10 TECHNICAL
FEATURES
10.1
WATER CHILLERS RATED TECHNICAL DATA
*
W
eights refer
red to version including pump and buffer tank
-
Cooling capacity: outdoor air temperature 35°C, water temperature 12°C / 7°C
-
Sound power level measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
-
Sound pressure level measured at a distance of 10 m and a height of 1.5 m above the ground in a free field (fan side).
-
The maximum electrical input is the mains electricity that must be available in order for the unit to work.
-
The maximum cur
rent absorption refers to the cur
rent that will trigger the inter
nal safety devices of the unit. It is the ma
ximum cur
rent allowed in the unit. This value may never be exceeded; it must
be used as a reference for deter
m
ining the size of the power supply line and the related safety devices (refer to the wiring di
agram supplied with the units).
MPE-
C
004 M
005 M
007 M
008 M
008
010 M
010
013
015
018
020
024
027
028
P
ower supply
V-ph-Hz
230-1-50
230-1-50
230-1-50
230-1-50
400-3-50
230-1-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
400
-3-50
Cooling capacity
kW
4,1
5,1
6,7
8,4
8,4
9,3
9,3
12,9
15,0
17,2
19,6
23,8
26,6
28,1
MPE CB T
otal power input
kW
1,3
1,7
2,3
3,3
3,1
3,2
3,2
4,2
5,2
6,3
7,1
8,1
9,3
8,7
EER
3,1
3,0
3,0
2,5
2,7
2,9
2,9
3,1
2,9
2,7
2,8
2,9
2,9
3,2
ESEER
3,5
3,4
3,3
3,0
3,4
3,4
3,4
3,7
3,5
3,3
3,2
3,4
3,4
3,8
MPE CP C
S T
otal power input
kW
1,5
1,8
2,4
3,5
3,2
3,6
3,6
4,5
5,5
6,7
7,5
8,5
9,7
9,2
Maximum power input
kW
2,0
2,3
3,0
5,0
5,0
5,1
7,2
8,9
10,5
12,5
13,6
14,5
18,0
18,3
Maximum cur
rent absorption
A
9,8
11,6
15,3
24,2
9,2
26,3
14,4
17,4
20,0
24,3
26,2
27,6
33,6
35,5
Star
ting absorbed cur
rent
A
38
44
63
98
49
99
50
65
68
75
104
158
132
133
n° of compressors / circuits
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 / 1
1 /
1
R
efrigerant charge
kg
1,5
1,5
2,0
2,1
2,1
2,9
2,9
4,0
4,1
3,7
4,2
5,8
6,0
7,5
Low/high pressure switch
bar
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2 / 42
2
/ 42
2 / 42
n
° o
f a
xi
al
fa
n
11111222244442
Air flow
m
3/h
3.635
3.635
3.406
3.406
3.406
7.385
7.385
6.939
6.939
9.990
9.990
9.307
9.307
16.276
W
ater flow
l/h
707
877
1.146
1.445
1.445
1.591
1.591
2.219
2.577
2.958
3.373
4.094
4.575
4.833
D
ia
m
et
er
o
f h
yd
ru
al
ic
c
on
ne
ct
io
ns
po
llic
i
11111
1 1
/4
1 1
/4
1 1
/4
1 1
/4
1 1
/4
1 1
/4
1 1
/4
1 1
/4
1 1
/4
W
ater side pressure drop
kP
a
24666
34
34
61
38
51
51
49
34
40
A
vailable pressure head
kP
a
63
61
57
53
53
116
116
83
103
129
123
116
124
143
W
ater content escluding optionals
dm3
1,5
1,5
1,5
1,5
1,5
3,0
3,0
3,0
3,0
4,0
4,0
4,0
4,0
5,5
E
xp
an
si
on
ta
nk
dm
3
11111555555558
Buffer tank
dm3
20
20
20
20
20
30
30
30
30
50
50
50
50
125
Height
m
m
758
758
758
758
758
1250
1250
1250
1250
1300
1300
1300
1300
1485
Length
mm
960
960
960
960
960
1220
1220
1220
1220
1565
1565
1565
1565
1990
Depth
mm
450
450
450
450
450
560
560
560
560
600
600
600
600
950
Sound power level
dB(A)
66
66
67
67
67
69
69
69
69
71
71
72
72
73
Sound pressure level
dB(A)
38
38
39
39
39
41
41
41
41
43
43
44
44
45
T
ranspor
t weight *
kg
98
100
107
110
110
202
202
209
209
260
260
280
285
370
Operating weight *
kg
92
94
101
104
104
228
228
235
235
306
296
327
332
492