- 54 -
Line
Function
Setting range
or display
Setting
increment
Basic
setting
1150
I
Floor curing function (
fi
g. 51, page 52
)
O
ff
- O
ff
: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational h ready heating.
- Ready h operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends automatically
after 25 days.
1151
I
Floor curing setpoint manually
(if line 1150 = manual)
0... 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains
fi
xed.
The concrete slab-drying program stops automatically after running for 25 days.
1156
I
Floor curing day current
0... 32
0
1157
I
Floor curing day completed
0... 32
0
1200
S
Operating mode changeover
None, Protection mode,
Reduced, Comfort, Automatic
Reduced
Operating mode at end of concrete slab drying period.
Cooling circuit 2
If the installation is
fi
tted with the cooling kit (Only with the cooling kit option).
1201
U
Operating mode
Protection, Automatic, Reduced,
Comfort
Protection
1202
U
Comfort cooling setpoint
17... 40 °C
0.5 °C
24 °C
1203
U
Reduced setpoint
5... 40°C
0.5 °C
26 °C
1208
I
Flow temp setp at OT° 25°C
6... 35 °C
0.5 °C
20 °C
1209
I
Flow temp setp at OT° 35°C
6... 35 °C
0.5 °C
16 °C
1212
I
Cooling limit at OT°
--, 8... 35 °C
0.5 °C
24 °C
1213
S
Lock time at end of heating / cooling
--, 8... 100
1 h
24 h
1218
S
Summer comp start at OT°
20... 50 °C
1 °C
26 °C
1219
S
Summer comp end at OT°
20... 50 °C
1 °C
40 °C
1220
S
Summer comp setp increase
--, 1... 10 °C
1 °C
4 °C
1223
S
Flow temp setp min OT° 25°C
6... 35 °C
0.5 °C
18 °C
1224
S
Flow temp setp min OT° 35°C
6... 35 °C
0.5 °C
18 °C
1228
S
Room in
fl
uence
--, 1... 100 %
1 %
80 %
If the installation is
fi
tted with a room thermostat:
This function enables you to choose the ambient temperature's in
fl
uence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1232
S
Room temp limitation
--, 0.5... 4 °C
0.5 °C
0.5 °C
1238
S
Mixing valve decrease
0... 20 °C
1 °C
0 °C
1241
S
Actuator running time
30... 650 s
1 s
240 s
1263
S
With primary controller / system pump
No, Yes
No*
*Basic setting : 1 circuit = No ; 2 circuits = Yes.
Waterstage Split Comfort DHW Serie / INSTALLATION / 2125 - EN