 3.10.2. Notes for electrical wiring

 WARNING

•  Wiring connections must be performed by a quali

fi

 ed person in accordance with the 

speci

fi

 cations. The voltage rating for this product is 208/230 V at 60 Hz. It should be 

operated within the range of 187 to 253 V.

•  Before connecting the wires, make sure the power supply is off.
•  Never touch electrical components immediately after the power supply has been 

turned off. Electrical shock may occur. After turning off the power, always wait 
10 minutes or more before touching electrical components.

•  Use a dedicated power supply circuit. Insuf

fi

 cient power capacity in the electrical 

circuit or improper wiring may cause electric shock or 

fi

 re.

•  Be sure to install an earth leakage breaker. 

Otherwise, it will cause electric shock or 

fi

 re.

•  A circuit breaker is installed in the permanent wiring. Always use a circuit that can 

trip all the poles of the wiring and has an isolation distance of at least 1/8 in (3 mm) 
between the contacts of each pole.

•  Use designated cables and power cables. Improper use may cause electric shock or 

fi

 re by poor connection, insuf

fi

 cient insulation, or over current.

•  Do not modify power cable, use extension cable or branch wiring. Improper use may 

cause electric shock or 

fi

 re by poor connection, insuf

fi

 cient insulation or over current.

•  Connect the connector cable securely to the terminal. Check no mechanical force 

bears on the cables connected to the terminals. Faulty installation can cause a 

fi

 re.

•  Use ring terminals and tighten the terminal screws to the speci

fi

 ed torques, 

otherwise, abnormal overheating may be produced and possibly cause serious 
damage inside the unit.

•  Make sure to secure the insulation portion of the connector cable with the cable 

clamp. Damaged insulation can cause a short circuit.

•  Fix cables so that cables do not make contact with the pipes (especially on high 

pressure side). Do not make power supply cable and transmission cable come in 
contact with valves (Gas).

•  Never install a power factor improvement condenser. Instead of improving the power 

factor, the condenser may overheat.

•  Be sure to perform the grounding work.

Do not connect grounding wires to a gas pipe, water pipe, lightning rod or grounding 
wire for a telephone.

 

- Connection to a gas pipe may cause a 

fi

 re or explosion if gas leaks.

 

- Connection to a water pipe is not an effective grounding method if PVC pipe is 

used.

 

- Connection to the grounding wire of a telephone or to a lightning rod may cause a 

dangerously abnormal rise in the electrical potential if lightning strikes.

 

- Improper grounding work can cause electric shocks.

•  Securely install the electrical box cover on the unit. An improperly installed service 

panel can cause serious accidents such as electric shock or 

fi

 re through exposure to 

dust or water.

•  Do not connect the AC power supply to the transmission line terminal board. 

Improper wiring can damage the entire system.

 CAUTION

•  The primary power supply capacity is for the air conditioner itself, and does not 

include the concurrent use of other devices.

•  If the electrical power is inadequate, contact your electric power company.
•  Install a breaker in a location that is not exposed to high temperatures. 

If the temperature surrounding the breaker is too high, the amperage at which the 
breaker cuts out may decrease.

•  When using an earth leakage breaker that has been designed solely for ground fault 

protection, be sure to install a fuse-equipped switch or circuit breaker.

•  This system uses an inverter, which means that it must be used an earth leakage 

breaker that can handle harmonics in order to prevent malfunctioning of the earth 
leakage breaker itself.

•  Do not use crossover power supply wiring for the outdoor unit.
•  If the temperature surrounding the breaker is too high, the amperage at which the 

breaker cuts out may decrease.

•  When the electrical switchboard is installed outdoors, place it under lock and key so 

that it is not easily accessible.

•  Start wiring work after closing branch switch and over current breaker.
•  Connection cable between indoor unit and outdoor unit is 208/230 V.
•  Be sure not to remove thermistor sensor etc. from power wiring and connection 

wiring. Compressor may fail if operated while removed.

•  Always keep to the maximum length of the connection cable. Exceeding the 

maximum length may lead to erroneous operation.

•  Do not start operation until the refrigerant is charged completely. The compressor 

will fail if it is operated before the refrigerant piping charging is complete.

•  The static electricity that is charged to the human body can damage the control PC 

Board when handling the control PC Board for address setting, etc.
Please keep caution to the following points.
Provide the grounding of Indoor unit, Outdoor unit and Option equipment.
Cut off the power supply (breaker).
Touch the metal section (such as the unpainted control box section) of the indoor or 
outdoor unit for more than 10 seconds. Discharge the static electricity in your body.
Never touch the component terminal or pattern on the PC Board.

•  Be careful not to generate a spark as follows for using a 

fl

 ammable refrigerant.

 

- Do not remove the fuse while power is on.

 

- Do not disconnect plug from the wall outlet and the wiring while the power is on.

 

- It is recommended to position the outlet connection in a high position. Place the 

cords so that they do not get tangled.

• Con

fi

 rm the indoor unit model name before connecting.

 ■

 How to connect wiring to the terminal

Caution when wiring cable 

•  When stripping off the coating of a lead wire, always use a special tool such as a wire 

stripper. If there is no special tool available, carefully strip the coating with a knife etc.

(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect 

to the terminal block.

(2)  Securely clamp the ring terminals to the wires using an appropriate tool so that the 

wires do not come loose.

Sleeve

Strip : 3/8 in (10 mm)

Ring terminal

(3)  Use the speci

fi

 ed wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

Wire

Screw with special washer

Ring terminal

Terminal blocks

Screw with 
special washer 

Wire

Ring terminal

(6)  Refer to the following table for the terminal screw tightening torques.

Tightening torque [lbs·in (N·m)]

M3.5 screw

7.0 to 8.8 (0.8 to 1.0)

M4 screw

10.6 to 15.9 (1.2 to 1.8)

M5 screw

17.7 to 26.5 (2.0 to 3.0)

3.10.3. Wiring method

 Connection diagrams

 CAUTION

When connecting the power supply cable, make sure that the phase of the power 
supply matches with the phase of the terminal board. If the phases do not match, the 
compressor will rotate in reverse and will not be able to compress.

1

3

2

1

2

3

L2

L1

Indoor unit

Terminal

Terminal

POWER SUPPL

Y

Single phase, 208/230 V

Earthing 
(grounding) line

Outdoor unit

Control line

(Inter Unit)

Power line

DISCONNECT 

SWITCH (Locally procured)

L2

L1

3

2

1

1 2 3 4

Outdoor unit terminal block

Indoor unit terminal block

Connection cable

Earth (ground) 
screw

Earth (ground) 
screw

Power supply cable

NOTES:  

Factory installed protective inline fuses for indoor units’ conductors are installed 
on the Power Supply PCB.

9319205403_IM_3L.indb   8

9319205403_IM_3L.indb   8

11/19/2019   9:02:48 AM

11/19/2019   9:02:48 AM

Содержание LM 12

Страница 1: ...uct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation for the outdoor unit This prevents water damage and abnormal vibration In an Area with High W...

Страница 2: ... earth ground the unit correctly and use the power cable combined with an Earth Leakage Circuit Breaker ELCB The units are not explosion proof and therefore should not be installed in explosive atmosphere This unit contains no user serviceable parts Always consult experienced service technicians for repairing When moving or relocating the air conditioner consult experienced service technicians for...

Страница 3: ...t Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes 2 3 2 Refrigerant pipe size and allowable piping length CAUTION Keep the piping length between the indoor unit and outdoor unit within the allowable tolerance The maximum lengths of this product are shown in the table If the units are further apart than t...

Страница 4: ...ignal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping Decide the mounting position with the customer as follows 1 Install the outdoor unit in a location which can withstand the weight of ...

Страница 5: ...9 15 16 252 15 11 16 399 3 2 3 Outdoor units installation multi row Unit in mm 1 Single parallel unit arrangement 4 100 or more 8 200 or more 20 500 or more 40 1 000 or more 2 Multiple parallel unit arrangement 8 200 or more 16 400 or more 40 1 000 or more 10 250 or more 80 2 000 or more 10 250 or more 40 1 000 or more 8 200 or more 8 200 or more 10 250 or more CAUTION Do not install the outdoor u...

Страница 6: ...before connecting the connection pipe 2 Centering the pipe against port on the outdoor unit turn the flare nut with your hand To prevent gas leakage coat the flare surface with alkylbenzene oil HAB Do not use mineral oil 3 Tighten the flare nut of the connection pipe at the outdoor unit valve connector Connection pipe liquid Connection pipe gas Flare nuts 2 way valve liquid 3 way valve gas 4 When ...

Страница 7: ...Gauge manifold Flare nuts Blank caps Vacuum pump Charging port Service valve gas Use a 3 16 in 4 mm hexagon wrench Charging port cap 3 9 Additional charging WARNING When moving and installing the air conditioner do not mix gas other than the specified refrigerant R410A inside the refrigerant cycle If air or other gas enters the refrigerant cycle the pressure inside the cycle will rise to an abnorm...

Страница 8: ...eaker itself Do not use crossover power supply wiring for the outdoor unit If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease When the electrical switchboard is installed outdoors place it under lock and key so that it is not easily accessible Start wiring work after closing branch switch and over current breaker Connection cable between ...

Страница 9: ... 16 20 3 4 19 05 3 8 10 1 2 13 5 8 16 13 16 21 When the ambient temperature and relative humidity exceed 89 6 F 32 C DB and 85 respectively please strengthen the heat insulation of refrigerant pipe 6 PUMP DOWN Pump down operation forced cooling operation To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal recover refrigerant by doing the forced cooling operat...

Отзывы: