5.3 Battery Charge:   

Fully  charge  the  batteries  of  the  UPS  system  by  leaving  the  UPS 

system  connected  to  the  mains  for  8  hours.  You  may  use  the  UPS 

system directly without charging it but the stored energy time may be 

shorter than the nominal value specified. 

 

5.4 Turn On the UPS:   

(1) With utility power connecting:   

Press “I” button continuously for more than 1 second to turn on the 

UPS. Then the UPS will get into self-test status first. After having 

finishing  the  self-test,  the  UPS  will  get  into  the  inverter  mode,  at 

this time, the LCD screen will light up and indicate the state of the 

UPS.   

(2) Without utility power connecting:   

Even  though  utility  power  is  not  connected  to  the UPS,  the UPS 

still  can  be  turned  on  by  just  simply  pressing  “I”  button 

continuously for more than 1 second. Then the UPS will get into 

self-test  status  first.  After  having  finishing  the  self-test,  the  UPS 

will  get  into  the  inverter  mode,  at  this  time,  the  LCD  screen  will 

light up and indicate the state of the UPS. 

Note: The default setting for bypass mode is no output after UPS 

is connecting utility power and breaker is turned on. This can be 

configured by monitoring the LCD panel or firmware. 

 

5.5 Test Function:   

Test  the  function  of  the  UPS  system  by  either  pressing  the  “On” 

button or disconnecting the input of the UPS system from the power 

supply. 

 

Содержание AP160LCD

Страница 1: ...USER S MANUAL MANUALE UTENTE For Models AP160LCD 1 6KVA Uninterruptible Power System...

Страница 2: ...S 14 5 7 Audible Alarm Mute Function 14 5 8 Operation Procedure of External Battery for Long Backup time Model S Model 14 6 Operating mode for all models 16 6 1 Line mode 16 6 2 Battery mode 17 6 3 By...

Страница 3: ...nzione Muto per l allarme sonoro 47 5 8 Procedura operativa della batteria esterna per modello a tempo di backup esteso Modello S 48 6 Modalit operative per tutti I modelli 49 6 1 Modalit normale Pres...

Страница 4: ...ation openings in the UPS s housing Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in such a way that no one can ste...

Страница 5: ...be operated by any individuals with no previous experience 1 3 Maintenance servicing and faults The UPS operates with hazardous voltages Repairs may be carried out only by qualified maintenance perso...

Страница 6: ...with the same quantity and the same type of batteries Do not attempt to dispose of batteries by burning them It could cause explosion Do not open or destroy batteries Effluent electrolyte can cause i...

Страница 7: ...000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 3 Low Frequency Signals IEC EN 61000 2 2 W...

Страница 8: ...5 2 Description of commonly used symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning...

Страница 9: ...s and powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by the m...

Страница 10: ...verter is off At this moment if Bypass is enabled then the output sockets are supplied with voltage via the bypass if the mains power is available Select Button If the UPS system is No output or Bypas...

Страница 11: ...be displayed from 0 to 999Vac Indicates the frequency value of input Line voltage which could be displayed from 0 to 99Hz Indicates the input Line current value which could be displayed from 0 to 99...

Страница 12: ...ltage value which could be displayed from 0 to 999Vdc Indicates the battery current value which could be displayed from 0 to 99 9A Indicates the battery capacitance percent and every grid represent 25...

Страница 13: ...be attention UPS setting Information The four value of the output voltage could be selected when the UPS is in No output or Bypass mode and only one of them could be active in the same time Derating 1...

Страница 14: ...socket with protection against electric current and pay attention to the capacity of the socket over 10A for 1K S 2K over 16A for 2KS 3K S 2 UPS Output Connection The output of 1K S 2K are socket type...

Страница 15: ...ck whether the wires are securely affixed d Put the small cover back to the rear panel 3 Computer Connection Connect your computer to the outlet sockets of the UPS system following the above diagram C...

Страница 16: ...ndicate the state of the UPS 2 Without utility power connecting Even though utility power is not connected to the UPS the UPS still can be turned on by just simply pressing I button continuously for m...

Страница 17: ...In emergency situation the UPS can be shutdown by taking off the EPO cover on the rear panel of the UPS When you want to turn on the UPS you should restore the cover firstly 5 7 Audible Alarm Mute Fun...

Страница 18: ...the external battery cord to the external battery socket on the rear panel of the UPS to complete the connection procedure and the UPS will start to charge the battery pack 5 The red wire is connected...

Страница 19: ...e by one to decrease the loads connected to the UPS less than 90 of its nominal power capacity Note Please follow the following steps to connect the generator Activate the generator and wait until the...

Страница 20: ...n the front panel is pressed for more than 1 second again the buzzer will stop beeping in silence mode Press the ON button once again for more than 1 second to resume the alarm function 2 The display...

Страница 21: ...y the load is supplied from the utility power via internal filter 6 4 NO output mode The LCD display in no output mode is shown in the following diagram The information about the utility power the bat...

Страница 22: ...fault etc the corresponding fault code would be shown to indicate the operating mode of the UPS And some warning words could also be shown for example short would be shown when the load or the UPS out...

Страница 23: ...ass Enable in turn And if pressing the Enter button for more than one second at this time the flickering black line would turn to flickerless and the output voltage or frequency or bypass state settin...

Страница 24: ...t voltage from 220Vac to 230Vac through the LCD panel Step 1 One flickering black line would appear under 208Vac after pressing the Select button Step 2 The flickering line would move to 230Vac after...

Страница 25: ...p 3 The line under 230Vac would turn to flickerless after pressing the Enter button and the flickering line would move to the next 240Vac Step 4 The output voltage would be 230Vac after the UPS is tur...

Страница 26: ...ail warning 09 Inverter fault 06 Fan fail warning 10 Overload fault 07 Bat over warning 11 Over temperature fault 08 Bat weak warning 12 Charger fail warning 13 If the UPS system does not operate corr...

Страница 27: ...once a second Charger or Batteries damaged Notify dealer Warning code is shown as 10 Fan is locked or not working Check fans and notify dealer Fault code is shown as 07 warning tone once a second Over...

Страница 28: ...bient temperature has been exceeded the batteries must be replaced In this case please contact your dealer 9 2 Storage If the batteries are stored in temperate climatic zones they should be charged ev...

Страница 29: ...7kW 2kVA 1 4kW 3kVA 2 1kW 6KVA 4 2KW Voltage 208 220 230 240 1 2 VAC Frequency 50 60 1 0 2 Hz Battery mode Wave form sinusoidal Derating 10 when the output voltage is adjusted to 208VAC BATTERIES Mod...

Страница 30: ...1K 482 6 470 88 16 3 1KS 482 6 470 88 9 1 Battery Pack 36V 482 6 470 88 17 5 2K 482 6 470 88 11 2 2KS 482 6 470 88 12 3 3K 482 6 470 88 11 2 3KS 482 6 470 88 12 3 Battery Pack 96V 482 6 470 88 22 5 6...

Страница 31: ...eries UPS has AS400 card an optional accessory for AS400 communication protocol Please contact your local distributor for details The following is the pin assignment and description of DB 9 connector...

Страница 32: ...control any UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Go to the website http www ups software download com winpower htm 2 Choose the operation system you need and fo...

Страница 33: ...30 Appendix Back View of 1K S Back View of 2K Back View of 2KS 3K S...

Страница 34: ...31 Back View of 6K S Battery pack for 1 3KS Battery pack for 6KS...

Страница 35: ...32 614 00652 01...

Страница 36: ...33 MANUALE DELL UTENTE Modelli AP160LCD 1 6KVA Gruppo di continuit UPS...

Страница 37: ...idi Non installare l UPS in luoghi dove potrebbe essere esposto alla luce diretta del sole o vicino a fonti di calore Nel posizionare l UPS porre attenzione a non ostruirne le prese d aria Non collega...

Страница 38: ...connesso alla presa d installazione domestica Per scollegare completamente l UPS premere innanzitutto il pulsante di Standby e poi sconnettere il cavo di alimentazione Assicurarsi che nessun liquido e...

Страница 39: ...nti necessari nel caso in cui si lavori con delle batterie non indossare gioielli orologi da polso anelli e altri oggetti metallici servirsi solo di attrezzi con impugnature e manici isolati Quando oc...

Страница 40: ...2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Campi elettromagnetici della frequenza di rete IEC EN 61000 4 8 Level 3 Se...

Страница 41: ...of high voltage Rischio di folgorazione Turn on the UPS Accensione UPS Turn off the UPS Spegnimento UPS Idle or shut down the UPS Spegnimento o disattivazione UPS Alternating current source Presa cor...

Страница 42: ...alla tensione della corrente continua genera una corrente alternata sinusoidale che alimenta costantemente i carichi Sia i computer che le periferiche sono quindi alimentati interamente dalla tensione...

Страница 43: ...disattivo Se a questo punto il by pass abilitato attraverso questo che vengono alimentate le prese d uscita se l alimentazione di rete disponibile Pulsante Select Se il sistema UPS in modalit No outpu...

Страница 44: ...dica il valore di frequenza del potenziale della corrente di rete in entrata da 0 a 99Hz Indica il valore della corrente in entrata da 0 a 99 9A Informazioni di Output Indica il valore del potenziale...

Страница 45: ...della corrente di batteria da 0 a 99 9A Indica la percentuale di capacit della batteria ogni tacca rappresenta una capacit del 25 Se sono visualizzate tutte le tacche la capacit del 100 Indica che l...

Страница 46: ...un allarme cui necessario prestare attenzione Informazioni sull impostazione dell UPS Si pu selezionare il valore di voltaggio in uscita tra i 4 possibili quando l UPS in modalit No output o By pass p...

Страница 47: ...cavo di alimentazione usare un connettore adeguato con opportuno isolamento e fare attenzione per quanto riguarda la corrente che sopporta fino a 10A per i modelli 1K S 2K fino a 16A per i modelli 2K...

Страница 48: ...ablaggio c Una volta completato il cablaggio verificare che I cavi siano assicurati saldamente d Rimettere il coperchietto alla morsettiera posta sul pannello posteriore 3 Collegamento del Computer Co...

Страница 49: ...rmo LCD si accender indicando lo stato dell UPS 2 Connessione senza tensione di rete Anche nel caso in cui non sia presente tensione di rete l UPS pu essere comunque acceso tenendo semplicemente premu...

Страница 50: ...ttivare l uscita 2 In modalit batteria Tenere premuto il pulsante OFF per pi di 1 secondo per spegnere l UPS L UPS effettuer per prima cosa il test automatico Una volta terminato il test l UPS si speg...

Страница 51: ...rie dell utente 3 Non connettere ancora l UPS a nessun carico Connettere quindi il cavo di alimentazione di rete all UPS per alimentare il sistema e permettergli di funzionare in modalit alimentazione...

Страница 52: ...e i carichi non necessari uno alla volta per ridurre i carichi connessi all UPS sotto il 90 della sua capacit di alimentazione nominale Nota seguire queste istruzioni per connettere il generatore Atti...

Страница 53: ...sul pannello frontale per pi di 1 secondo l avvisatore smetter di suonare modalit silenziosa Tenere premuto il pulsante ON per pi di 1 secondo per riattivare l allarme 2 Lo stesso display viene visua...

Страница 54: ...ico viene fornita dall alimentazione di rete passando per il filtro interno 6 4 Modalt No output Il display LCD in modalit No output mostrato nel diagramma sottostante Sono visualizzati i dati relativ...

Страница 55: ...ori nel Bus ecc verr mostrato il codice di errore corrispondente per indicare la modalit operativa dell UPS Potrebbero comparire anche avvertimenti come short nel caso in cui il carico o l uscita dell...

Страница 56: ...By pass Bypass Enable Attiva modalit By pass A questo punto se si tiene premuto il pulsante Enter per pi di un secondo la linea nera smette di lampeggiare e il valore di voltaggio della frequenza in u...

Страница 57: ...ioin uscita da 220Vac a 230Vac tramite il pannello LCD Passo 1 Premere il pulsante Select sotto la scritta 208V apparir una linea nera lampeggiante Passo 2 Premere il pulsante Select altre due volte l...

Страница 58: ...remere il pulsante Enter la linea sotto 230Vac smette di lampeggiare e si mette a lampeggiare sotto l opzione successiva 240Vac Passo 4 La tensione in uscita risulter impostato su 230Vac una volta ria...

Страница 59: ...Errore nell inverter 06 Allarme ventola 10 Errore sovraccarico 07 Allarme sovratensione batteria 11 Errore temperatura eccessiva 08 Allarme batteria bassa 12 Allarme caricabatterie 13 Se il sistema UP...

Страница 60: ...visualizzato il codice di allarme 13 allarme acustico una volta al secondo Caricabatterie o batterie danneggiate Contattare il fornitore Viene visualizzato il codice di allarme 10 La ventola bloccata...

Страница 61: ...ento Il sistema UPS non contiene parti riparabili dall utente Se la durata di servizio della batteria 3 5 anni a 25 C di temperatura ambientale stata superata le batterie vanno sostituite In questo ca...

Страница 62: ...50A OUTPUT USCITA N modello 1K S 2K S 3K S 6K S Potenza 1kVA 0 7kW 2kVA 1 4kW 3kVA 2 1kW 6KVA 4 2KW Tensione 208 220 230 240 1 2 VAC Frequenza 50 60 1 0 2 Hz Modalit batteria Forma d onda sinusoidale...

Страница 63: ...10 3 Dimensioni e pesi N Modello Dimensioni L x P x H mm Peso netto kg 1K 482 6 470 88 16 3 1KS 482 6 470 88 9 1 Battery Pack 36V 482 6 470 88 17 5 2K 482 6 470 88 11 2 2KS 482 6 470 88 12 3 3K 482 6...

Страница 64: ...cheda AS400 come accessorio opzionale per il protocollo di comunicazione AS400 Rivolgersi al distributore locale per i dettagli Nella tabella seguente sono indicati i numeri e la descrizione dei pin d...

Страница 65: ...e controllare tutti gli UPS su una stessa LAN a prescindere dalla distanza a cui si trovano gli UPS Procedura di Installazione 1 Andare sul sito web http www ups software download com winpower htm 2 S...

Страница 66: ...63 Appendice Vista posteriore dei modelli 1K S Vista posteriore del modello 2K Vista posteriore dei modelli 2KS 3K S...

Страница 67: ...64 Vista posteriore dei modelli 6K S Battery pack per i modelli 1 3KS Battery pack per i modelli 6KS...

Отзывы: