background image

Functional Devices, Inc.

 

     •      p: 800.888.5538      •      f: 765.883.7505      •      www.functionaldevices.com      •      [email protected]

# Relays & Contact Type:

Expected Relay Life:

Operating Temperature:

Operate Time:

Green LED:

Green LED:

Yellow LED:

Pink LED:

Red LED:

Dimensions:

Wires:

Approvals:

Housing Rating:

Gold Flash:

Relay Override Switch:

Current Sensor Range:

Wifi:

One (1) SPDT Continuous Duty Coil

10 million cycles minimum mechanical

-30 to 140° F

18mS

Device Status

Wifi Ad-Hoc Status

Wifi Infrastructure Status

Digital Input Status

Relay Status

4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple

16˝, 600V Rated

UL Listed, UL916, C-UL

 

FCC, Wifi Certified ASD Device

 

UL Accepted for Use in Plenum,  NEMA 1 No

DIP Switch Control

0.50 Amp - 20 Amps, in 0.25 Amp increments

 

IEEE 802.11 b/g/n Compatible

2 Mbps Data Rate

-91 dBm Min. Sensitivity 

+102 Bm Max Output Power

Currently Unsecured Connection

(WPA-PSK or WPA-2-PSK Available)

Supports PING and ARP

DSSS Modulation

RIBTWXV-WI Series

Wifi IEEE 802.11 Network Enclosed I/O Device: One Discrete Output (20 Amp Relay SPDT +  

Override), One Discrete Input (Dry Contact, Class 2); Analog and Digital Current and Relative  

Power

*

 Indication; 

24 Vac/dc; 120 Vac, 208 Vac, 240 Vac, or 277 Vac Power

Class 2

Dry Contact

Digital Input

2 1

OPEN

DIP Switch

CLOSED

24 Vac

24 Vdc

Common

DIP Switch Relay Control

DIP Switch

**

       Relay State

  1           2

0           1

Auto

1           X           Override ON
0           0           Override OFF

**

 0 = Open ; 1 = Closed

J1 - Not Used

RESET to Factory 

Defaults Pushbutton

(Activate with

insulated tool.)

Code 

Version 

3.1

Power Input:

 

24 Vac = Terminal Strip

24 Vdc = Terminal Strip (24 Vdc + 25% – 6%)

120 Vac = Wht/Blk Wire

208 Vac, 240 Vac, 277 Vac = Wht/Brn Wire

Neutral or Other Phase = Wht/Yel Wire

Device Settings by Network:

 Power up default relay state

 Host name and location labels

 Relay bound to digital input 

 Current threshold for go/no-go status

 Load voltage entry for power conversion

Device Settings:

 

 Local Override

 Reset to Network Defaults Pushbutton 

Specifications

Network Compatible Relay / Current Sensor Combos

Notes:

 This device is not intended for revenue 

grade power measurement. However, in 

addition to Wifi load control, this device is 

useful for building audits or LEED programs 

requiring relative readings to inexpensively  

pinpoint high power usage equipment or 

to identify energy waste due to equipment 

maintenance requirements or 

malfunction. 

*

Power Input Ratings:

125 mA Max  @  24 Vac 

88 mA Max  @  24 Vdc

120 mA Max  @  120 Vac (RIBTWXV2401B-WI)

120 mA Max  @  208 Vac (RIBTWXV24208B-WI)

120 mA Max  @  240 Vac (RIBTWXV24240B-WI)

120 mA Max  @  277 Vac (RIBTWXV24277B-WI)

Available TCP/IP Settings:

 

 IP Address (Static)

 Port Number

 Subnet Mask

 Gateway

 Ad-Hoc mode

 Infrastructure mode

 Scan for wireless networks

Contact Ratings:

 

20 Amp Resistive  @  277 Vac

20 Amp Ballast  @  120/277 Vac (N/O)

10 Amp Ballast  @  120/277 Vac (N/C)

Not rated for Electronic Ballast

10 Amp Tungsten  @  120 Vac (N/O)

2 HP  @  277 Vac

1 HP  @  120 Vac

RIBTWXV-WI Series Selection Guide

Model#

24 Vac/dc

120 Vac

208 Vac

240 Vac

277 Vac

RIBTWXV2401B-WI

RIBTWXV24208B-WI

RIBTWXV24240B-WI

RIBTWXV24277B-WI

Setup Instructions available on website.

http://www.functionaldevices.com/pdf/bulletins/B1598_393186.pdf

Or scan QR code with your smart phone.

Wifi

Made in USA

Meets

 

Buy American

 

of ARRA 2009

RED LED = Relay Status

PINK LED = Digital Input Status

YELLOW LED = Wifi Infrastructure Status

GREEN LED = Wifi Ad-Hoc Status

GREEN LED =  

Device Status LED

Wht/Yel Wht/Blk

or

Wht/Brn

Blu

N/C

Yel

COM

Org

N/O

Power

Sensing