Line
Function
Setting range
or display
Setting
increment
Basic
setting
850
I
Off
- Off: Early interruption of the current programme, programme inactive
- Operational heating
- Heating ready for occupation
- Operational h ready heating
- Ready h operational heating
- Manual: Manual mode enables you to programme your own concrete slab drying time The function ends
automatically after 25 days
"
Please comply with the
standards and instructions
of the manufacturer of
the building ! A good
performance of this function
is only possible with an
i n s t a l l a t i o n c o r r e c t l y
implemented (hydraulic,
electricity and adjustments) !
This function can be stopped
by anticipation when setting
the adjustment to "Off".
50
45
40
35
30
20
5
0
25
55
1
1
5
7
X
10
18
25
15
1
figure 3 - Diagram of the concrete slab drying programmes
Heating flow temperature °C
Operational h Heating ready for occupation
Heating ready for occupation
Day
Operational
heating
851
I
Floor curing setpoint manually
(if line 850 = manual)
0 95 °C
1 °C
25 °C
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying programme stops automatically after running for 25 days
856
I
Floor curing day current
0 32
857
I
Floor curing day completed
0 32
900
S
Operating mode changeover
None, Protection mode,
Reduced, Comfort, Automatic
1
Reduced
Operating mode at end of concrete slab drying period
Cooling circuit 1
If the installation is fitted with the cooling kit (Only with the cooling kit option).
901
U
Operating mode
Protection, Automatic, Reduced,
Comfort
Protection
902
U
Comfort cooling setpoint
17 40 °C
0,5 °C
24 °C
903
U
Reduced setpoint
5 40°C
26 °C
908
I
Flow temp setp at OT° 25°C
6 35 °C
0,5 °C
20 °C
909
I
Flow temp setp at OT° 35°C
6 35 °C
0,5 °C
16 °C
912
I
Cooling limit at OT°
8 35 °C
0,5 °C
24 °C
913
S
Lock time at end of heating / cooling
8 100
1 h
24 h
918
S
Summer comp start at OT°
20 50 °C
1 °C
26 °C
919
S
Summer comp end at OT°
20 50 °C
1 °C
40 °C
920
S
Summer comp setp increase
1 10 °C
1 °C
4 °C
923
S
Flow temp setp min OT° 25°C
6 35 °C
0,5 °C
18 °C
924
S
Flow temp setp min OT° 35°C
6 35 °C
0,5 °C
18 °C
Maintenance document "1792 - EN"
Split system single phase type
- 48 -