™ C5 Quick Start Guide
If the Centurion Controller and Display Modules are already installed, skip the Installation section and go to the
section titled
Before Starting the Equipment for the First Time
.
Installation
The following instructions will guide you through installing the Centurion C5 controller, display and additional
communication modules.
For wiring connections, please open the appropriate Installation Manual file on the white thumb drive provided.
No special cables are required. The Centurion system is designed for use within a weatherproof enclosure only.
Basic Components Include:
Centurion C5 Controller Module
M-VIEW
™
Display Module
Optional Components Include:
MX4-R2 (Interchange Communication Control Module)
MX5-R2 (Interchange Communication Control Module)
Before installing the product, inspect each item for damage which sometimes occurs during shipping.
Centurion C5 Controller Module
The Centurion Module Controller must be mounted in an enclosure meeting the requirements of IP54 or greater
according to the intended use and environmental conditions in accordance with standard UL 60529 and only
accessible by use of a tool.
Operating Temperature 40° to 185° F (-40°
to +85°
C)
Pressure 80 kPa (0,8 bar) to 110 kPa (1,1 bar)
Air with normal oxygen content, typically 21% v/v
Temperature Class T4
“ic”: intrinsic safety, (for EPL Gc)
Increased safety, (for EPL Gc)
The Centurion Controller can be mounted vertically or horizontally on a standard
DIN rail.
Attach the four clamp-type feet along the bottom of the controller to the DIN rail.
We recommend installing rail stops to prevent sliding.