En-3

 CAUTION

Series

Outdoor unit 

capacity

MINIMUM CIRCUIT 

AMPACITY

MAX. CKT. BKR.

LM

9

9.7 A

15 A

12

11.5 A

15 A

LZ

9, 12

13.4 A

15 A

15

16.5 A

20 A

LZ

(Cold region)

9, 12

14.4 A

15 A

15

17.5 A

20 A

•  

 Before starting work check that power is not being supplied to all poles of the indoor 
unit and outdoor unit.

•  

Install all electrical works in accordance to the national standard.

•  

 Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the 
units. (Both indoor unit and outdoor unit)

•  Install the circuit breaker nearby the units.

2.6. Additional charge

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 
of work.

Refrigerant suitable for a piping length of 49ft (15m) is charged in the outdoor unit at the 
factory.
When the piping is longer than 49ft (15m), additional charging is necessary.
For the additional amount, refer to the following table.

Pipe length

49 ft

(15 m)

65 ft

(20 m)

Rate

Additional refrigerant

None

+3.5 oz

(+100 g)

0.2 oz/ft

(20 g/m)

2.7. Operating range

Outdoor temperature

Cooling/Dry Mode 

About 14 to 115 °F 

Heating Mode

LM series (9, 12)

About 5 to 75 °F

LZ series (9, 12, 15)

About -5 to 75 °F

LZ (Cold region) series (9, 12, 15)

About -15 to 75 °F

3. INSTALLATION WORK

Make sure to obtain the customer’s approval for selecting and installing the outdoor unit.

3.1. Selecting an installation location

 WARNING

•  Securely install the outdoor unit at a location that can withstand the weight of the 

unit. Otherwise, the outdoor unit may fall and cause injury.

•  Be sure to install the outdoor unit as prescribed, so that it can withstand earthquakes 

and typhoons or other strong winds. Improper installation can cause the unit to 
topple or fall, or other accidents.

•  Do not install the outdoor unit near the edge of a balcony. Otherwise, children may 

climb onto the outdoor unit and fall off of the balcony.

2.3. Pipe requirement

2.3.1. Protection of pipes

•  Protect the pipes to prevent the entry of moisture and dust.
•  Especially, pay attention when passing the pipes through a hole or connecting the end 

of a pipe to the outdoor unit.

Location

Working period

Protection method

Outdoor

1 month or more

Pinch pipes

Less than 1 month

Pinch or tape pipes

Indoor

-

Pinch or tape pipes

2.3.2. Refrigerant pipe size and allowable piping length

 CAUTION

•  Keep the piping length between the indoor unit and outdoor unit within the allowable 

tolerance.

•  The maximum lengths of this product are shown in the table. If the units are further 

apart than this, correct operation cannot be guaranteed.

Model

LM series

LZ series

(includes cold region model)

9, 12 models

15 model

Pipe diameter <Liquid/Gas>  [in (mm)]

1/4 (6.35) / 3/8 (9.52)

1/4 (6.35) / 
1/2 (12.70)

Max. piping length (L) 

[ft (m)]

65 (20)

Max. height difference (H)
<Indoor unit to outdoor unit>  [ft (m)]

49 (15)

View (Example)

H

L

2.4. Power source

 WARNING

•  Always use a special branch circuit and install a special receptacle to supply power 

to the room air conditioner.

•  Use a circuit breaker and receptacle matched to the capacity of the air conditioner.
•  Install a leakage circuit breaker in accordance with the related laws and regulations 

and electric company standards.

•  The circuit breaker is installed in the permanent wiring. Always use a circuit that can 

trip all the poles of the wiring and has an isolation distance of at least 3 mm between 
the contacts of each pole.

 CAUTION

•  The power source capacity must be the sum of the air conditioner current and 

the current of other electrical appliances. When the current contracted capacity is 
insuf

fi

 cient, change the contracted capacity.

•  When the voltage is low and the air conditioner is dif

fi

 cult to start, contact the power 

company the voltage raised.

2.5. Electric requirement

 CAUTION

•  Be sure to install a breaker of the speci

fi

 ed capacity.

•  Regulation of cables and breaker differs from each locality, refer in accordance with 

local rules.

Voltage rating

1 ø 208/230 V (60 Hz)

Operating range

187-253 V

Cable

Type

Remarks

Power supply cable

14AWG

2 cable + Earth (Ground), 1 

ø 208/230 V

Connection cable

14AWG

3 cable + Earth (Ground), 1 

ø 208/230 V

Select the correct cable type and size according to the country or region’s regulations. 
Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 
diameter when the wire length is long.

9319205403_IM_3L.indb   3

9319205403_IM_3L.indb   3

11/19/2019   9:02:48 AM

11/19/2019   9:02:48 AM

Содержание LM 12

Страница 1: ...uct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation for the outdoor unit This prevents water damage and abnormal vibration In an Area with High W...

Страница 2: ... earth ground the unit correctly and use the power cable combined with an Earth Leakage Circuit Breaker ELCB The units are not explosion proof and therefore should not be installed in explosive atmosphere This unit contains no user serviceable parts Always consult experienced service technicians for repairing When moving or relocating the air conditioner consult experienced service technicians for...

Страница 3: ...t Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes 2 3 2 Refrigerant pipe size and allowable piping length CAUTION Keep the piping length between the indoor unit and outdoor unit within the allowable tolerance The maximum lengths of this product are shown in the table If the units are further apart than t...

Страница 4: ...ignal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping Decide the mounting position with the customer as follows 1 Install the outdoor unit in a location which can withstand the weight of ...

Страница 5: ...9 15 16 252 15 11 16 399 3 2 3 Outdoor units installation multi row Unit in mm 1 Single parallel unit arrangement 4 100 or more 8 200 or more 20 500 or more 40 1 000 or more 2 Multiple parallel unit arrangement 8 200 or more 16 400 or more 40 1 000 or more 10 250 or more 80 2 000 or more 10 250 or more 40 1 000 or more 8 200 or more 8 200 or more 10 250 or more CAUTION Do not install the outdoor u...

Страница 6: ...before connecting the connection pipe 2 Centering the pipe against port on the outdoor unit turn the flare nut with your hand To prevent gas leakage coat the flare surface with alkylbenzene oil HAB Do not use mineral oil 3 Tighten the flare nut of the connection pipe at the outdoor unit valve connector Connection pipe liquid Connection pipe gas Flare nuts 2 way valve liquid 3 way valve gas 4 When ...

Страница 7: ...Gauge manifold Flare nuts Blank caps Vacuum pump Charging port Service valve gas Use a 3 16 in 4 mm hexagon wrench Charging port cap 3 9 Additional charging WARNING When moving and installing the air conditioner do not mix gas other than the specified refrigerant R410A inside the refrigerant cycle If air or other gas enters the refrigerant cycle the pressure inside the cycle will rise to an abnorm...

Страница 8: ...eaker itself Do not use crossover power supply wiring for the outdoor unit If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease When the electrical switchboard is installed outdoors place it under lock and key so that it is not easily accessible Start wiring work after closing branch switch and over current breaker Connection cable between ...

Страница 9: ... 16 20 3 4 19 05 3 8 10 1 2 13 5 8 16 13 16 21 When the ambient temperature and relative humidity exceed 89 6 F 32 C DB and 85 respectively please strengthen the heat insulation of refrigerant pipe 6 PUMP DOWN Pump down operation forced cooling operation To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal recover refrigerant by doing the forced cooling operat...

Отзывы: