PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation
or forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the
forced cooling operation.)

(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening the

low-pressure valve slightly.

(2) Close the valve stem of 2 way valve completely.
(3) Start the cooling operation or following forced cooling operation.

When using the remote control unit
Press the TEST RUN button after starting the cooling operation by the remote control unit.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4) Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm

2

).

(5) Stop the operation.

• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side.
  (It is not necessary to press on keeping for more than 10 seconds.)

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above  248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insula-
tion around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the
expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 68 °F).

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.

Содержание Inverter Halcyon ASU24CL

Страница 1: ...ng tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceilin...

Страница 2: ...rigerant cycle If air or other gas enters the refrigerant cycle the pressure inside the cycle will rise to an abnormally high value and cause breakage injury etc WARNING CAUTION When installing pipes shorter than 10 ft 3m sound of the outdoor unit will be transferred to the indoor unit which will cause large operating sound or some abnormal sound Special tools for R410A Contents of change Pressure...

Страница 3: ...eration lubricant E Clamps or saddles to secure refrigerant piping 3 OPERATING RANGE CAUTION 1 When adding refrigerant add the refrigerant from the charging port at the completion of work 2 The maximum length of the piping is 99 ft 30 m If the units are further apart than this cor rect operation can not be guaranteed Name and Shape Q ty Name and Shape Q ty Wall hook bracket Remote control unit Bat...

Страница 4: ...CAUTION 1 Do not install where there is the danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the unit 4 Install the indoor unit on the wall where the height from the floors more than 240 cm INDOOR UNIT Indoor unit piping direction The piping can be connected in the 7 dire...

Страница 5: ...all the wall hook bracket horizontally and perpen dicularly FORMING THE DRAIN HOSE AND PIPE Rear piping Right piping Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Install the piping so that the drain hose is at the bottom Wrap the pipes of the indoor unit that are visible from the outside with decorative tap...

Страница 6: ...G PIPES 1 When bending the pipe be careful not to crush it 2 To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 6 150 mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place Tighten with two wrenches Torque wrench Wrench fixed Flare nut Indoor unit pipe Connection pi...

Страница 7: ... tighten securely with the terminal screw using a screwdriver B For strand wiring 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 3 8 10 mm to expose the strand wiring 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using a round terminal fastener or pliers securely clamp a round terminal to each stripped wire end 4 Position...

Страница 8: ...nect inter unit wire harness to the terminal correctly please refer to the figure to adjust the length of the part of Inter unit Wire harness ahead from conduit holder 7 1 2 190mm 1 25mm 1 25mm 7 175mm 1 1 14AWG EARTH WIRE CONDUIT HOLDER CONDUIT CONNECTOR ...

Страница 9: ...8 At the end of pump down close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump 9 Slowly loosen the valve stem of the 3 way valve When the compound pressure gauge reading reaches 0 1 0 2 MPa retighten the valve stem and disconnect the charge hose from the 3 way valve charging port If the stem of the 3 way valve is opened fully before the charge hose is disconnected...

Страница 10: ... be sure all wiring is tightly connected Connect wires to the matching numbers of ter minals NOTE Connector trade size for this unit is 1 2 12 7 mm The connector can be bought at a hardware store Refer to How to connect wir ing to the terminals for instructions on connecting depending on the wire type you are using The fuse located in the outdoor unit provides power supply pro tection and may blow...

Страница 11: ...intake grille is removed THE INTAKE GRILLE INSTALLATION 1 The fixing axle of the intake grille is installed on the Panel 2 Lay down the intake grille THE FRONT PANEL REMOVAL 1 Remove intake grille Reference the intake grille removal 2 Remove six screws 3 The thumb is hung on the lower part as shown in the figure and it pulls to the front pushing mark and bottom hooks two position is removed from w...

Страница 12: ... the power check if the voltage is within the 208 V 10 to 230 V 10 range 3 Always use a special branch circuit and install a special receptacle to supply power to the room air conditioner 4 Use a circuit breaker and receptacle matched to the capacity of the air conditioner 5 Do not extend the power cord 6 Perform wiring work in accordance with stand ards so that the air conditioner can be operated...

Страница 13: ...f 3 way valve when the reading on the compound pressure gage becomes 0 05 0 MPa 0 5 0 kg cm2 5 Stop the operation Press the START STOP button of the remote control unit to stop the operation Press the MANUAL AUTO button when stopping the operation from indoor unit side It is not necessary to press on keeping for more than 10 seconds CAUTION Install heat insulation around both the gas and liquid pi...

Страница 14: ... Insure the length of wire is not over the recommended maximum length Before setting up the wired remote control unit please confirm whether air conditioner can receive the signal ONT PANEL CONTROL BOX COVER AND DISPLAY CASE REMOVAL r to FRONT PANEL REMOVAL AND INSTALLATION to remove the front panel ove screws then remove the control box cover ove the display case and connector NNECTING TO CONTROL...

Отзывы: