background image

Page 11

Controlling The Temperature

The Microprocessor will scan the temperature parameters every 3 minutes, when the temperature
goes outside of the temperature parameters this will generate a text alarm sent to the users indicating
the current temperature and turn on relay 1.

When the temperature returns into the temperature parameters, a text will be generated to let users
now temperature is normal, and relay 1 will be turned off

Text Commands

#

+

09*20

#

  This will save the parameter settings for plus 9 degrees to plus 20 degrees

#

-

10*20

#

 

This will save the parameter settings for minus 10 degrees to minus 20 degrees

*NOTE YOU CANNOT MIX MINUS AND PLUS TEMPERATURES - PLEASE USE + OR - SYMBOL

#

START

#

 will start the temperature reading / temperature alarm

#

STOP

#

  will stop the temperature reading / temperature alarm

*Note In the event of a power loss the unit will remember if it was in stop or start mode

#

TEMP

#

  at any time you can text this to get a temperature reading

Содержание 4GAD+

Страница 1: ...GSM 4G AUTO DIALLER PLUS Control and Monitoring from your mobile phone Page 1 MODEL 4GAD ...

Страница 2: ... Deleting Contact Numbers 7 How to Store Input Text Messages How to Set Phone Call Alerts and Text Messages 8 Activating the Output Relays 9 Activating Inputs 10 Mains Failure Monitoring Battery Back Up Microphone Speaker Optional 11 Temperature Monitoring 12 Quick Programming Guide Factory Reset 13 Important Installer Notes Page 2 ...

Страница 3: ...Mhz 4G Bands B1 B5 B7 B8 B12 B14 B18 B20 B25 B26 B28 B66 B71 Power Supply Voltage 9 24 volts DC Current Used in Standby Mode 35 Milliamps Max Current Up to 2 Amps Standard 2G 3G 4G Simcard No landline required Dimensions L170 x W120 x H60mm Weight 360 grams Operating Temperature 10 40 C Signal Strength Function Stay Active Simcard Function Watchdog and Self Repair Function 3 Inputs and 1 Alarm Inp...

Страница 4: ...he red LED indicates that the battery is in charging mode Battery Switch push on to turn battery backup on battery only charges with battery switch on Dipswitch The dialler can work on 2G 3G 4G networks The module it uses works worldwide with all simcard see page 3 for applicable bands You can choose which frequency the unit will use at the start by using the dipswitch combinations below 1 If Dips...

Страница 5: ... 4502 Giff Gaff call 1626 EE send the text message command VM OFF to 150 ENSURE THE UNIT IS POWERED DOWN AND BATTERY TURNED OFF BEFORE INSERTING THE SIMCARD 1 Slide back the sim door and lift it up 2 Slide the simcard in to the door making ensuring that the clipped corner of the simcard lines up with the clipped corner of the simcard holder 3 Close the sim door 4 Slide the sim door to lock the sim...

Страница 6: ...umbers please follow this example PH1 07712345678 Stores the mobile landline phone number as contact no 1 PH2 01903123456 Stores the mobile landline phone number as contact no 2 PH3 07123456789 Stores the mobile landline phone number as contact no 3 A maximum of 3 phone numbers in total To delete a stored number use the following example PH1 DELETE YOU CANNOT DELETED NUMBER 1 ONLY OVERRIDE PH2 DEL...

Страница 7: ...is INPUT ACTIVATED Note your can only use a maximum of 30 characters including spaces for you customised message Telephone Call Alerts The auto dialler can be programmed to send you a telephone call after each text alarm has been sent You will receive approximately three ring tones The unit will then hang up automatically This prevents call charges being incurred To set call alerts to ON please se...

Страница 8: ...on please send the SMS AUTO ON this will turn the AUTO function on for relay 2 only AUTO OFF this will turn the AUTO function off for relay 2 only default setting is off Activation by SMS Text Message By texting the unit you can turn relay 1 and 2 ON or OFF individually Below are examples on how to do this REL1 ON This will turn on relay 1 REL1 OFF This will turn off relay 1 REL2 ON This will turn...

Страница 9: ...ERED ALARM OFF This will deactivate the alarm Pulling the input to the ground will mean you will receive NO notifications Using the Inputs Inputs 1 2 3 Automatically Reset Inputs 1 2 3are triggered by a negative pulse eg pulled tothe ground for a period of not less than one second The image at the bottom of the page 1s a typical application ofhow to connect the unit to an alarm panel Input 1 and I...

Страница 10: ...t will need to be recharged by connecting 12 volts back to the power input NOTE The battery will only work when the battery is switched on If you do not switch the battery switch on then the battery backup will not work Please refer to PCB reference on page 4 Microphone and Speaker optional extra purchased seperately The unit has an onboard microphone To activate it make a phone call to the units ...

Страница 11: ... now temperature is normal and relay 1 will be turned off Text Commands 09 20 This will save the parameter settings for plus 9 degrees to plus 20 degrees 10 20 This will save the parameter settings for minus 10 degrees to minus 20 degrees NOTE YOU CANNOT MIX MINUS AND PLUS TEMPERATURES PLEASE USE OR SYMBOL START will start the temperature reading temperature alarm STOP will stop the temperature re...

Страница 12: ...Page 11 Quick Reference ...

Страница 13: ...ore commissioning please ensure the signal strength is sufficient by sending the text message STATUS We strongly recommend you need a score of at least 10 Also try the signal using both the 2G 3G 4G via dipswitch 1 2 If you do not receive a good signal please reposition the aerial antenna to improve the signal strength or alternatively change the network provider as signal strength can vary betwee...

Отзывы: