Clear 18:
Fan motor error (permanent stoppage)
Hydraulic Unit LED:
Green 9 flashes / Red 7 flashes
Outdoor Unit LED:
flash
Probable causes:
•
Fan motor failure
•
Motor protection
•
Main PCB failure
Check:
Clear 18:
1 Check fan rotation:
- Switch off the heat pump and rotate the fan manually
- If the fan or bearings are faulty, replace them
2 Check the ambient temperature around the motor:
- Check excessively high temperature around the fan
Wait until the temperature comes down again and switch the
fan back on
OK
OK
3 Check the main board output voltage:
- On the outdoor unit, check the output voltage (DC) of the following connectors:
Terminals
Voltage
1 (red)/ 3 (black)
240~400V (for 060LFCA and 080LFCA)
300~400V (for 100LFTA)
4 (white)/3 (black)
15 ±1 5V
FAN MOTOR
If the voltage is incorrect, replace Main PCB
Maintenance document "1792 - EN"
- 21 -
Split system single phase type