Section 50 

 

00-02-1033 

2018-12-03 

- 13 - 

4.  Open the following list of screens to verify or change the factory settings as needed for your site 

location.  

a.  We suggest you record these values in the Sequence of Operation. This gives you a 

reference of any changed settings from the factory default. 

b.  From the Home screen, touch the Setup Enter icon to open the Setup Menu screen. 

 

c.  From Setup Menu screen, touch the Setpoints icon to open it. Open and verify the set 

values under the Blue (active) icons. Touch a value to change it. Touch X to go back one 
page or the Menu icon to go back to Setup Menu screen. 

i.  Once verification and changes are made and recorded, return to the Setup Menu 

screen and open another screen from the list below. Repeat these steps to verify 
the set values under the remaining screens listed. 

 

Setpoints 

 

Control Loop 

 

Analog Inputs 

 

General Timer 

 

State Timer 

 

Temperature Inputs 

 

Rod Load Setup 

 

NOTE:

 For screen specific help, press the 

 Information icon to view 

information about the items and settings available on the displayed page. 

5.  Start the unit. 

a.  Clear any Alarms Class A (always armed)

 

faults from the system. On the display the Unit 

State will read Panel Rdy if no Class A shutdown condition exist. 

b.  Touch and hold the Run Stop icon on the display for 2 seconds. This will initiate the start 

cycle. Depending on your configuration, the Centurion will send signals to possibly 
prelube the equipment, check pre-starting permissives and then signal the driver to start 
the equipment.  Confirmation of running may be in the form of RPM signal or digital 
switch input feedback. Once running signal is confirmed, the Centurion will be in a 
running condition.  Class B and S lockout timers will begin timing to faults that require 
time lockout.  Additional warmup and load permissives will be monitored as configured for 
the package prior to enabling any load control. 

c. 

After all preload permissives have been achieved, such as oil or water temperatures, and 
possible minimum warmup times, the Unit State will read Loaded and will continue until 
the stop button is pressed, RPM is lost or a fault condition exist. 

 

 

Содержание Centurion C5

Страница 1: ...Components Include MX4 R2 Interchange Communication Control Module MX5 R2 Interchange Communication Control Module Before installing the product inspect each item for damage which sometimes occurs du...

Страница 2: ...y accessible by the use of a tool Pressure 80 kPa 0 8 bar to 110 kPa 1 1 bar Air with normal oxygen content typically 21 v v Temperature Class T4 ic intrinsic safety for EPL Gc Increased safety for EP...

Страница 3: ...Section 50 00 02 1033 2018 12 03 3 M VIEW Display Dimensions MV 5 C M VIEW Monochrome LCD MV 7T M VIEW Touch Series MV 10T M VIEW Touch Series...

Страница 4: ...of controller in the cutout before proceeding with drilling mounting holes 5 If applicable drill holes where indicated for the mounting screws MV 5 C Display NOTE The Centurion MV 5 C display can be...

Страница 5: ...rt the display back side first from the front side of the panel 3 Ensure that there is adequate clearance for the edges of the display housing and the back of the case is flush against the outside sur...

Страница 6: ...ection 50 00 02 1033 2018 12 03 6 Stand Mount Four mount tapped screw holes M4 x 0 7 5 mm deep are located on the rear of the panels for stand or wall mounting Tapped screw hole locations MV 7T MV 10T...

Страница 7: ...r User Menu in addition to the Standard password features Default passwords are Operator 164 Super User 133 Your password access times out three minutes after the editing session is exited NOTE If a p...

Страница 8: ...nd verify its drawing number matches the sticker on the lower front panel 2 Locate the legend of the drawing and find the configuration description Record this description 3 Power up the Centurion Sys...

Страница 9: ...tatus MVIEW Comm Status Centurion Comm Status Real Time Clock Setup Super User Setup Centurion Serial Ports Centurion Can Ports Centurion Ethernet Centurion EMMC Log MVIEW Serial Ports MVIEW CAN Ports...

Страница 10: ...the Unit State will read Stopping 4 When everything has been recognized as back to normal the Unit State will read Panel Ready Fault Shutdown The Centurion will continually monitor for Fault or ESD sh...

Страница 11: ...be displayed as a percentage of the range d Custom Generic Register allows user to display up to 20 items on a page that can be mapped to the Centurion Modbus map and given a label For more informati...

Страница 12: ...en approximately 15 seconds b If Centurion has integrated EICS displays enabled the System View will be the initial powerup view Touch the screen on the Centurion Gage side to open its Home screen in...

Страница 13: ...n icon to view information about the items and settings available on the displayed page 5 Start the unit a Clear any Alarms Class A always armed faults from the system On the display the Unit State wi...

Страница 14: ...een with time and date of occurrence 1 The Shutdown History screen displays information of the fault Touch the Book icon for troubleshooting a Centurion Home Gage Screen FN Shutdown History 2 The Shut...

Страница 15: ...rcentage of the range d Custom Generic Register allows user to display up to 20 items on a page that can be mapped to the Centurion Modbus map and given a label For more information on configuring the...

Страница 16: ......

Отзывы: