IP54 and power supply of ~ 24V. The louvre may be opened or
closed automatically at the signal of the external auxiliary contacts (not
supplied) such as antifreeze thermostats, timers, etc., with the possibility
of connecting multi-servomotors in parallel to an individual opening-closing
control.
C) 230V - 24V voltage transformer, complete with support terminal strip
housed inside the specific electrical box, which functions as a mechanical
protection for preventing the access to the connecting terminal strip and to
the transformer itself.
D) Self-threading fixing screws.

GA / GAT - Vibration dampers

Manufactured in galvanized sheet
steel, the GA/GAT connection
panels are used to connect to
rectangular ducts equipped with
flanges and other flanged
accessories.
They are made up of a rectangular
panel that is to be secured to the
machine or to another accessory
with similar drilling (i.e. MAF,
MAFO, RE etc...) coupled by means of a flexible bellow to a flanged sleeve
that rapresents the starting point for rectangular ducts of the type commonly
used in distribution plants.
If the vibration damping joint is used together with the electrical heating
elements module (accessory RE) a GAT joint made of heat-resistant silicone
material is to be fitted on the delivery line.

TFA - Not insulated flexible ducts

Uninsulated flexible duct for the connections to the air distribution with 

φ

200 mm diameter, supplied in 6 m lenght undivisible.

TFM - Insulated flexible ducts

Insulated flexible duct for the connections to the air distribution with 

φ

200 mm diameter, supplied in 6 m lenght undivisible. The insulation of
the duct is optained by means of fiberglass, thickness 25 mm with 16
Kg/m

density.

TP - Plastic cap

Plastic cap 

φ

 200 mm for the closing on the PCOF, of the air outlet not used.

CA / CAF - Air inlet plenum box

Intake Plenum box in galvanised sheet metal
complete with circular collars (Ø 200 mm)
for the connection, by means of hoses and
intake grids with fixed fins, to pocket type
structures, to increase the free air flow cross
section.
Sized to be adaptable to the modular structure
of the ceiling panels, they are equipped with
2 or 3 circular collars so that they can be connected, following their suitable
combination, to all the heater fans of the UTN range. The CA version is
equipped with just the grid alone whereas the CAF version is also equipped
with a flat filter in acrylic material, with filtering rating G2, housed in the
standard frame. The filter of this second type of intake box can be serviced
(cleaned) on a periodic basis without having to access the unit fitted behind
the ceiling panels or in a service room.

GM - Alluminium air outlet grille

Air delivery grids with double row of adjustable
fins in anodised aluminium, equipped with
galvanised sheet metal frame that is used to
wall-mount the grids or to fit them directly on
the delivery head of the machine.
The galvanised sheet metal frame is drilled at
one end so that it can be secured directly to
the delivery head of the heater fan (or to accessories such as the additional
RE electrical module).

GR - Alluminium air inlet grille

Air intake grids with single row of fins in anodised
aluminium, equipped with galvanised sheet metal
frame that is used to wall-mount the grids or to fit
them directly on the intake head of the machine.
The galvanised sheet metal frame is drilled at one
end so that it can be secured directly to the intake
head of the heater fan (or to accessories such as the
MAF and MAFO filtering units).

Содержание UTN Series

Страница 1: ...GB high pressure fan coils technical manual...

Страница 2: ...lares under its own exclusive responsibility that the UTN range of air conditioning and hot air heating units heating and conditioning equipment for systems that distribute air through channels comply...

Страница 3: ...room thermostat TA2 Electromechanical room thermostat with summer winter selection CSD Wall mounted control for proportional opening and closing of the motor driven air intake louver AIR SUCTION MODUL...

Страница 4: ...0 20 17 29 26 28 19 30 24 38 50 DF heating capacity 4 pipes High kW 4 01 4 01 5 63 5 63 8 24 8 24 11 50 11 50 19 70 19 70 26 20 26 20 Water flow l h 353 353 496 496 726 726 1013 1013 1735 1735 2309 23...

Страница 5: ...1489 1422 1351 1274 1191 1101 999 881 734 1 m 3 h 1495 1451 1405 1358 1308 1256 1201 1143 1081 1015 942 862 770 661 515 3 m 3 h 2304 2242 2178 2112 2043 1972 1897 1819 1737 1650 1557 1457 1348 1227 10...

Страница 6: ...5 1249 1167 1078 977 860 714 1 m 3 h 1477 1433 1388 1340 1291 1239 1185 1127 1066 1000 928 849 758 649 504 3 m 3 h 2248 2187 2124 2059 1992 1922 1848 1772 1691 1605 1514 1416 1309 1189 1053 2 m 3 h 17...

Страница 7: ...Pa 1 3 3 5 6 7 9 11 13 15 17 20 22 GR Pa 2 4 5 7 9 12 14 17 21 24 28 32 37 GM Pa 1 1 1 2 2 3 4 4 5 6 7 Qa m3 h 400 500 600 700 800 900 1000 1100 1200 1300 1400 1600 1800 2000 2200 2400 2600 2800 3000...

Страница 8: ...POWER LEVELS FOR OCTAVE BAND Legend Psu Available static pressure LWA A weighted sound power Vr Fan speed 3 high 2 medium 1 low 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz LwA Vr dB dB dB dB...

Страница 9: ...4410 0 247 12 3870 3870 0 185 7 3550 3550 0 169 6 1400 6770 5400 0 323 19 5840 5040 0 279 14 4370 4370 0 208 9 4010 4010 0 191 7 1600 7470 6040 0 356 22 6470 5650 0 308 17 4830 4830 0 230 10 4440 4440...

Страница 10: ...17 5460 4790 0 260 13 4230 4230 0 202 8 1400 7970 6160 0 380 25 7090 5820 0 338 20 6150 5470 0 293 16 4760 4760 0 227 10 1600 8790 6890 0 419 30 7820 6520 0 373 24 6800 6130 0 324 19 5260 5260 0 251 1...

Страница 11: ...314 15 8290 0 201 7 10690 0 261 10 14400 0 177 5 1000 7720 0 374 20 9850 0 239 9 12730 0 310 14 17100 0 210 7 1200 8880 0 430 26 11300 0 274 11 14630 0 356 17 19590 0 240 8 1200 7920 0 383 21 10030 0...

Страница 12: ...290 13 8290 0 201 7 10690 0 261 10 14400 0 177 5 1000 7130 0 345 18 9850 0 239 9 12730 0 310 14 17100 0 210 7 1200 8200 0 397 22 11300 0 274 11 14630 0 356 17 19590 0 240 8 1200 7310 0 354 18 10030 0...

Страница 13: ...485 15 12540 0 304 6 16450 0 401 10 21690 0 266 5 2500 11530 0 558 19 14400 0 350 8 18920 0 461 13 24900 0 305 6 3000 12900 0 624 23 16080 0 390 10 21150 0 515 16 27790 0 341 7 60 50 70 60 90 70 20 50...

Страница 14: ...to avoid moisture formation Keep free space around the fan coil to allow proper operation of the unit and ordinary and extraordinary maintenance Install the remote control panel if any in a position t...

Страница 15: ...1 D 208 45 C 15 D 15 32 208 40 280 5 280 40 173 67 C 15 D 15 2 3 7 7 3 2 4 A B C D UTN 06 754 707 676 646 UTN 08 754 707 676 646 UTN 12 964 917 886 856 UTN 16 1174 1127 1096 1066 9 DIMENSIONAL DATA 1...

Страница 16: ...AIR DELIVERY 6A 17 6B 88 375 170 718 B 23 A 23 D 227 45 15 D 15 C 45 352 275 32 15 D 15 C 74 198 294 208 273 392 365 473 523 617 135 204 28 53 17 188 165 100 57 215 294 208 273 392 382 506 510 579 98...

Страница 17: ...lied M fan motor RD red low speed TA room thermostat WH white common N L S RL 4 1 2 3 4 5 6 7 8 9 WH BK GY BU RD 1 230 1 50 IL F CD CN GNYE M TC 10 2 UTN with CD remote three speed selector and TC fan...

Страница 18: ...erface accessory IL mains switch not supplied M fan motor RD red low speed WH white common 230 1 50 9 8 7 6 5 4 M 1 GNYE L N F IL 2 1 N N RF c S RL 4 1 2 3 CN CD TA2 RD BU GY BK WH T SF 10 4 UTN with...

Страница 19: ...low speed SF Centralised mode selector not supplied TA room thermostat TC fan stop thermostat WH white common L IL F N 9 8 7 6 5 4 M 1 SF CN RD BU GY BK WH 9 8 7 6 5 4 M 1 CN RD BU GY BK WH 1 2 3 4 5...

Страница 20: ...C 9 8 7 6 5 4 CN M 1 WH BK BU GY RD 230 1 50 TC SF ACC T TDC GNYE 10 8 UTN units with TDC wall mounted control with speed selector and electromechanical thermostat BK black high speed BU blue medium s...

Страница 21: ...m speed IL mains switch not supplied M fan motor RD red low speed SF centralised mode selector not supplied TD4T wall mounted control with speed selector electromechanicalthermostatandsummerwintersele...

Страница 22: ...l p a n e l f o r t h e a u t o m a t i c c o n t r o l o f t h e f a n c o i l R D r e d l o w s p e e d S A R o o m t e m p e r a t u r e p r o b e f o r a u t o m a t i c f a n s p e e d s e l e c...

Страница 23: ...R O D W a l l m o u n t e d m i c r o p r o c e s s o r c o n t r o l p a n e l R C H R e m o t e s w i t c h f o r t h e c e n t r a l i z e d c o o l i n g h e a t i n g m o d e s e l e c t i o n n...

Страница 24: ...o d e b y m e a n s o f f a n s t a rt s t o p a t a m a n u a l l y s e t t e m p e r a t u r e T D C W a l l m o u n t e d c o n t r o l w i t h s p e e d s e l e c t o r a n d t h e r m o s t a t W...

Страница 25: ...ls for in built MICROPRO and wall MICROPRO D installation complete with fan speed selector electronic thermostat and cooling heating mode selector for the automatic control of the fan working on the v...

Страница 26: ...tc coupled to a flanged sleeve that represents the starting point for rectangular ducts of the type commonly used in distribution plants PCOF Connecting panel to flexible ducts Manufacturedingalvanise...

Страница 27: ...ther flanged accessories They are made up of a rectangular panel that is to be secured to the machine or to another accessory with similar drilling i e MAF MAFO RE etc coupled by means of a flexible b...

Страница 28: ...d maintenance Pay utmost attention during the maintenance operations accidentally coming into touch with some of the metallic parts might cause injuries therefore wear safety work gloves Every time th...

Отзывы: