WATER AND ELECTRICAL CONNECTIONS

3.2 ELECTRICAL 

CONNECTIONS

Warning

 

 the filters associated with the inverter (in order to minimize 

emissions and at the same time to ensure that the unit complies with the 
EMC Directives) produce earth leakage. This may cause the differential safety 
switch to trip It is recommended to install an additional calibratable differential 
switch, dedicated to the unit supply line only.

All operations must be performed by qualified service personnel in accordance 
with current laws and regulations. For any electrical work on the unit, refer 
to the electric diagrams supplied with the unit.
It is recommended to make sure that:
- The characteristics of the mains power supply are adequate for the electrical 
inputs specified in the table of electrical data.

Warning 

Before carrying out any job on electrical parts, make sure 

the power supply is disconnected. Check also that the mains electricity 
supply is compatible with the specifications (voltage, number of phases, 
frequency) shown on the unit rating plate. The supply voltage may not 
undergo fluctuations exceeding ±5% of the rated voltage. The electrical 
connections must be made in accordance with the wiring diagram 
provided with the unit and the regulations in force.

Warning 

Never attempt to modify internal electrical connections: 

any undue modifications will immediately invalidate the warranty.

Important!

Upstream from the electrical control panel it is mandatory to 

use an omnipolar thermomagnetic circuit breaker complying with IEC-EN 
standards (contact gap of at least 3 mm), with an adequate breaking 
capacity and differential protection based on the electrical data table 
shown below, installed as close as possible to the unit.
For the unit power supply line use H07RN-F- type flexible cables having 
the cross sectional area shown in the table.

HWMC 

 

  010M 013 018 023 029 

Cross-section area of power cables  

mm

2  

4 6 6 10 10 

Safety fuse 

  20 25 25 32 32 

Main switch 

IL 

  20 25 25 40 40 

To route the cables use sheaths and conduits suitable for outdoor 
installation.
You must provide a switch with a delayed fuse meeting the specifications 
indicated in the table.

Important!

Upstream from the electric control board, you must provide a 

switch with a delayed fuse meeting the specifications indicated in the table.

To access the electric control board it is necessary to remove the inspection 
panel (figure 4) by taking out the screws; introduce the power cable into the 
unit through the bushing on the side panel; then bring it to the electric control 
board through the cable holder provided.

Important!

Tighten the wires securely to the terminals and clamp the 

cable in place with the cable holder (figure 5).

Important!

To maintain the IP protection rating a cable gland compatible 

with the diameter of the sheath or power cable must be fit in the hole 
on the side panel of the unit.

Important!

Make sure that the length of cable inside the unit enters 

the bushing from below: this is necessary to prevent rainwater from 
dripping inside the unit.

Important!

 An earth connection is mandatory: connect the earthing 

wire to the terminal provided on the electric control board (see the 
electric control board layout supplied with the unit ), marked 

Important!

If you wish to include:

-  a remote on/off switch
-  a remote switch for changing over
-  a remote control

it is a good idea to do so at this stage of the installation procedure, by 
connecting the switches or the remote control (accessory) to the electric 
control board terminals as directed in section 3.3 and using the unit wiring 
diagram as your reference.

Содержание HWMC 10 EC

Страница 1: ...HWMC 10 kW 29 kW Total heat recovery reversible multi purpose heat pumps DC INVERTER INSTALLATION USE AND MAINTENANCE MANUAL GB...

Страница 2: ...recovery 29 5 4 Operating limits only in DHW production 29 5 5 Thermal carrier fluid 29 6 CONTROL AND SAFETY DEVICES 30 6 1 Control devices 30 6 1 1 Service thermostat 30 6 1 2 Control device settings...

Страница 3: ...Galletti S p A via L Romagnoli 12 a 40010 Bentivoglio BO Italia The unit data are reported on the rating label in this page THE LABEL SHOWS THE FOLLOWING DATA Series and size of the unit Date of manuf...

Страница 4: ...ll not accept any liability for injury or damage resulting from improper use of the equipment or failure to comply with the directions provided in this manual and on the unit itself It is mandatory to...

Страница 5: ...tioning as a traditional heat pump air evaporation on the heat exchanger side and water condensation on the dedicated plate heat exchanger on the system side 4 Domestic hot water production in wintert...

Страница 6: ...system DHW side 5 2 EC pumps system DHW side 6 Field 3 Inertial buffer tank 0 Absent 0 Present system side S Field 4 Auxiliary contacts 0 Absent 0 User tank sensor 1 External electric heating element...

Страница 7: ...7 HWMC HWMC 10 EC PUMPS All copying even partial of this manual is strictly forbidden RG66008809 Rev 00 1 THE SERIES HWMC 1 3 DESCRIPTION OF COMPONENTS Description 12 Circulation pump HWMC 10 EC PUMPS...

Страница 8: ...Fan 4 Water differential pressure switch no 1 fan compartment 5 Automatic air vent valve 6 Expansion tank fan compartment 7 Buffer tank 8 Refrigerant solenoid valve 9 Electronic thermostatic valve 10...

Страница 9: ...9 HWMC HWMC 13 18 EC PUMPS All copying even partial of this manual is strictly forbidden RG66008809 Rev 00 1 THE SERIES HWMC 1 3 DESCRIPTION OF COMPONENTS Description 12 Circulation pump...

Страница 10: ...3 Fan 4 Water differential pressure switch no 1 fan compartment 5 Automatic air vent valve 6 Expansion tank fan compartment 7 Buffer tank 8 Refrigerant solenoid valve 9 Electronic thermostatic valve 1...

Страница 11: ...23 29 FANS HWMC 23 29 EC PUMPS All copying even partial of this manual is strictly forbidden RG66008809 Rev 00 1 THE SERIES HWMC 1 3 DESCRIPTION OF COMPONENTS Description 12 Circulation pump HWMC 23...

Страница 12: ...exchanger 3 Fan 4 Water differential pressure switch 5 Automatic air vent valve 6 Expansion tank fan compartment 7 Buffer tank 8 Refrigerant solenoid valve 9 Electronic thermostatic valve 10 Water saf...

Страница 13: ...DIAGRAMS HWMC EVAPORATOR AND PUMP HWMC EVAPORATOR Legend VR Filling valve VS Safety valve EV Evaporator PD Differential pressure switch MA Water pressure gauge VAS Air vent valve VE Expansion tank P P...

Страница 14: ...ifferential pressure switch MA Water pressure gauge VAS Air vent valve VE Expansion tank P Pump RS Drainage valve RC Water filling cock VU Check valve SA Buffer tank 1 THE SERIES HWMC 1 4 PLUMBING DIA...

Страница 15: ...ND DUAL PUMP HWMC EVAPORATOR DUAL PUMP AND TANK Legend VR Filling valve VS Safety valve EV Evaporator PD Differential pressure switch MA Water pressure gauge VAS Air vent valve VE Expansion tank P Pum...

Страница 16: ...r removing the unit from the pallet handle it gently without applying excessive pressure on the side panels finned coil and fan grille You should collect and separate the packing materials wood cardbo...

Страница 17: ...male 3 Water outlet 1 female 2 Sanitary hot water outlet 1 female 5 Safety valve discharge outlet with rubber ring holder 6 Water supply male optional tap 7 Water drainage female 8 Sanitary hot water...

Страница 18: ...le 3 Water outlet 1 female 2 Sanitary hot water outlet 1 female 5 Safety valve discharge outlet with rubber ring holder 6 Water supply male optional tap 7 Water drainage female 8 Sanitary hot water dr...

Страница 19: ...e section on installation clearance requirements This device is not intended to be used by children or by people with physical sensoryormentalimpairments exceptundersupervision Make sure that children...

Страница 20: ...anual is strictly forbidden RG66008809 Rev 00 2 INSPECTION HANDLING DIMENSIONS AND SITING 2 4 SITING 2 4 1 INSTALLATION CLEARANCE REQUIREMENTS COIL PLUMBING CONNECTION SIDE ELECTRIC CONTROL BOARD COIL...

Страница 21: ...ven partial of this manual is strictly forbidden RG66008809 Rev 00 2 INSPECTION HANDLING DIMENSIONS AND SITING 2 5 POSITIONING OF VIBRATION DAMPERS ACCESSORY HWMC NO OF VIBRATION DAMPERS 10 18 4 23 29...

Страница 22: ...ANDATORY on the pipes feeding the unit in proximity to the latter a mechanical filter supplied as standard FM MANDATORY and a check valve VNR on the supply line upstream from the filling tap RC an air...

Страница 23: ...ontinue filling until the pressure gauge reading is 1 5 bars Warning Heating cooling system circuit and domestic hot water system circuit are separated To fill the DHW system use a heat storage tank b...

Страница 24: ...DHW must be connected directly to the buffer tank without interposed coil in this way the water content of the buffer tank will be sufficient to ensure the proper operation of the unit heat transfer t...

Страница 25: ...table shown below installed as close as possible to the unit For the unit power supply line use H07RN F type flexible cables having the cross sectional area shown in the table HWMC 010M 013 018 023 02...

Страница 26: ...als of the electric control panel at the terminals 50 24V where an interface with a voltage free contact is desired a relay must be fitted by the installer DIAGRAM SHOWING HWMC ELECTRICAL CONNECTIONS...

Страница 27: ...roperlymadeaccording to the indications given on the plates to be found on the unit itself water inlet water outlet etc Make sure that the pump is not blocked Make sure that the water circuit is duly...

Страница 28: ...mp min max min max Inlet water temperature C 8 20 1 25 42 Outlet water temperature C 5 19 28 58 2 Water temperature differential C 3 8 3 8 Outdoor air temperature C 10 3 48 10 35 1 For transitory peri...

Страница 29: ...0 30 40 Air temp C DHW out water temp C All copying even partial of this manual is strictly forbidden RG66008809 Rev 00 5 OPERATING LIMITS 5 3 OPERATING LIMITS IN DHW TOTAL HEAT RECOVERY 5 4 OPERATING...

Страница 30: ...approximately 5 minutes 6 1 2 CONTROL DEVICE SETTINGS Control devices Set point min max differential Service thermostat C 7 5 15 2 outlet water temp cooling mode Service thermostat C 45 25 53 2 outlet...

Страница 31: ...hen working in proximity to finned coils since the aluminium fins are extremely sharp and can cause cuts Warning Never attempt to access internal parts of the unit without having first disconnected it...

Страница 32: ...W kW 13 00 17 20 25 00 29 70 40 00 Total COP 6 99 7 29 6 29 7 02 6 43 Heating mode system DHW Heating capacity 2 kW 11 40 14 90 21 50 25 60 33 70 Power input 2 kW 3 44 4 34 7 51 8 05 12 00 COP 3 30 3...

Страница 33: ...ss 8 Solenoid valve 9 High pressure switch 10 Low pressure switch 11 High pressure gauge 12 Low pressure gauge 13 Service connection 14 Differential pressure switch 15 Check valve 16 4 way valve 17 Li...

Страница 34: ...V1 V2 All copying even partial of this manual is strictly forbidden RG66008809 Rev 00 10 COOLING CIRCUIT DIAGRAMS 10 1 BASIC COOLING CIRCUIT LAYOUT OF HWMC CHILLING UNITS WITH ELECTRONIC VALVE DHW SI...

Страница 35: ...opying even partial of this manual is strictly forbidden RG66008809 Rev 00 10 COOLING CIRCUIT DIAGRAMS 10 2 COOLING CIRCUIT LAYOUT OF HWMC 10 29 CHILLING UNITS WITH ELECTRONIC VALVE DHW SIDE SYSTEM SI...

Страница 36: ...X X U Antifreeze Alarm circuit 1 Not enabled by antifreeze thermostat Check the water temperature Checking the antifreeze setting X X S Evaporator Inlet Temp Sensor Alarm Antifreeze sensor defective...

Страница 37: ...e dirt from the coil X S LOW Pressure Alarm trig gered by sensor circuit 1 Presence of frost on the evapora ting coil See item O X U LOW Pressure Alarm trig gered by sensor circuit 1 Evaporator fan no...

Страница 38: ...S Compressor does not provide the rated heating capacity Check and replace or overhaul X X Liquid filter clogged Replace M The unit works regularly but with an insufficient capacity X X S Low level o...