D1073 

- SIL 2 Temperature Signal Converter and Trip Amplifiers 

G.M. International ISM0019-13 

General Description:

 The single channel DIN Rail Temperature Signal Converter and Trip Amplifier D1073S accepts a low level dc signal from millivolt, thermocouple or RTD 

temperature sensor, located in Hazardous Area, and converts, with isolation, the signal to drive a Safe Area load. Output signal can be direct or reverse. Two independent Alarm Trip 
Amplifiers are also provided. Each alarm energizes, or de-energizes, an SPST relay for high, low, low-startup or burnout alarm functions. The two alarm relays trip points are settable 
over the entire input signal range. 

Function:

 1 channel I.S. input from mV, thermocouples, 3-4 wires resistance thermometers, transmitting potentiometers, provides 3 port isolation (input/output/supply) and current 

(source mode) or voltage output signal. The programmable RTD line resistance compensation allows the use of 2 wires RTDs or error compensation for 3-4 wires RTDs. 
Reference junction compensation can be automatic, with option 91, or fixed by software setting. In addition it provides two SPST relay alarm contacts with adjustable alarm trip point. 

Signalling LEDs:

 Power supply indication (green), burnout (red), alarm A (red), alarm B (red). 

Configurability:

 Totally software configurable, no jumpers or switches, input sensor, connection mode, burnout operation, mA or V output signal, alarm trip point, high, low, low-startup 

or burnout alarm mode, NE/ND relay operation, hysteresis, delay time, by GM Pocket Portable Configurator PPC1090, powered by the unit or configured by PC via RS-232 serial line 
with PPC1092 Adapter and SWC1090 Configurator software. A 16 characters tag can be inserted using SWC1090 Configurator software. 

EMC:

 Fully compliant with CE marking applicable requirements. 

Supply: 

24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. 

Current consumption @ 24 V: 

65 mA with 20 mA output and relays energized typical. 

Power dissipation:

 1.5 W with 24 V supply, 20 mA output and relays energized typical. 

Max. power consumption: 

at 30 V supply voltage, overload condition, relays energized and PPC1090 connected, 2.1 W. 

Isolation (Test Voltage): 

I.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV; Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV. 

Input: 

millivolt or thermocouple type A1, A2, A3, B, E, J, K, L, Lr, N, R, S, S1, T, U or 3-4 wires RTD Pt100, Pt200, Pt300 to DIN43760, Pt100 (0.3916), Ni100, Ni120 or 

Pt500, Pt100, Pt50, Cu100, Cu53, Cu50, Cu46 (russian standard) or 3 wires transmitting potentiometer (50 

 to 20 K

). 

Integration time: 

500 ms. 

Resolution: 

5 µV on mV or thermocouple, 1 µV thermocouple type B, R, S, S1, 2 µV thermocouple A1, A2, A3, 20 m

 on RTD, 0.05 % on transmitting potentiometer. 

Visualization: 

0.1 °C on temperature, 10 µV on mV, 0.1 % on potentiometer. 

Input range: 

within rated limits of sensor (-10 to + 80 mV). 

Measuring RTD current: 

 0.5 mA. 

RTD line resistance compensation: 

 10 

RTD line resistance error compensation: 

- 5 to + 20 

, programmable. 

Thermocouple Reference Junction Compensation: 

automatic, by external sensor OPT91 separately ordered, or fixed programmable from - 60 to + 100 °C. 

Thermocouple burnout current: 

 30 nA. 

Burnout: 

enabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing. Burnout condition signalled by red front panel LED. 

Alarms can be programmed to detect burnout condition. 

Output: 

0/4 to 20 mA, on max. 600 

 load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V. 

Resolution: 

2 µA current output or 1 mV voltage output. 

Transfer characteristic: 

linear or reverse on mV or transmitting potentiometer, temperature linear or reverse on temperature sensors. 

Response time: 

 50 ms (10 to 90 % step change). 

Output ripple: 

 20 mVrms on 250 

 load. 

Alarm: 

Trip point range: 

within rated limits of input sensor (see input for step resolution). 

ON-OFF delay time: 

0 to 1000 s, 100 ms step, separate setting. 

Hysteresis: 

0 to 5 °C for temperature sensor input, 0 to 50 mV for mV input, 0 to 50 % for potentiometer input (see input for step resolution). 

Output: 

voltage free SPST relay contact. 

Contact rating: 

2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). 

Performance: 

Ref. Conditions 24 V supply, 250 

 load, 23 ± 1 °C ambient temperature. 

Input: 

Calibration and linearity accuracy:

 

 ± 40 µV on mV or thermocouple, 200 m

 on RTD, 0.2 % on potentiometer or ± 0.05 % of input value. 

Temperature influence: 

 ± 2 µV, 20 m

, 0.02 % or ± 0.01 % of input value for a 1 °C change. 

Ref. Junction Compensation influence: 

 ± 1 °C (thermocouple sensor). 

Analog Output: 

Calibration accuracy: 

 

± 0.1 % of full scale. 

Linearity error: 

 ± 0.05 % of full scale. 

Supply voltage influence: 

 ± 0.05 % of full scale for a min to max supply change. 

Load influence: 

 ± 0.05 % of full scale for a 0 to 100 % load resistance change. 

Temperature influence: 

 ± 0.01 % on zero and span for a 1 °C change. 

Compatibility: 

 

CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive. 

Environmental conditions: 

Operating:

 temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. 

Storage:

 temperature limits – 45 to + 80 °C. 

Safety Description:

 

II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nA IIC T4, [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I associated electrical apparatus. 

Uo/Voc = 10.8 V, Io/Isc = 9 mA, Po/Po = 24 mW at terminals 13-14-15-16. 

Ui/Vmax = 18 V, Ci = 6 nF, Li = 0 nH at terminals 13-14-15-16. 

Um = 250 Vrms, -20 °C 

 Ta 

 60°C. 

Approvals: 

DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11, 

IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, GM International CRR028 conforms to EN60079-0, EN60079-15, 

UL & C-UL E222308 conforms to UL913 (Div.1), UL 60079-0 (General, All Zones), UL60079-11 (Intrinsic Safety “i” Zones 0 & 1) for UL and 

CSA-C22.2 No.157-92 (Div.1), CSA-E60079-0 (General, All Zones), CSA-E60079-11 (Intrinsic Safety “i” Zones 0 & 1) for C-UL, 

refer to control drawing ISM0142 for complete UL and C-UL safety and installation instructions, 

FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15, 

Russia according to GOST 12.2.007.0-75, R 51330.0-99, R 51330.10-99 [Exia] IIC X, Ukraine according to GOST 12.2.007.0,22782.0,22782.5 Exia IIC X, 

TUV Certificate No. C-IS-204194-02, SIL 2 according to IEC 61508, IEC 61511. Please refer to Functional Safety Manual for SIL applications. 

DNV and KR Type Approval Certificate for marine applications. 

Mounting: 

T35 DIN Rail according to EN50022. 

Weight: 

about 160 g. 

Connection: 

by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm

2

Location:

 Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA 

T4 installation. 

Protection class: 

IP 20. 

Dimensions: 

Width 22.5 mm, Depth 99 mm, Height 114.5 mm. 

 

 

 

Technical Data 

Characteristics 

For Safety Related System and SIL2, SIL3 Applications according IEC61508 & IEC61511 Standards refer to “Functional Safety Manual” document number ISM0071 

 

SIL Applications 

 

Содержание D1073S

Страница 1: ...D1073 SIL 2 Temperature Signal Converter and Trip Amplifiers ISM0019 13 D1073S INSTRUCTION MANUAL INSTRUCTION MANUAL SIL 2 Temperature Signal Converter And Trip Amplifiers Din Rail Model D1073S ...

Страница 2: ...max 600 Ω load source mode current limited at 22 mA or 0 1 to 5 V or 0 2 to 10 V signal limited at 11 V Resolution 2 µA current output or 1 mV voltage output Transfer characteristic linear or reverse on mV or transmitting potentiometer temperature linear or reverse on temperature sensors Response time 50 ms 10 to 90 step change Output ripple 20 mVrms on 250 Ω load Alarm Trip point range within rat...

Страница 3: ... resistance compensation Reference Junction Compensation automatic or fixed programmable value 0 4 20 mA 0 1 5 V 0 2 10 V Output Signal temperature linear or reverse 16 characters tag Two independent trip amplifiers Output for burnout detection Common burnout detection available when using Power Bus enclosure High Accuracy µP controlled A D converter Three port isolation Input Output Supply EMC Co...

Страница 4: ...ntation if the device is Intrinsically Safe check its suitability for the Hazardous Area Hazardous Locations and gas group encountered and that its maximum allowable voltage current power Ui Vmax Ii Imax Pi Pi are not exceeded by the safety parameters Uo Voc Io Isc Po Po of the D1073 Associated Apparatus connected to it Also consider the maximum operating temperature of the field device check that...

Страница 5: ...S LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 For SIL applications alarm contacts must be used in series with equal configuration Relay contact shown in de energized position MODEL D1073S 3 4 1 2 RL mA V Supply 24 Vdc Source I Source V Out 1 13 14 15 16 5 6 7 8 Alarm A Alarm B Set A Set B In 1 3 wire RTD 4 wire RTD Pot MODEL D1073S 3 4 1 2 RL mA V Supply 24 Vd...

Страница 6: ...connect power before servicing or unless area is known to be nonhazardous Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative Any unauthorized modification must be avoided Warning Operation Input channel of D1073 accepts a ...

Страница 7: ...ocouple positive extension wire at terminal 15 negative and shield if any at terminal 16 Make sure that compensating wires have the correct metal and thermal e m f and are connected to the appropriate thermocouple terminal note that a wrong compensating cable type or a swapped connection is not immediately apparent but introduces a misleading measurement error that appears as a temperature drift F...

Страница 8: ...e value obtained from the section Technical Data Considering the 1 3 load power and the 70 above discussed the power effectively dissipated internally by the isolators can therefore become of the actual power delivered by the power supply Digital barriers dissipate all the supply power inside the enclosure consequently the total power dissipation into a cabinet with mixed analog and digital barrie...

Страница 9: ...value press the Select key to highlight the character you want to change and then the Up and Down keys to select the number confirm the modification with the Enter key 7 Sens 3 Level Menu Displays the input sensor type configuration Press Enter to set the input sensor press the Select key to the next menu level item or Up key to return to second level If you pressed Enter key you can choose betwee...

Страница 10: ...essed Enter key you can choose between 5 different alarm conditions press Select key to change the type and then the Enter key to confirm the choice The condition types are OFF no alarm detection the relay output is always in normal condition HI high alarm condition the relay output change status when an alarm condition is detected input variable goes above the set value LO low alarm condition the...

Страница 11: ...n type Fixed only range from 60 to 100 C RTD line resist line resistance error compensation value thermoresistance only range from 5 to 20 Ω INPUT TAG SECTION OUTPUT SECTION Output analog output type 4 20 mA current output range from 4 to 20 mA 0 20 mA current output range from 0 to 20 mA 1 5 V voltage output range from 1 to 5 V 0 5 V voltage output range from 0 to 5 V 2 10 V voltage output range ...

Отзывы: