The maximum input power is the mains power that must be available in order for the unit to work.
-
The maximum cur
rent absorption refers to the cur
rent that will trigger the inter
nal safety devices of the unit. It is the max
imum cur
rent allowed in the unit
This value may never be exceeded; it must be used as a reference for deter
m
ining the size of the power supply line and the rel
ated safety devices
(refer to the wiring diagram supplied with the units). Cross-section area of cables: 4 A/mm2 approx.
3
PLUMBING AND ELECTRICAL CONNECTIONS
3.3 ELECTRICAL
DATA
MPE
004M
005M
007M
008 M
008
010 M
010
013
015
018
020
024
027
028
Maximum power input
kW
2,0
2,3
3,0
5,0
5,0
5,1
7,2
8,9
10,5
12,5
13,6
14,5
18,0
18,3
Maximum cur
rent absorption
A
9,8
11,6
15,3
24,2
9,2
26,3
12,3
15,4
18,0
21,7
21,7
24,0
28,6
28,6
Star
ting absorbed cur
rent
A
38
44
63
98
49
99
50
65
68
75
104
158
132
133
F
an motor rated power
kW
0,135
0,135
0,135
0,135
0,135
0,135
0,135
0,135
0,135
0,135
0,135
0,135
0,135
0,320
F
an motor rated cur
rent
A
0,64
0,64
0,64
0,64
0,64
0,64
0,64
0,64
0,64
0,64
0,64
0,64
0,64
1,75
Pump motor rated power
kW
0,14
0,14
0,14
0,14
0,14
0,37
0,37
0,37
0,37
0,37
0,37
0,37
0,37
0,55
Pump motor rated cur
rent
A
0,58
0,58
0,58
0,58
0,58
2,00
2,00
2,00
2,00
2,00
2,00
2,00
2,00
3,00
P
ower supply
V/f/Hz
Auxiliar
y power supply
V/f/Hz
P
ower cables
mm2
4,0
4,0
6,0
6,0
4,0
6,0
4,0
4,0
4,0
6,0
6,0
10,0
10,0
10,0
PCD connecting cables
mm2
PCDS connecting cables
mm2
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
Safety fuse F
A
16,0
16,0
20,0
25,0
10,0
32,0
16,0
20,0
20,0
25,0
25,0
32,0
32,0
32,0
Circuit breaker IL
A
20,0
20,0
25,0
25,0
16,0
32,0
20,0
25,0
25,0
25,0
25,0
32,0
32,0
32,0
MPE
032
035
040
054
066
T30
T34
T40
T45
T54
T61
T69
T76
Maximum power input
kW
18,9
21,8
22,4
22,7
23,3
20,9
24,4
26,6
30,8
27,0
30,0
32,0
39,0
Maximum cur
rent absorption
A
32,4
35,2
36,4
45,2
46,2
39,9
45,9
49,7
56,7
48,0
53,0
57,0
69,0
Star
ting absorbed cur
rent
A
166
161
163
163
165
86
96
127
130
177
187
202
229
F
an motor rated power
kW
0,320
0,320
0,320
0,610
0,610
0,320
0,320
0,320
0,320
0,400
0,400
0,400
0,400
F
an motor rated cur
rent
A
1,75
1,75
1,75
2,65
2,65
1,75
1,75
1,75
1,75
1,80
1,80
1,80
1,80
Pump motor rated power
kW
0,55
0,55
0,55
0,90
0,90
0,55
0,55
0,55
0,55
1,30
1,30
1,30
1,30
Pump motor rated cur
rent
A
3,00
3,00
3,00
4,90
4,90
3,00
3,00
3,00
3,00
5,90
5,90
5,90
5,90
P
ower supply
V/f/Hz
Auxiliar
y power supply
V/f/Hz
P
ower cables
mm2
10,0
10,0
10,0
16,0
16,0
10,0
16,0
16,0
16,0
16,0
16,0
16,0
25,0
PCD connecting cables
mm2
PCDS connecting cables
mm2
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
1,0
Safety fuse F
A
32,0
40,0
40,0
50,0
50,0
40,0
50,0
63,0
63,0
63,0
63,0
63,0
80,0
Circuit breaker IL
A
40,0
40,0
50,0
63,0
63,0
50,0
50,0
63,0
63,0
63,0
63,0
63,0
80,0