F01 - Access Code:

This is required to change the settings of the parameters. This code does not need to be entered to view 
the adjusted parameters.
Allows you to enter the access codes provided:

[,123]

- Enables you to change the table parameters;

[,231]

- Allows you to configure the temperature measurement units;

F02 - Desired temperature (setpoint) (r1):
F03 - Desired temperature (setpoint) (r2):
F04 - Desired temperature (setpoint) (r3):
F05 - Desired temperature (setpoint) (r4):

It is the control temperature of the normal operating mode. When the temperature of the S1 sensor 
(room sensor) is lower than the value set for this function, the compressor will be turned off.

F06 - Desired temperature (economy setpoint) (r1):
F07 - Desired temperature (economy setpoint) (r2):
F08 - Desired temperature (economy setpoint) (r3):
F09 - Desired temperature (economy setpoint) (r4):

It is the control temperature when the economy operating mode is on. When the temperature of the S1 
sensor (room sensor) is lower than the value set for this function, the compressor will be turned off.

F10 - Minimum desired temperature (setpoint) allowed to the user:
F11 - Maximum desired temperature (setpoint) allowed to the user:

Limits  set  in  order  to  avoid  excessively  high  or  low  temperatures  being  accidentally  set  for  the 
temperature  setpoint,  which  could  lead  to  high  energy  consumption  by  keeping  the  system  on 
continuously.

F12 - Operating setpoint control differential:
F13 - Differe control of economy setpoint:

It is the temperature difference between turning the cooling off and on again.

F14 - Fast Freezing Temperature Limit  (r1):
F15 - Fast Freezing Temperature Limit (r2):
F16 - Fast Freezing Temperature Limit (r3):
F17 - Fast Freezing Temperature Limit (r4):

This is the minimum temperature that the instrument can reach during the Fast Freezing process.

F18 - Maximum Fast Freezing time:

This the duration of the Fast Freezing process.

F19 - Delay time when powering up the controller:

When the instrument is turned on, it can remain disabled for a while, delaying the start of the process. 
During this time, it only works as a temperature gauge. Helps to avoid high demands for power, when 
power returns after a power cut, where several pieces of equipment are all on the same connection. 
Therefore, you can set different times for each device. This delay can relate to the compressor or 
defrosting (where defrosting is part of the sequence).

F20 - Defrost type (0 = resistance/ 1 = hot gas / 2 = natural):

[,,,0]

- Electrical Defrosting (using coils), which only applies to the defrost outlet.

[,,,1]

 - Hot Gas Defrosting, which only applies to the compressor and defrosting outlets.

[,,,2]

 - Natural defrosting, which only applies to the fan outlet.

F21 - Condition for starting defrosting:

[OFF,]

 - No automatic defrosting, only manual defrosting;

[,,,1]

- Set time to start defrosting;

[,,,2]

 - Set temperature to start defrosting;

[,,,3]

 - Set temperature difference (S1-S2) to start defrosting;

[,,,4]

 - Set temperature and temperature difference (S1-S2) to start defrosting.

F22 - Interval between defrosting periods if 

[,F21]

 =1 or the Maximum time without defrosting 

if 

[,F21]

 = 3 or 4:

It  determines  how  often  and  after  how  long  defrosting  take  place,  based  on  the  time  of  the  last 
defrosting. If the controller is configured to defrost according to temperature (

[F21] 

= 2, 3 or 4), this 

time acts as a level of safety in situations in which the evaporator temperature (S2 sensor) does not 
reach the values programmed in

 [F24]

 or 

[F25]

. This function determines the maximum time that 

the controller will wait before carrying out defrosting.

F23 - Additional time at the end of the first refrigeration cycle:

This is to set a longer period of time for the first refrigeration cycle. Where there are setups with several 
pieces of equipment, you can avoid high demand peaks by ensuring that defrosting takes place at 
different times by assigning different values to this function.

F24 - Temperature of the evaporator (S2 sensor) in order to begin defrosting if 

[,F21] 

= 2, 3 or 

4:

When the temperature of the evaporator (S2 sensor) reaches a value using this function, the controller 
will wait for the length of time before beginning defrosting.

F25- Temperature Difference in order to start defrosting (S1-S2) if 

[,F21]

 = 3 or 4:

When the difference between the temperature of the room sensor (S1 sensor) and the temperature of 
the evaporator (S2 sensor) reaches a value using this function, the controller will wait for the length of 
time before beginning defrosting.

F26-Time  to  confirm  the  lower  temperature  (sensor  S2)  to  start  the  pre-defrost  setting  if 

[,F21]

 = 2, 3 or 4

If the controller is configured to defrost according to temperature, the moment the temperature reaches 
the set value, it will run a delay before starting the pre-defrost stage.
If the temperature remains low, while this stage is running, the pre-defrost process is started. If it 
doesn’t and the temperature rises above the set value, the system will return to a refrigeration cycle.

F27-Defrost when the controller is powered on:

This enables a defrosting to be conducted when the controller is powered on. For example, when the 
electricity returns after a power cut.

F28 - Smooth Defrost if 

[,F20]

 = 0:

Smooth  Defrost  mode  provides  a  smoother  defrosting,  saving  energy  and  preventing  the  room 
temperature from rising as much as in a standard defrost. In this mode, the defrost output remains on 
as long as the evaporator temperature (S2 sensor) is less than 2°C (35.6°F) and, after passing that 
temperature, the output remains on for the percentage of time configured in this function, within a 2 
minute period.

F29 - Enable Tray Defrost:

With this function active, the FAN output starts to operate as a Second defrost output. This output is 
activated during the pre-defrost, defrost and drain periods.

Note:

 

With

 [F29]

 = On, the functionalities related to the fan control are disregarded.

F30 - Length of pre-defrost (collecting in gas):

When the defrost starts, the controller will only use the fan during this time, in order to take advantage of 
the residual energy of the gas.

F31 - Temperature of the Evaporator (S2 sensor) to finish the defrost:

If the temperature in the evaporator (sensor S2) reaches the set value, the defrost cycle will be halted, 
i.e., temperature controlled. This way it improves the defrosting process.

F32 - Temperature of the Ambient Sensor (S1 sensor) to finish the defrost:

If the room temperature (sensor S1) reaches the set value, the defrost cycle will be halted due to 
temperature.

F33 - Maximum time on defrost (for safety):

This function adjusts the maximum duration of a defrost cycle. If the defrosting is not complete, during 
this period, according to the temperature, a dot will begin flashing in the lower right corner of the display 
(if  it’s  enabled  in

 [F77]

),  indicating  that  the  time  set  for  the  defrost  has  ended  by  the  required 

temperature has not been reached. This can happen when the temperature set is too high, the time 
limit is insufficient, the S2 sensor is disconnected, or it isn’t in contact with the evaporator.

F34 - Draining time (from water collected from defrosting):

Time required for removing excess water, i.e., for the last drops of water to drain from the evaporator. 
During this period, all outputs remain switched off. This function can be turned off by setting it to the 
minimum value 

[OFF,]

.

F35 - Fan operation mode:

[,,,0]

 - Automatic according to time: the fan will be on when the compressor is on. When the 

compressor is off, the fan will oscillate according to the times set in 

[F36]

 and

 [F37]

[,,,1]

 - With the compressor on, the fan is on. With the compressor off, the fan turns on when the 

temperature is higher than the se 60% of the hysteresis and turns off when the temperature is 
lower than the se20% of the hysteresis;

[,,,2]

 - Continuous: the fan is always on;

[,,,3]

 - Dependent: the fan operates together with the compressor;

[,,,4]

- For a period of time after the compressor is turned off: after turning off the compressor, the 

fan will remain on for the time set in 

[F36]

.

Note 1:

 Modes 0 and 1 will only switch the fan on if the temperature of the S2 sensor is lower than the 

temperature of the S1 sensor.

Note 2:

 Mode 1 will activate the fan only if the temperature of sensor S2 is lower than the configured 

setpoint.

F36 -Time fan is on if 

[,F35] 

= 0 or 4:

This is how long the fan is on for.

F37 - Time fan is turned off is 

[,F35]

 =0 (automatic timed mode) :

This is how long the fan is off for.

F38 - Length of time door is open until fan is turned off 

[,F42]

 = 1 or2:

This is the length of time that the fan will continue to run after the door is opened. 
If you set a minimum value of 

[OFF,]

, the fan will not switch off if the door is opened.

If you set a value of 

[,,,0]

, the fan will switch off immediately if the door is opened.

8.19.1 Description of the parameters

CONDEN

SER

[,F82]

[,F81]

[,F83]

[,F84]

[,F85]

[,F86]

[,F87]

[,F88]

[,F89]

[,F90]

[,F91]

[,F92]

[,F93]

[,F94]

[,F95]

0 (Off)

 

 

0(Off)

 

 

105,0

 

 

105,0

 

 

105,0

 

 

105,0

 

 

221,0

 

 

221,0

 

 

0 (Off)

 

 

0 (Off)

 

 

221,0

 

 

221,0

 

 

1

 

 

1

 

 

3,0

 

 

5,4

 

 

0,1

 

 

1

 

 

1

 

 

°C

 

 

°C

 

 

°F

 

 

°F

 

 

minutes

 

 

minutes

 

 

°C

 

 

°F

 

 

-

 

 

-

 

 

20,0

 

 

0

 

 

0

 

 

36,0

 

 

1

 

 

0

 

 

15

 

 

15

 

 

0 (Off)

 

 

1

 

 

-

 

 

-

 

 

seconds

 

 

seconds

seconds

 

 

seconds

 

 

seconds

 

 

°C

 

 

°F

°C

 

 

°F

 

 

seconds

 

 

-

 

 

-

 

 

15

 

 

0 (Off)

 

 

15

 

 

0 (Off)

 

 

°C

 

 

°F

 

 

-

 

 

-

 

 

-

 

 

-

 

 

999

 

 

999

 

 

2

 

 

2

 

 

20

 

 

20

 

 

20,0

 

 

36,0

 

 

3

 

 

3

 

 

2

 

 

2

 

 

20

 

 

0 (Off)

 

 

0 (Off)

 

 

0,0

 

 

0,0

 

 

0,0

 

 

0,0

 

 

20,0

 

 

60

 

 

2

 

 

60

 

 

2

 

 

0,1

 

 

0 (Off)

 

 

-20,0

 

 

-36,0

 

 

0

 

 

0 (Off)

 

 

0 (Off)

 

 

0 (Off)

 

 

0 (Off)

 

 

20

 

 

36,0

 

 

20

 

 

36,0

 

 

0 (Off)

-36,0

 

 

-36 (Off)

 

 

15

 

 

0 (Off)

 

 

0,0

 

 

0,0

 

 

0 (Off)

 

 

1

 

 

1

 

 

0

 

 

0

 

 

0

 

 

0

 

 

0

 

 

0

 

 

-20,0

 

 

-21,1 (Off)

 

 

15

 

 

0 (Off)

 

 

Maximum capacitor temperature (S3) to switch off control outputs if 

[,F42]

 = 13

 

 

High condenser temperature alarm (S3) if 

(visual and audible only)

[,F42]

 = 13 

 

 

Control differential for maximum condenser temperature (hysteresis) if 

[,F42]

 = 13

 

 

Digital filter actuation mode

 

 

Intensity of the digital filter on the room temperature sensor (S1 sensor) (Rising)

 

 

Intensity of the digital filter on the room temperature sensor (S1 sensor) (Descending)

 

 

Displacement of the values from the room sensor (S1 sensor)

 

 

Displacement of the values from the evaporator sensor (S2 sensor)

 

 

 

[,F42]

 = 13

Displacement of the auxiliary sensor indication (sensor S3) if

 

 

Preferred indication on the display

 

 

Ambient Temperature (S1 sensor) value locked in during defrosting

 

 

Maximum length of time that the temperature is locked during defrosting

 
 

Mode for locking functions

 

 

Function Lock Period

Shutdown of control functions

 

 

SENSORS

FUNCTIONS

Mín

Máx

Default

Unit

Descrição

Fun

Mín

Máx

Default

Unit

CELSIUS (°C)

FAHRENHEIT (°F)

Содержание TC-970E+ECO Faston

Страница 1: ...SEALTHATPREVENTSANYLIQUIDSENTERINGTHEOPENINGANDTHECONTROLLER Power supply Control Temperature Temperature Resolution Average consumption Digital input Maximum Sizes mm Degree of protection 0 1 C 0 1 F...

Страница 2: ...eaudiblealarm brieflypressthe key 8 5 Manual defrost To start stop defrost regardless of the schedule press the key for 4s until the message dEFr appears Then release it The message On will be display...

Страница 3: ...iod of time the defrost will be runfirstandthenitwillgointofastfreezingmode 8 14 Display output frequency The output frequency applied to the variable compressor can be viewed by pressing the key unti...

Страница 4: ...F55 1 On 999 F55 1 On 999 F54 105 0 999 F54 221 0 105 0 500 999 40 0 0 Off 5 104 0 Off 5 1 150 0 Off 1 150 0 Off 4 30 0 Off 4 30 0 Off 999 300 999 105 0 F54 999 9999 221 0 F54 999 9999 999 999 13 999...

Страница 5: ...or example when the electricityreturnsafterapowercut F28 SmoothDefrostif F20 0 Smooth Defrost mode provides a smoother defrosting saving energy and preventing the room temperature from rising as much...

Страница 6: ...parameterworksinconjunctionwith F59 and F60 F59 VariablecompressortimeonincaseoferrorinsensorS1 roomsensor F60 VariablecompressortimeoffincaseoferrorinsensorS1 roomsensor If the room sensor S1 sensor...

Страница 7: ...rtiallocking wherethecontrolfunctionswillbeblockedbuttheadjustmentofthe setpointsandthealterationoftherecipesremainreleased 2 Enablestotallocking leavingonlyaccesstothefunctionsofthefacilitatedmenuava...

Страница 8: ...ols WARRANTY FULL GAUGE CONTROLS Products manufactured by Full Gauge Controls as of May 2005 have a two 02 year warranty as of the date of the consigned sale as stated on the invoice They are guarante...

Отзывы: