Full Gauge Controls MT-444E Faston Скачать руководство пользователя страница 1

Fast 

Freezing

 1. DESCRIPTION

The 

MT-444

Faston

  has  3  recipe  options,  each  with  its  control  temperature  and  their 

differentials (hysteresis), as well as specific keys for triggering / disabling and turn the lamp on / off, in 
addition to fast freezing functionality. It also has a digital filter, which has the purpose of simulating an 
increase in mass in the ambient sensor (S1), delaying its response time (thermal inertia) and avoiding 
unnecessary compressor trips. It also includes an intelligent blocking of functions and a shutdown mode 
of the control functions.
Product conforming to UL Inc. (United States and Canada).
 

 2. SAFETY RECOMMENDATIONS

- Check the controller for correct fastening;
- Make sure that the power supply is off and that it is not turned on during the controller installation;
- Read the present manual before installing and using the controller;
- Use adequate Personal Protective Equipamenet (PPE); 
- For application at sites subject to water spills, such as refrigerated counters, install the protecting vinyl 
supplied with the controller;
-  For  protection  under  more  critical  conditions,  we  recommend  the  Ecase  cover,  which  we  make 
available as an optional item (sold separately);
- The installation procedures should be performed by a qualified technician.

 3. APPLICATIONS

        

• Beverage displays;        • Reach-in coolers;
• Refrigeration counters;
• Up right freezers.

 4.TECHNICAL SPECIFICATIONS

evolution

 

 

V

er

.04

Setpoint Temperature

5. INDICATORS AND KEYS

Upper key

Lower  key

Set Key

Quick Access 
Menu Key (Flatec)

Refrigeration indicator LED

Defrost indicator LED

Temperature unit indicator LED

- 50 to 75°C (-58 to 167°F)

Power supply

MT-444E Faston: 

115 or 230Vac ±10%(*) (50/60 Hz)

MT-444EL Faston: 

12 or 24Vac/dc +10%(*)    

 

Operating humidity

10 to 90% RH (without condensation)

(*) Admissible variation in relation to the voltage rating.
(**) Maximum dimensions without connectors.

Maximum dimensions (**) (mm)

Cutouts dimensions (mm)

76 x 34 x 84 (WxHxD)
X = 71±0,5  Y = 29±0,5  (see Image V)

Digital input

Dry contact type configurable

6. WIRING DIAGRAM

The 

sensor S1

 must be in the ambient.

The

 sensor S2

 must be placed in the evaporator 

through metallic cramp.

6.1. Temperature sensors connection

 

- Connect the 

sensor S1

 wires to terminals "1 and 2", wires of 

sensor S2

 to terminals "3 and 4" and wires 

of 

sensor S3

 to terminals ‘’5 and 6'’: the polarity is not relevant.

- Length of the sensor cables can be increased by user himself to up to 200 meters, using a PP 2x24 AWG 
cable.

6.2. Recommendations of IEC60364 standard

a) 

Install overload protectors in the controller supply.

b)

 Install transient suppressors – suppressor filter RC – in the circuit to increase the service life of the 

controller relay. See connection instructions of the filter on the previous page.

c) 

The  sensor  cables  may  be  together,  but  not  in  the  same  conduit  where  the  power  supply  of  the 

controller and/or of the loads passes through.

Light indicator LED

Fan indicator LED

Power-saving mode indicator LED

MT-444

Controller power supply

Use the pins according to table below, considering the set version:

Pins

MT-444E Faston

MT-444EL Faston

9 and 10

9 and 11

115 Vac
230 Vac

12 Vac/dc
24 Vac/dc

DIGITAL REFRIGERATION 

CONTROLLER

Control 

functions 

shutdown

Functions 

lock

Serial 

Programming

Protection

level

On/off 

light

IP 65

FRONT

Power-saving 

mode

Connector 

for quick 
coupling

Buzzer

Approximate consumption

3.4 VA

NEW CONNECTION SYSTEM (QUICK COUPLING):

FASTON and PUSH-IN FAST

CONNECTION:

- Hold the wire near its end and insert it into the 
desired slot.
-  If  necessary,  press  the  bottom  to  assist  the 
connection.

DISCONNECT:

- To disconnect the cord, press the bottom and 
remove it.

NOTE:

-  In  the  connectors  1  to  6  the  maximum  wire 
diameter that can be used is 1,5mm².
- The wires must be tinned or use Rocket Pin 
terminals with a maximum diameter of 0,75mm².

BOTTOM

WIRE INPUT

The wire should be picked
in  5  mm  and  tinned.

Terminal Rocket Pin.

 7. FIXING PROCEDURE 

a)

 Cutout the panel plate (Image V - item 13) where the controller will be fixed, with dimensions              X 

= 71±0,5 mm and Y = 29±0,5 mm;

b)

 Remove the side locks (Image VI - item 13): To do this, squeeze the elliptical central part (with the Logo 

Full Gauge Controls) and move the latches back;

c)

 Pass the wires through the cutout of the plate (image VII - Item 13) and make the electrical installation 

as described in item 6;

d)

 Insert the controller into the panel cutout, from the outside in;

e)

 Replace the latches and push then until they are pressed against the panel, securing  the controller to 

the housing (see arrow in Figure VI - item 13);

f)

 Adjust the parameters as described in item 9.

      WARNING:

 

for installations requiring liquid-tight sealing, the cut-off for the installation of the 

controller should be at must 70.5x29mm. The side latches must be secured so that they press the 
rubber sealing to prevent infiltration between the cutout and the controller.
Vinyl protector - Image IX (item 13)

Protects the controller should when installed in a place with splashing water, such as in refrigerated 
counters. This adhesive vinyl accompanies the instrument, on the packaging.

       IMPORTANT:

 

Apply only after completing electrical connections.

a)

 Retract the lateral locks (Image VI - item 13);

b)

 Remove the protective film from the adhesive side of the vinyl;

c)

 Apply the vinyl over the whole top, folding the flaps, as indicated by the arrows - Image IX (item 13);

d)

 Reinstall the latches.

NOTE:

 The vinyl is transparent, allowing to visualize the electric scheme of the instrument.

Image I - Connection 115 Vac

Image II - Connection 230 Vac

Image III - Connection 12 Vac/dc

Image IV - Connection 24 Vac/dc

3

4 5 6

7

8

9

10 11 12 13 14

D1/S3

DEFR

LIGHT

115 Vac

 S1

 S2

COMP

FAN

1

2

3

4 5 6

7

8

9

10 11 12 13 14

D1/S3

DEFR

LIGHT

230 Vac

 S1

 S2

COMP

FAN

1

2

3

4 5 6

7

8

9

10 11 12 13 14

12 Vac/dc

Power 
supply

DEFR

LIGHT

COMP

FAN

1

2

D1/S3

 S1

 S2

3

4 5 6

7

8

9

10 11 12 13 14

24 Vac/dc

Power 
supply

DEFR

LIGHT

COMP

FAN

1

2

D1/S3

 S1

 S2

MT444EF

AST

ONV04-01T

-17665

MT-444

Faston

MT-444

 

MT-444

 

E251415

Operating Temperature

Maximum current per output COMP

873

60730-1

UL / CSA Standards

12(8)A / 240V 1HP

5A / 250Vac 1200W
1/8HP / 250Vac
1A E-Ballast / 250Vac

3A / 240Vac 720W
5(3)A / 240Vac
5W LED / 240Vac

12(8)A / 240V 1HP

-10 a 60°C / 14 a 140°F

-10 a 50°C / 14 a 122°F

Maximum current per output
DEFR / FAN / LIGHT

 Note: Only Coating controllers from version 04 onwards meet Standard 60730-1.

Содержание MT-444E Faston

Страница 1: ...nd 10 9 and 11 115 Vac 230 Vac 12 Vac dc 24 Vac dc DIGITAL REFRIGERATION CONTROLLER Control functions shutdown Functions lock Serial Programming Protection level On off light IP 65 FRONT Power saving mode Connector for quick coupling Buzzer Approximate consumption 3 4 VA NEW CONNECTION SYSTEM QUICK COUPLING FASTON and PUSH IN FAST CONNECTION Hold the wire near its end and insert it into the desire...

Страница 2: ...icktouchorusethequickaccessmenu Item8 1 8 4 Silencing the alarm Tosilencetheaudiblealarm pressthe key quicktouch 8 5 Manual Defrost To start stop a manual defrost regardless of the schedule press and hold the key for 6s until the dEFr message appears Then release it The On message will appear when it has started and the OFF message when it has been stopped It can also be accessed through the quick...

Страница 3: ...e sensor S1 temperature room is lower than the configured value for this function the compressor willbeturnedoff This is the control temperature when the power saving mode is active If the sensor S1 temperature room is lower than the configured value for this function the compressor will be turned off Limitspreventingtheaccidentalsetupofanexcessivelyhighorlowtemperaturesetpoint whichcouldresultinh...

Страница 4: ...esandwhenitfalls 1 The filter operates only when the temperature rise When the temperature fall theresponseisimmediate Intensity of the digital filter applied to the room sensor sensorS1 Thevalueadjustedinthisfunctionrepresentsthetime inseconds forthetemperatureto change by 0 1 C Atypical application for this type of filter is for ice cream and frozen food frezzers as when the door is opened a mas...

Страница 5: ...is function is to stop the evaporator fan until the room temperature approaches that listed in the project thus preventing a high temperature and suction pressure which can damage the compressor If the evaporator temperature surpasses that of the value the faz is turned off turning back on with a set hysteresis of 2 C 4 F It is a valuable resource when for example cooling equipment has been inacti...

Страница 6: ...he LED indicator for the lightoutputisconstantlyoff 3 0 0 no 999 H no Operating Mode Lamp Output Alarm Door Resistance 2 2 no f67 f68 0 999 min 20 0 999 min 10 CELSIUS FAHRENHEIT FUN MIN MAX UNIT DEFAULT DESCRIPTION FUNCTION If the room sensor sensor S1 is disconnected or out of its measuring range the compressorwillturnonandoffaccordingtothesetupconfiguredinthesefunctions Compressor ON time in ca...

Страница 7: ...fr Defrost LOC Blocked No No OFF Turnedoff disabled ON Turnedon enabled Refr Refrigeration SET asin Setting settingorconfiguration 12 OPTIONAL ITEMS Sold Separately Ecase protective cover It is recommended for the Evolution line keeps water from entering the back part of the instrument It also protects the productwhentheinstallationsiteiswashed NOTE Ecase is compatible with the use of small type F...

Страница 8: ...he product is violated or repaired by any person not a member of the technical team of Full Gauge Controls Damage has been caused by a fall blow and or impact infiltration of water overload and or atmospheric discharge USE OF WARRANTY To make use of the warranty customers must send the properly packaged product to Full Gauge Controls together with the invoice or receipt for the corresponding purch...

Отзывы: