326
Upgrade and Maintenance Manual
TX2560 M2 / RX2560 M2
Expansion cards and backup units
9.4.3.2
Removing the FBU
Figure 232: Disconnecting the FBU adapter cable from the FBU cable
Ê
Press down on the locking latch on the FPU cable (see close-up) and
disconnect the FBU adapter cable.
Figure 233: Removing the FBU holder from the system air duct
Ê
Lift up the locking handle on the FBU holder (see circle) while sliding the
FBU holder in direction of the arrow as far as it will go (1).
I
After that, the shoulder screw caps on the system air duct will rest in
the wide ends of the keyhole slots on the FBU holder.
Ê
Lift the FBU holder from the system air duct (2).
Содержание PRIMERGY RX2560 M2
Страница 6: ...Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 ...
Страница 26: ...Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Contents ...
Страница 42: ...42 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Before you start ...
Страница 110: ...110 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Basic hardware procedures ...
Страница 152: ...152 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Power supply unit PSU ...
Страница 282: ...282 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Hard disk drive HDD solid state drive SSD ...
Страница 364: ...364 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Main memory ...
Страница 434: ...434 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Accessible drives ...
Страница 492: ...492 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 System board and components ...
Страница 508: ...508 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Converting a tower model to a rack model ...
Страница 544: ...544 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Cabling ...
Страница 568: ...568 Upgrade and Maintenance Manual TX2560 M2 RX2560 M2 Appendix ...