Proper battery installation is the first step in getting the best performance out of
your Fullriver battery.
2.1 - SELECTING THE APPROPRIATE CABLE SIZE
Cables must be sized to carry the maximum expected load. Under-sized cables can
result in over-heating, melted connections and are a potential fire hazard.
Refer to
TABLE 1
below for the current carrying capacity by cable size. These values
are for cable lengths of 6 feet (1.83 meters) or less. It is preferable that all cables in a
series connection or in a parallel connection are the same length.
To significantly reduce the amount of heat generated at the terminals,
use cables with solder-dipped ends.
Installation
25
30
40
55
75
95
130
150
170
265
360
Ampacity (Amps)
14
12
10
8
6
4
2
1
1/0
2/0
3/0
Cable Gauge (AWG)
TABLE 1