Fujitsu Inverter Halcyon ASU24CL Скачать руководство пользователя страница 9

OUTDOOR UNIT

1. Check if the piping connections are secure.

2. Check that the stems of 2-way valve and 3-way valve are closed

fully.

3. Connect the gauge manifold charge hose to the charging port

of the 3-way valve (side with the projection for pushing in the
valve core).

4. Open the low pressure side valve of the gauge manifold fully.

5. Operate the vacuum pump and start pump down.

6. Slowly loosen the flare nut of the 3-way valve and check if air

enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)

OUTDOOR UNIT INSTALLATION

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in
the outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and
do not operate it during the following work.

Set the unit on a strong stand, such as one made of concrete blocks to
minimize shock and vibration.

Do not set the unit directly on the ground because it will cause trouble.

Connector cover removal

Remove the tapping screws.

Installing the connector cover

(1) After inserting the two front hooks, then insert the rear hook.
(2) Tighten the tapping screws.

7. Pump down the system for at least 15 minutes, then check if the

compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).

8. At the end of pump down, close the low pressure side gauge of

the gauge manifold fully and stop the vacuum pump.

9. Slowly loosen the valve stem of the 3-way valve. When the

compound pressure gauge reading reaches 0.1-0.2 MPa,
retighten the valve stem and disconnect the charge hose from
the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
charge hose is disconnected, it may be difficult to disconnect
the charge hose.)

 10. Fully open the valve stems of the 2-way valve and 3-way valve

using a hexagon wrench. (After the valve stem begins to turn,
turn it with a torque of less than 2.14 ft•lbs (30 kgf•cm) until it
stops turning.)

 11.  Firmly tighten the 2-way valve and 3-way valve blank cap and

the charging port cap.

Tightening torque

Blank cap (2-way valve) 14.75 to 18.44 ft•lbs (200 to 250 kgf•cm)

Blank cap (3-way valve) 22.12 to 25.81 ft•lbs (300 to 350 kgf•cm)

Charging port cap

7.37 to 8.85 ft•lbs (100 to 120 kgf•cm)

LO

HI

Flare nut

3-way valve

-0.1 MPa
(-76 cmHg
-1 bar)

High
pressure
side valve
(closed)

Low pressure
side valve

Blank cap

Charge
hose

Vacuum pump

2-way valve

Valve stem

Charge hose

Charging port cap

Charging port

Gauge manifold

Compound pressure gauge

Pressure gauge

CAUTION

(1) Refrigerant must not be discharged into atmos-

phere.

(2) After connecting the piping , check the joints for

gas leakage with gas leak detector.

Tapping screw

Rear hooks

Connector cover

Front hooks

WARNING

(1) Install the unit where it will not be tilted by more

than 5°.

(2) When installing the outdoor unit where it may

exposed to strong wind, fasten it securely.

Содержание Inverter Halcyon ASU24CL

Страница 1: ...ng tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceilin...

Страница 2: ...rigerant cycle If air or other gas enters the refrigerant cycle the pressure inside the cycle will rise to an abnormally high value and cause breakage injury etc WARNING CAUTION When installing pipes shorter than 10 ft 3m sound of the outdoor unit will be transferred to the indoor unit which will cause large operating sound or some abnormal sound Special tools for R410A Contents of change Pressure...

Страница 3: ...eration lubricant E Clamps or saddles to secure refrigerant piping 3 OPERATING RANGE CAUTION 1 When adding refrigerant add the refrigerant from the charging port at the completion of work 2 The maximum length of the piping is 99 ft 30 m If the units are further apart than this cor rect operation can not be guaranteed Name and Shape Q ty Name and Shape Q ty Wall hook bracket Remote control unit Bat...

Страница 4: ...CAUTION 1 Do not install where there is the danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the unit 4 Install the indoor unit on the wall where the height from the floors more than 240 cm INDOOR UNIT Indoor unit piping direction The piping can be connected in the 7 dire...

Страница 5: ...all the wall hook bracket horizontally and perpen dicularly FORMING THE DRAIN HOSE AND PIPE Rear piping Right piping Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Install the piping so that the drain hose is at the bottom Wrap the pipes of the indoor unit that are visible from the outside with decorative tap...

Страница 6: ...G PIPES 1 When bending the pipe be careful not to crush it 2 To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 6 150 mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place Tighten with two wrenches Torque wrench Wrench fixed Flare nut Indoor unit pipe Connection pi...

Страница 7: ... tighten securely with the terminal screw using a screwdriver B For strand wiring 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 3 8 10 mm to expose the strand wiring 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using a round terminal fastener or pliers securely clamp a round terminal to each stripped wire end 4 Position...

Страница 8: ...nect inter unit wire harness to the terminal correctly please refer to the figure to adjust the length of the part of Inter unit Wire harness ahead from conduit holder 7 1 2 190mm 1 25mm 1 25mm 7 175mm 1 1 14AWG EARTH WIRE CONDUIT HOLDER CONDUIT CONNECTOR ...

Страница 9: ...8 At the end of pump down close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump 9 Slowly loosen the valve stem of the 3 way valve When the compound pressure gauge reading reaches 0 1 0 2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnected...

Страница 10: ... be sure all wiring is tightly connected Connect wires to the matching numbers of ter minals NOTE Connector trade size for this unit is 1 2 12 7 mm The connector can be bought at a hardware store Refer to How to connect wir ing to the terminals for instructions on connecting depending on the wire type you are using The fuse located in the outdoor unit provides power supply pro tection and may blow...

Страница 11: ...intake grille is removed THE INTAKE GRILLE INSTALLATION 1 The fixing axle of the intake grille is installed on the Panel 2 Lay down the intake grille THE FRONT PANEL REMOVAL 1 Remove intake grille Reference the intake grille removal 2 Remove six screws 3 The thumb is hung on the lower part as shown in the figure and it pulls to the front pushing mark and bottom hooks two position is removed from w...

Страница 12: ... the power check if the voltage is within the 208 V 10 to 230 V 10 range 3 Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner 4 Use a circuit breaker and receptacle matched to the capacity of the air conditioner 5 Do not extend the power cord 6 Perform wiring work in accordance with stand ards so that the air conditioner can be operated...

Страница 13: ...f 3 way valve when the reading on the compound pressure gage becomes 0 05 0 MPa 0 5 0 kg cm2 5 Stop the operation Press the START STOP button of the remote control unit to stop the operation Press the MANUAL AUTO button when stopping the operation from indoor unit side It is not necessary to press on keeping for more than 10 seconds CAUTION Install heat insulation around both the gas and liquid pi...

Страница 14: ... Insure the length of wire is not over the recommended maximum length Before setting up the wired remote control unit please confirm whether air conditioner can receive the signal ONT PANEL CONTROL BOX COVER AND DISPLAY CASE REMOVAL r to FRONT PANEL REMOVAL AND INSTALLATION to remove the front panel ove screws then remove the control box cover ove the display case and connector NNECTING TO CONTROL...

Отзывы: