Trouble Shooting
ISSUE
: THE INVERTER DOES NOT POWER UP OR THERE’S NO DISPLAY
SOLUTIONS
:
Check the breakers inside the
control console.
1.
2.
Check the Emergency Stop button
is released.
3.
Check the contactor.
RELEASED
NOT RELEASED
ISSUE
: AN ERROR COMES UP IN MY INVERTER
SOLUTION
: This is call a “fault”. A fault is a condition that stops the drive. Check in the tables below the most
common fault numbers, types, description and actions to solve the error. First, there are two fault types:
TYPE FAULT
DESCRIPTION
1
Auto-Reset/Run When this type of fault occurs, and A451 [Auto Rstrt Tries] is set to a value greater than
“0”, a user-configurable timer, A452 [Auto Rstrt Delay], begins. When the timer reaches
zero, the drive attempts to automatically reset the fault. If the condition that caused
the fault is no longer present, the fault will be reset and the drive will be restarted.
2
Non-Resetable This type of fault may require drive or motor repair, or is caused by wiring or programing
errors. The cause of the fault must be corrected before the fault can be cleared.