background image

 

D1073 

- SIL 2 Temperature Signal Converter and Trip Amplifiers 

G.M. International ISM0019-13 

Power Dissipation of D1073 Isolators

 

Section “Technical Data” of D1073 isolator specifies the current consumption (maximum current from the nominal power supply, typical 24 Vdc, in normal operation); this data serves to 
dimension the current rating of the power supply unit. Section “Technical Data” indicates also the maximum power consumption (maximum power required from the power supply in the 
worst (abnormal) operating conditions like for example supply voltage at 30 Vdc, short circuit on the outputs and on the inputs terminals. 
The power dissipated 

Pd

 inside the enclosure for analog signal isolators is: 

Pd = Current Consumption (A) * Supply Voltage (V) - Power Dissipated into the input/output loads 

Analog signal isolators have higher dissipation than digital signal isolators. In analog signal isolators each transmitter requires and dissipates 15 V * 0.02 A = 0.3 W. Usually the loads 
outside the isolator dissipate 1/3 of the total power used. Isolators are not running at the maximum current all at the same time, the average power consumption of a multitude of isolators 
can be considered to be only 70 % of the value obtained from the section “Technical Data”. Considering the 1/3 load power and the 70 % above discussed, the power effectively 
dissipated internally by the isolators can therefore become ½ of the actual power delivered by the power supply. Digital barriers dissipate all the supply power inside the enclosure 
consequently the total power dissipation into a cabinet, with mixed analog and digital barriers, is determined by the number of channels more than by the number of isolator enclosures. 
The following tables give advises for the DIN rail orientation (vertical or horizontal) of the barriers mounting, D1073S (single channel) isolators, installed on DIN rail, bus or custom board 
assembly. 
 

A) 

Cabinet with Natural Ventilation 

Maximum recommended ambient temperature in °C depending on barrier type and installation method: 

 

Installation in Cabinet 

 

 

 

Any orientation 

Vertical 

Horizontal 

Installation of Multiple units with DIN-rail Bus 

Single unit 

Installation 

 

Type of Isolator 

 

 

 

Vertical 

Horizontal 

Installation on Custom Boards 

B) 

Cabinet with Forced Ventilation 

Maximum recommended ambient temperature in °C depending on barrier type and installation method: 

 

 

 

Any orientation 

Vertical 

Horizontal 

Installation of Multiple units with DIN-rail Bus 

Single unit 

Installation 

 

Type of Isolator 

 

60°C 

40°C 

45°C 

Vertical 

Horizontal 

Installation on Custom Boards 

45°C 

50°C 

 

 

D1073S 

60°C 

30°C 

35°C 

D1073S 

35°C 

40°C 

Содержание D1073S

Страница 1: ...D1073 SIL 2 Temperature Signal Converter and Trip Amplifiers ISM0019 13 D1073S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Temperature Signal Converter And Trip Amplifiers Din Rail Model D1073S ...

Страница 2: ...max 600 Ω load source mode current limited at 22 mA or 0 1 to 5 V or 0 2 to 10 V signal limited at 11 V Resolution 2 µA current output or 1 mV voltage output Transfer characteristic linear or reverse on mV or transmitting potentiometer temperature linear or reverse on temperature sensors Response time 50 ms 10 to 90 step change Output ripple 20 mVrms on 250 Ω load Alarm Trip point range within rat...

Страница 3: ... resistance compensation Reference Junction Compensation automatic or fixed programmable value 0 4 20 mA 0 1 5 V 0 2 10 V Output Signal temperature linear or reverse 16 characters tag Two independent trip amplifiers Output for burnout detection Common burnout detection available when using Power Bus enclosure High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Co...

Страница 4: ...ntation if the device is Intrinsically Safe check its suitability for the Hazardous Area Hazardous Locations and gas group encountered and that its maximum allowable voltage current power Ui Vmax Ii Imax Pi Pi are not exceeded by the safety parameters Uo Voc Io Isc Po Po of the D1073 Associated Apparatus connected to it Also consider the maximum operating temperature of the field device check that...

Страница 5: ...S LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 For SIL applications alarm contacts must be used in series with equal configuration Relay contact shown in de energized position MODEL D1073S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 13 14 15 16 5 6 7 8 Alarm A Alarm B Set A Set B In 1 3 wire RTD 4 wire RTD Pot MODEL D1073S 3 4 1 2 RL mA V Supply 24 Vd...

Страница 6: ...connect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative Any unauthorized modification must be avoided Warning Operation Input channel of D1073 accepts a ...

Страница 7: ...ocouple positive extension wire at terminal 15 negative and shield if any at terminal 16 Make sure that compensating wires have the correct metal and thermal e m f and are connected to the appropriate thermocouple terminal note that a wrong compensating cable type or a swapped connection is not immediately apparent but introduces a misleading measurement error that appears as a temperature drift F...

Страница 8: ...e value obtained from the section Technical Data Considering the 1 3 load power and the 70 above discussed the power effectively dissipated internally by the isolators can therefore become of the actual power delivered by the power supply Digital barriers dissipate all the supply power inside the enclosure consequently the total power dissipation into a cabinet with mixed analog and digital barrie...

Страница 9: ...value press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key 7 Sens 3 Level Menu Displays the input sensor type configuration Press Enter to set the input sensor press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key you can choose betwee...

Страница 10: ...essed Enter key you can choose between 5 different alarm conditions press Select key to change the type and then the Enter key to confirm the choice The condition types are OFF no alarm detection the relay output is always in normal condition HI high alarm condition the relay output change status when an alarm condition is detected input variable goes above the set value LO low alarm condition the...

Страница 11: ...n type Fixed only range from 60 to 100 C RTD line resist line resistance error compensation value thermoresistance only range from 5 to 20 Ω INPUT TAG SECTION OUTPUT SECTION Output analog output type 4 20 mA current output range from 4 to 20 mA 0 20 mA current output range from 0 to 20 mA 1 5 V voltage output range from 1 to 5 V 0 5 V voltage output range from 0 to 5 V 2 10 V voltage output range ...

Отзывы: