* Calibration Procedures

(1) Press both  scroll  and  down  key,  then  release.   Tool  program will

appear on the upper and lower displays.  Repeat above operation until

    appear on the displays.

(2) Press and release the scroll key.  The display will show a

      number with a prefix  "     "

(3) Use  the up and down keys to change the value on the display
      until  this  value  coincide  with  the  ambient  temperature in degree C

which is measured by the standard thermometer.

(4) Press the scroll key for at least 3.2 seconds, then release.  The
      display will blink a moment and then show the ambient temperature in

degree C.

(5) Press and release the scroll key.  The display will show a number with

a prefix "    " , and the display will show 0.00.

(6) Press and hold down the push-button switch SW1.  Don't release

SW1.  Press the scroll key for at least 3.2 seconds, then release.  The
display now will show 20.00.  Release SW1.

(7) Press and  release  the  scroll  key.   The display will show a number

with a prefix "    ".    If  the number is not equal to 0.0, use the up and
down keys to set the value to 0.0.   Then  press the scroll key for at
least 3.2 seconds, then release.  The "    " code is reset.

* Verify Calibration Accuracy

(1) Operate the key pads until the display reaches the calibration mode

(                         appear on the displays ).

(2) Press and release the scroll key until a      code is shown in the display.

The display will  indicate  process  value  with respect to the 0-20mA
input.  Feed a  standard signal to the  correct mA  input terminals and
examine the accuracy of the display.

(3) Press and release the scroll key again until a       code is shown in the

display.    Now the display will indicate process value with respect to
the INPT  type selected.  Feed a standard signal to the appropriate input
terminals and examine the accuracy of the display.

(4) Press         and         ,  then  release  quickly,  the  display will indicate

process value with respect to the PT100/DIN input.   Feed a standard
signal to the PT100 input terminals and examine the accuracy of the
display.

(5) Press         and         ,  then  release  quickly,  the  display  will  indicate

process value with respect to the 0-10V input.  Feed a standard signal
to the voltage input terminals and examine the accuracy of the display.

* Warm-up  drift correction for thermocouple  input   after completing  the

above calibration procedure, connect a thermocouple to terminal 13 and
14 ( observing polarity ) and select a  correct " INPT "  for the thermocouple.
Switch the power on and let the controller to be powered for at least 30
minutes.  If the controller does not measure a correct temperature for the
thermocouple, the following procedures may be employed to correct the
error.

(1) Perform procedure (1) and (2) stated in calibration procedures.

(2) Press and release the scroll key.

(3) Press and release the scroll key again.  Now the "        " code with zero

value is obtained on the display.

(4) Use the up and down keys to change the "          "  code  value  until the

display shows a correct temperature.   The unit of  "       "code

      value is always in degree C independent of the selection of " UNIT ".

(5) Press the scroll  key  for  at  least  3.2  seconds,  then  release.    The

display will blink a moment and show an accurate temperature.  If the
accuracy of the controller is still unacceptable, replace the controller.

7.  ERROR  MESSAGE  &  DIAGNOSIS

          This procedure requires access to the circuitry of a live power unit.
Dangerous accidental contact with line voltage is possible.  Only qualified
personnel are to perform these procedures.  Potentially lethal voltages are
present.

Experience has proven that many control problems are not caused by a
defective instrument.  See chart below and Table 7.1 for some of the other
common causes of failures:

* Line wires are improperly connected

* No voltage between line terminals

* Incorrect voltage between line terminals

* Connections to terminals are open, missing or loose

* Thermocouple is open at tip

* Thermocouple lead is broken

* Shorted thermocouple leads

* Short accross terminals

* Open or shorted heater circuit

* Open coil in external contactor

* Burned out line fuses

* Burned out relay inside control

* Defective solid-state rellays

* Defective line switches

* Burned out contactor

* Defective circuit breakers

If the points listed on the chart have been checked and the controller does
not function. it is suggested that the instrument be returned to the factory
for inspection.

Do not attempt to make repairs.  It usually creates costly damage.  Also, it
is advisable to use adequate packing materials to prevent damage in
shipment.

FDC-9200

A1

SV

OUT

A2

PV

F

C

Press both sides of the latch located on

rear terminal block.Hold tightly and

remove the terminal block from the

housing.

(1)

Expand the rear edge of the housing by

using a tool. Pull out the PCB from the

(2)

Dismantling the controller

Page 12

Содержание FDC-9200

Страница 1: ...User s Manual FDC 9200 Self Tune Fuzzy PID Process Temperature Controller...

Страница 2: ...although PID control has been used and proved to be an efficient controlling method by many industries yet the PID is difficult to deal with some sophisticated systems such as second order systems lon...

Страница 3: ...Band Reset Integral Rate Derivative Ramp Rate Dwell ON OFF Cycle Time Control Action POWER Rating Consumption ENVIRONMENTAL PHYSICAL Safety Protection EMC Emmission EMC Immunity Operating Temperature...

Страница 4: ...larity is observed throughout Joints in the cable should be avoided if possible The colour codes used on the thermocouple extension leads are shown in Table 4 1 4 4 5 Relay Output Direct Drive Figure...

Страница 5: ...C 3 Silicon Rubber buttons For ease of control set up and setpoint adjustment Control Output Setpoint Value Alarm Outputs Process Value 3 5 7 4 6 8 or or Alarm 2 Control Output 2 Alarm1 Output Control...

Страница 6: ...Hold Function Dwell Timer ON as Time Out No Special Function Alarm with Latch Function Alarm with Latch Hold Function Dwell Timer OFF as Time Out Deviation High Alarm Full Scale High Alarm Full Scale...

Страница 7: ...compensatio Adjust the drift compensation code 6 6 6 6 count Select a proper status for Output 1 Output 1 ON Output 1 OFF Select Lock or F ree for the Security Level 0 Protect Lock all the Level 0 pa...

Страница 8: ...be added to the process value so that the process value will be read with minimum error For those process with bad circulation may use this parameter to compensate the temperature difference between...

Страница 9: ...r that parameter by using up key or down key Finally press and hold 3 2 seconds or longer now the new level value is entered If the level value is unchanged the above operation for entering can be omi...

Страница 10: ...is set parameters TI TD and CCT will have no effect on the system nor can the manual mode and the auto tune program be executed PV Time D action Perfect TD too high TD too low SP PV Time Time P action...

Страница 11: ...e to be used An error message will be shown in the display The manual control is used during Teaching the process The controller fails The manual control is an open loop control The process may rise t...

Страница 12: ...enabled by configuring the alarm 1 to act as a dwell timer If A1SF is set to time out on the alarm 1 relay will now operate as a timer contact with the contact being opened on initial start up The ti...

Страница 13: ...procedure connect a thermocouple to terminal 13 and 14 observing polarity and select a correct INPT for the thermocouple Switch the power on and let the controller to be powered for at least 30 minut...