background image

En-6

Transportation of the unit

21 41 

 

WARNING

Do not touch the fins. Otherwise, personal injury could result.

 

CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful. If 

the outdoor unit is carried from the bottom, hands or fingers may be pinched.

Be sure to hold the handles on the sides of the unit. Otherwise, holding the suction 

• 

grille on the sides of the unit may cause deformation.

Handle

Handle

Installation of the unit

21 21 

Install 4 anchor bolts at the locations indicated with arrows in the figure.

• 

To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

• 

base (such as concrete blocks).

The foundation shall support the legs of the unit and have a width of 50 mm or more.

• 

Depending on the installation conditions, the outdoor unit may spread its vibration 

• 

during operation, which may cause noise and vibration. Therefore, attach damping 

materials (such as damping pads) to the outdoor unit during installation.

Install the foundation, making sure that there is enough space for installing the 

• 

connection pipes.

Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially 

• 

available M10 bolts, nuts, and washers.)

The bolts should protrude 20 mm. (Refer to the figure.)

• 

If overturning prevention is required, purchase the necessary commercially available 

• 

items.

(Unit : mm (in.))

650

(25-19/32)

370 

(14- 9/16)

Bottom side

4-ø12 (1-15/32) hole

Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 

bolt, nut and washer.)

Bolt

Nut 

Block

SYSTEM CONFIGURATION

PIPE INSTALLATION - 1

41 

Flare connection (pipe connection)

41 11 

 

CAUTION

Do not use mineral oil on a flared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

While welding the pipes, be sure to blow dry nitrogen gas through them.

The maximum lengths of this product are shown in the table. If the units are further 

apart than this, correct operation cannot be guaranteed.

Flaring

Use special pipe cutter and flare tool exclusive for R410A.

• 

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that the cuttings will not enter the pipe and remove 

any burrs.

(3)  Insert the flare nut (always use the flare nut attached to the indoor and outdoor 

units respectively) onto the pipe and perform the flare processing with a flare tool. 

Leakage of refrigerant may result if other flare nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

L

Check if [L] is flared uniformly 

and is not cracked or scratched.

Pipe

A

B

Die

Pipe outside  

diameter [mm (in1)]

Dimension A  [mm (in1)]

Dimension B

  

0

-  014

 

[mm (in1)]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5 (0 to 1/32)

9.1 (3/8)

9.52 (3/8)

13.2 (17/32)

12.70 (1/2)

16.6 (21/32)

15.88 (5/8)

19.7 (25/32)

19.05 (3/4)

24.0 (15/16)

When using conventional flare tools to flare R410A pipes, the dimension A should 

• 

be approximately 1/32 in. more than indicated in the table (for flaring with R410A 

flare tools) to achieve the specified flaring. Use a thickness gauge to measure the 

dimension A.

Pipe outside  

diameter  

[mm (in1)]

Width across flats

of Flare nut  

[mm (in1)]

6.35 (1/4)

17 (21/32)

9.52 (3/8)

22 (7/8)

12.70 (1/2)

26 (1-1/32)

15.88 (5/8)

29 (1-5/32)

19.05 (3/4)

36 (1-13/32)

Width across flats

Bending pipes

41 11 11 

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 

curvature of 100 mm (4 in.) or more.
If the pipe is bent repeatedly at the same place, it will break.

If pipes are shaped by hand, be careful not to collapse them.

• 

Do not bend the pipes at an angle of more than 90°.

• 

When pipes are repeatedly bent or stretched, the material will harden, making it 

• 

difficult to bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.

• 

Pipe connection

41 11 21 

 

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit 

correctly. If the centering is improper, the flare nut cannot be tightened smoothly.  

If the flare nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the outdoor unit pipe until immediately before 

connecting the connection pipe.
After installing the piping, make sure that the connection pipes do not touch the 

compressor or outer panel. If the pipes touch the compressor or outer panel, they will 

vibrate and produce noise.

9374747115_IM_En.indd   6

20/12/2553   8:58:43

Содержание R410A

Страница 1: ...TIONER OUTDOOR UNIT PART NO 9374747115 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado 9374747115_IM_En indd 1 20 12 2553 8 58 37 ...

Страница 2: ...ply refrigeration compressor oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigera...

Страница 3: ...g than with refrigerant models Also when storing the piping securely seal the openings by pinching taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Special tools for R410A 222222 Tool name Contents of change Gauge manifold Pressure is high and cannot ...

Страница 4: ...of this product are shown in the table If the units are further apart than this correct operation cannot be guaranteed Total max length a b c d 70 m 230 ft 1 Max length for each indoor unit a b c or d 25 m 82 ft Max height difference between outdoor unit and each indoor unit H1 15 m 49 ft Max height difference between indoor units H2 10 m 33 ft Min length for each indoor unit a b c or d 5 m 16 ft ...

Страница 5: ...the like to prevent their access Install the outdoor unit in a location that would not inconvenience your neighbors as they could be affected by the airflow coming out from the outlet noise or vibration If it must be installed in proximity to your neighbors be sure to obtain their approval If the outdoor unit is installed in a cold region that is affected by snow accumulation snow fall or freezing...

Страница 6: ...ere it is very dusty 7 Do not install the unit where people pass 8 Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible 9 Install the unit where connection to the indoor unit is easy Single outdoor unit installation 333333333 When the upward area is open When there are obstacles at the back side 100 m m 4 in or m ore When there are o...

Страница 7: ... a pipe cutter 2 Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dus...

Страница 8: ...of the specified capacity When selecting breaker please comply with the laws and the regulations of each country One breaker must be installed on the power supply of the outdoor unit Wrong selection and setup of the breaker will cause electric shock or fire Do not connect AC power supply to the transmission line terminal board Improper wiring can damage the entire system Connect the connector cord...

Страница 9: ...the specified wires connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the tab...

Страница 10: ...p to the specified pressure all at once but do so gradually 1 Increase the pressure up to 0 5 MPa 73 psi let it sit for about 5 minutes and then check for any decrease in pressure 2 Increase the pressure up to 1 5 MPa 218 psi let it sit for about 5 minutes and then check for any decrease in pressure 3 Increase the pressure up to the specified pressure the pressure designed for the product and then...

Страница 11: ...e air conditioner do not mix gas other than the specified refrigerant R410A inside the refrigerant cycle When charging the refrigerant R410A always use an electronic balance for refrigerant charging to measure the refrigerant by weight When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose...

Страница 12: ...val and cleaning 3 Give the operating manual and installation instruction sheet to the customer TEST RUN 888 The test run method may be different for each indoor unit that is connected Refer to the installation instruction sheet included with each indoor unit CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection Make a test run in ac...

Страница 13: ...9374747115_IM_En indd 12 20 12 2553 8 59 06 ...

Отзывы: