Connection cable preparation

6

1 21 21 

 

Earth (ground) wire

Power supply cable 

or connection cable

Keep the earth (ground) wire longer than the other wires.

• Use a 4-core wire cable.

30 mm

40 mm or more

How to connect wiring to the terminals. 

 

(For strand wiring)

Use crimp-type terminals with insulating sleeves as shown in the figure below to 

(1) 

connect to the terminal block.

Securely crimp the crimp-type terminals to the wires using an appropriate tool so that 

(

2

the wires do not come loose.

  Strip 10 mm

Crimp-type

terminal

Sleeve

Use the specified wires, connect them securely, and fasten them so that there is no 

(3) 

stress placed on the terminals.

Use an appropriate screwdriver to tighten the terminal screws. 

(4) 

Do not use a screwdriver that is too small, otherwise, the screw heads may be 

damaged and prevent the screws from being properly tightened.

Do not tighten the terminal screws too much, otherwise, the screws may break.

(5) 

See the table below for the terminal screw tightening torques. 

(

6

 

WARNING

Use crimp-type terminals and tighten the terminal screws to the specified torques, 

otherwise, abnormal overheating may be produced and possibly cause serious 

damage inside the unit.

Tightening torque [N·m (kgf·cm)]

M4 screw

1.2 to 1.8 (12 to 18)

M5 screw

2.0 to 3.0 (20 to 30)

Screw with

special washer

Crimp-type

terminal

Terminal blocks

Wire

Wire

Screw with

special

washer

Crimp-type

terminal

Connection wiring

6

1 21 21 

 

CAUTION

Use care not to mistake the power supply cable and connection wires when installing.
Install so that the wires for the remote controller will not come in contact with other 

connection wires.

(1)  Remove the control box cover and install each connection wire.

 

Control box

cover

Loosen the screws.

(4 locations)

 

Control line

Connection cable

Power line

Outdoor unit

Earth (ground)

Black

White

Red

Remote

controller

*Earth 

 (ground)

 wire

*Ground the remote controller if it has a earth (ground) wire.

(2) 

After wiring is complete, secure the remote controller cable, connection cable, and 

power supply cable with the cable clamps.

 

Connection cable

(to outdoor unit)

Remote controller

cable

Cable tie (Medium)

(Accessory)

Control box

(3)  Seal the cable outlet or other gaps with putty to prevent dew condensation or insect 

from entering the electric control box.

(4)  Install the control box cover.

 

CAUTION

Do not bundle the remote controller cable, or wire the remote controller cable in 

parallel, with the indoor unit connection wire (to the outdoor unit) and the power supply 

cable. It may cause erroneous operation.

REMOTE CONTROLLER SETTING

7

 CAUTION

When using the temperature sensor of remote controller, 

be sure to meet the following location requirements for 

installation of the remote controller in order to detect the 

room temperature correctly. If the remote controller is 

installed in an improper location, troubles such as “the 

room does not become cool or warm” may occur even 

though there is no problem in the air conditioner.

Temperature sensor

A location where the average room temperature can be detected.

 

A location that is not directly exposed to the air blown out of the indoor unit.

 

A location that is not exposed to direct sunlight.

 

A location that is not affected by any heat source.

 

Do not touch the remote controller PC board and PC board parts directly with your hands.
Install the remote controller wires so as not to be direct touched with your hand.
Do not wire the remote controller cable and the bus wire together with or parallel to 

the connection cables, transmission cables, and power supply cables of the indoor 

and outdoor units. It may cause erroneous operation.
When installing the bus wire near a source of electromagnetic waves, use shielded wire.
Do not set the DIP switches, either on the air conditioner or the remote controller, in 

any way other than indicated in this manual or the manual that is supplied with the air 

conditioner. Doing so may result in an accident.

9380441038_IM.indb   7

28/1/2556   13:44:40

Содержание INDOOR UNIT Duct Type

Страница 1: ...os Solo para personal autorizado MANUALE D INSTALLAZIONE UNITÀ INTERNA Tipo di condotto Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύποςαγωγού Гια εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO UNIDADE INTERIOR Tipo conduta Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ Канального типа Для yпoлнoмoчeнного персонала KURULU...

Страница 2: ... person responsible for their safety Children should be supervised to ensure that they do not play with the appliance ABOUT THE UNIT 222 Precautions for using R410A refrigerant 222222 WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and ...

Страница 3: ...s to fall or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasolin...

Страница 4: ...n of the indoor unit If maintenance work is to be done from the top keep the space of the more than 450 mm between the indoor unit and ceiling 800 or more 500 or more 30 or more 500 or more 200 or more Service access size of 3 2 1 Drain pan Unit mm Service access size of 3 2 2 Installation the unit 333333 WARNING Install the air conditioner in a location which can withstand a load of at least 5 ti...

Страница 5: ...than those indicated in the table even if they are available on the market Pipe outside diameter mm in Thickness mm 6 35 1 4 0 8 9 52 3 8 0 8 12 70 1 2 0 8 15 88 5 8 1 0 19 05 3 4 1 2 Pipe requirement 444444 CAUTION Refer to the Installation Manual of the outdoor unit for description of the length of connecting pipe or for difference of its elevation Diameter mm in Liquid 9 52 3 8 Gas 15 88 5 8 Us...

Страница 6: ...y side Flare nut Holding Wrench Flare nut mm in Tightening torque N m kgf cm 6 35 1 4 dia 16 to 18 160 to 180 9 52 3 8 dia 32 to 42 320 to 420 12 70 1 2 dia 49 to 61 490 to 610 15 88 5 8 dia 63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1 100 Installing heat insulation 444444 Install the heat insulation material after performing a refrigerant leak check see the Installation Manual for the out...

Страница 7: ...led electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Install a ground leakage breaker In addition install the ground leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire co...

Страница 8: ...und the remote controller if it has a earth ground wire 2 After wiring is complete secure the remote controller cable connection cable and power supply cable with the cable clamps Connection cable to outdoor unit Remote controller cable Cable tie Medium Accessory Control box 3 Seal the cable outlet or other gaps with putty to prevent dew condensation or insect from entering the electric control bo...

Страница 9: ...ing Refer to 11 3 Dual remote controllers 3 Cannot be used Do not change 4 Cannot be used Do not change 5 Cannot be used Do not change 6 Invalidity Validity Memory backup setting Set to ON to use batteries for the memory backup If batteries are not used all of the settings stored in memory will be deleted if there is a power failure Factory setting FUNCTION SETTING 888 CAUTION Confirm whether the ...

Страница 10: ... Setting Description Function Number Setting Value Standard No correction 30 00 Low control 1 0 C 01 Slightly lower control 0 5 C 02 Slightly warmer control 0 5 C 03 Warmer control 1 0 C 04 Setting the Heater Room Temperature Correction Depending on the installed environment the room temperature sensor may require a correction The settings may be selected as shown in the table below The unit is fa...

Страница 11: ...e control unit normal Is the drain normal Is there any abnormal noise and vibration during operation Do not operate the air conditioner in the running state for a long time Operation method For the operation method refer to the Operating Manual Stop the air conditioner operation Press the MODE button and the FAN button simultaneously for 2 seconds or more to start the test run Test run display Pre...

Страница 12: ...oller Indoor unit Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit R C address DIP switch setting Transmission cable Power supply cable Remote controller cable Bus wire Power supply cable Primary Secondary Function number 51 Refrigerant circuit address Function number 02 Simultaneous triple Make sure that the indoor unit with the R C address ...

Страница 13: ...ng for room temperature control setting When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 48 Room temperature setting to 01 Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Cooler air temperature correction to 01 Set Function Numb...

Страница 14: ... 1 Indoor unit Indoor unit fan motor1 error 5 3 Indoor unit Drainage error 5 7 Damper error 5 9 Indoor unit Indoor unit fan motor2 error 5 15 Indoor unit Indoor unit error 6 2 Outdoor unit Outdoor unit model information error 6 3 Outdoor unit Inverter error 6 4 Active filter error PFC circuit error 6 5 Outdoor unit I P M error 6 10 Display PCB microcomputers communication error 7 1 Outdoor unit Di...

Отзывы: