Line
Function
Setting range
or display
Setting
increment
Basic
setting
1150
I
)
Off
- Off: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational h ready heating.
- Ready h operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
1151
I
Floor curing setpoint manually
(if line 1150 = manual)
0 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying program stops automatically after running for 25 days.
1156
I
Floor curing day current
0 32
1157
I
Floor curing day completed
0 32
0
1200
S
Operating mode changeover
None, Protection mode,
Reduced, Comfort, Automatic
Reduced
Operating mode at end of concrete slab drying period.
Cooling circuit 2
If the installation is fitted with the cooling kit (Only with the cooling kit option).
1201
U
Operating mode
Protection, Automatic, Reduced,
Comfort
Protection
1202
U
Comfort cooling setpoint
17 40 °C
0,5 °C
24 °C
1203
U
Reduced setpoint
5 40°C
26 °C
1208
I
Flow temp setp at OT° 25°C
6 35 °C
0,5 °C
20 °C
1209
I
Flow temp setp at OT° 35°C
6 35 °C
0,5 °C
16 °C
1212
I
Cooling limit at OT°
8 35 °C
0,5 °C
24 °C
1213
S
Lock time at end of heating / cooling
8 100
1 h
24 h
1218
S
Summer comp start at OT°
20 50 °C
1 °C
26 °C
1219
S
Summer comp end at OT°
20 50 °C
1 °C
40 °C
1220
S
Summer comp setp increase
1 10 °C
1 °C
4 °C
1223
S
Flow temp setp min OT° 25°C
6 35 °C
0,5 °C
18 °C
1224
S
Flow temp setp min OT° 35°C
6 35 °C
0,5 °C
18 °C
1228
S
Room influence
1... 100 %
1 %
80 %
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1232
S
Room temp limitation
0,5... 4 °C
0,5 °C
0,5 °C
1238
S
Mixing valve decrease
0 20 °C
1 °C
0 °C
1241
S
Actuator running time
30... 873 s
1 s
240 s
1263
S
With prim contr / system pump
No, Yes
No*
*Basic setting : 1 circuit = No ; 2 circuits = Yes.
Installation and operation manual "1764 - EN"
Air to Water Heat Pump, split system
- 56 -
Содержание WOYA060LFCA
Страница 23: ... Installation and operation manual 1764 EN 23 Air to Water Heat Pump split system ...
Страница 29: ... Installation and operation manual 1764 EN 29 Air to Water Heat Pump split system ...
Страница 33: ...Installation and operation manual 1764 EN 33 Air to Water Heat Pump split system ...
Страница 35: ... Installation and operation manual 1764 EN 35 Air to Water Heat Pump split system ...
Страница 71: ...Installation and operation manual 1764 EN 71 Air to Water Heat Pump split system ...
Страница 73: ... Installation and operation manual 1764 EN 73 Air to Water Heat Pump split system ...
Страница 79: ... Installation and operation manual 1764 EN 79 Air to Water Heat Pump split system ...
Страница 86: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 86 ...
Страница 87: ...Installation and operation manual 1764 EN 87 Air to Water Heat Pump split system ...
Страница 88: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 88 ...
Страница 89: ...Installation and operation manual 1764 EN 89 Air to Water Heat Pump split system ...
Страница 90: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 90 ...
Страница 91: ... Installation and operation manual 1764 EN 91 Air to Water Heat Pump split system ...