3 .4 .6
Pump down operation (Refrigerant collecting
operation) outdoor unit
"
Ensure that
the general electrical power
supply has been cut off before starting any
repair work.
"
stored energy: after disconnecting power
supplies wait 1 minute before accessing the
internal parts of the equipment.
Perform the following procedures to collect the
refrigerant.
-
1
-
Turn
OFF
the
start/stop
switch
(ref.
3
,
). Disconnect the outdoor
units power supply.
-
2
- Remove the front panel. Open the power control
box. Then turn
ON
the
DIP SW1
on the interface
board,
-
3
- Reconnect the power supply. Turn ON the start/
stop switch.(Green and Red LED on the board start
flashing ; 1 sec. on / 1 sec. off repeated). The outdoor
unit begins cooling operation about 3 minutes after
switching ON
-
4
-
Rapidly
: Set the parameter
7700
(
Relay output
QX1
) to
ON
. => The pump works normally.
Reminder: Press
OK
Hold on the key
for 3s
and select the level of access* used with the aid
of the knob
Confirm with the key
OK
* Choose “Specialist” level / Inputs / outputs test.
-
5
- Close the liquid valve on the outdoor unit 30 s
maximum
after operation starts.
-
6
- Close the gas valve on the outdoor unit as soon as
the pressure is lower 0,02 bar relative reading on the
Manifold
or 1-2 minutes after closing the liquid valve,
while the outdoor unit keeps running.
-
7
- Disconnect the power supply.
-
8
- The refrigerant collecting operation is over.
Remarks:
- The pump down operation cannot be activated even if
DIP SW1
is changed while heat pump's power is
ON
- Do not forget to turn back
DIP SW1
on the interface
board to
OFF
, after the pump down operation has
been completed.
- Select the "AUTO" heating mode.
- When the pump down operation is repeated,
temporarily turn OFF the start/stop switch after opening
the closed valves (both liquid and gas).
Interface card
LED2
(green)
LED1
(red)
OFF
ON
figure 24 - Location of DIP switches and LED
on the hydraulic unit interface card
Installation and operation manual "1764 - EN"
Air to Water Heat Pump, split system
- 28 -
Содержание WOYA060LFCA
Страница 23: ... Installation and operation manual 1764 EN 23 Air to Water Heat Pump split system ...
Страница 29: ... Installation and operation manual 1764 EN 29 Air to Water Heat Pump split system ...
Страница 33: ...Installation and operation manual 1764 EN 33 Air to Water Heat Pump split system ...
Страница 35: ... Installation and operation manual 1764 EN 35 Air to Water Heat Pump split system ...
Страница 71: ...Installation and operation manual 1764 EN 71 Air to Water Heat Pump split system ...
Страница 73: ... Installation and operation manual 1764 EN 73 Air to Water Heat Pump split system ...
Страница 79: ... Installation and operation manual 1764 EN 79 Air to Water Heat Pump split system ...
Страница 86: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 86 ...
Страница 87: ...Installation and operation manual 1764 EN 87 Air to Water Heat Pump split system ...
Страница 88: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 88 ...
Страница 89: ...Installation and operation manual 1764 EN 89 Air to Water Heat Pump split system ...
Страница 90: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 90 ...
Страница 91: ... Installation and operation manual 1764 EN 91 Air to Water Heat Pump split system ...