background image

Other relay states: OFF, OVERRIDDEN ON, ON, BOUND ON, BOUND OFF
Other network command: ON
Other digital in state: OPEN
Load current in 0.25 Amp resolution
User defined threshold for generating digital load status
Other digital load status: ON
User defined load voltage from 0 Vac to 300 Vac
Relative load power
Other default power on states: ON, LASTSTATE
Other binding state: BOUND
User defined label
User defined label
Factory firmware version

<relayState>OVERRIDDEN OFF</relayState>
<lastCommand>OFF</lastCommand>
<digital

I

nputState>CLOSED</digital

I

nputState>

<loadCurrent>0.00 Amps</loadCurrent>
<loadCurrentThreshold>1.00 Amps</loadCurrentThreshold>
<loadCurrentState>OFF</loadCurrentState>
<loadVoltage>120.00 Vac</loadVoltage>
<loadPower>0.00 Watts (VA)</loadPower>
<powerOnState>OFF</powerOnState>
<bindingState>UNBOUND</bindingState>
<deviceHostName>Device Name</deviceHostName>
<deviceLocation>Device Location</deviceLocation>
<deviceVersion>v3.0.9 WRIBXV</deviceVersion>
<bss>
   <valid>0</valid>
   <name>0</name>
   <privacy>0</privacy>
   <wlan>0</wlan>
   <strength>0</strength>
</bss>
<scan>0</scan>
<ver>4615</ver>
<count>0</count>
<ssid>WRIB24XV</ssid>

</response>

Router information

}

Relay is commanded by webpage of device or by HTTP command. Local overrides are done manually by DIP switches and take precedence over webpage, HTTP commands, 

or Digital Input if Binding is enabled. Digital Input may be used for general purpose inputs and may be bound to relay to allow direct control of the relay with Digital Input. 

Use Default Relay Setting to determine power on state of relay after power cycle; On, Off, or Last Commanded State.

For proper power reading, set voltage to which load will be applied. 

For ON/OFF “Digital” Load Status, set Load Current Threshold – Load Current Status will indicate if load is ON (above threshold) or OFF (below threshold).

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide 

reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy, and if not installed 

and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in 

a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, 

the user is encouraged to try to correct the interference by one or more of the following measures:

• Reorient or relocate the receiving antenna.

• Increase the separation between the equipment and receiver.

• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

• Consult the dealer or an experienced radio/TV technician for help.

To read status information:

http://192.168.100.10/status.xml

Response will be in the following format:

<?xml version=”1.0” encoding=”utf-8”?>

<response>

Functional Devices, Inc.

 

     •      p: 800.888.5538      •      f: 765.883.7505      •      www.functionaldevices.com      •      [email protected]

071717