INSTALL THE DRAIN PIPE

 

Use general hard polyvinyl chloride pipe (VP25) and connect it with adhesive (polyvinyl 

chloride) so that there is no leakage. Do not perform air bleeding.

Main drain pipe 

(1) 

Provide one trap on the 

main drain pipe near the 

indoor unit.

Unit

Drain pipe

Trap

H

1

=100 mm (Approx.)

H

2

 pt=50~100 mm

H

2

H

1

Safety drain 

(

2

There is no need to provide a trap 

for the safety drain pipe. 

If the safety drain pipe is 

connected to the main drain pipe, 

make the connection below the 

trap on the main drain pipe

Unit

Drain pipe

Main

Safety

Make sure that drain pipe is installed 

 

without rises.

Do not perform air bleeding.

 

Rise

Air bleeding

Rise

PROHIBITED

 

CAUTION

Make sure the drain water is properly drained.

ELECTRICAL WIRING

6

 

WARNING

Electrical work must be performed in accordance with this Manual by a person 

certified under the national or regional regulations. Be sure to use a dedicated circuit 

for the unit.  

An insufficient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or fire.

Before starting work, check that power is not being supplied to the indoor unit and 

outdoor unit.

Use the included connection cables and power cables or ones specified by the 

manufacturer. Improper connections, insufficient insulation, or exceeding the allowable 

current can cause electric shock or fire.

For wiring, use the prescribed type of cables, connect them securely, making sure 

that there are no external forces of the cables applied to the terminal connections. 

Improperly connected or secured cables can cause serious accidents such as 

overheating the terminals, electric shock, or fire.
Do not modify the power cables, use extension cables, or use any branches in the 

wiring. Improper connections, insufficient insulation, or exceeding the allowable 

current can cause electric shock or fire.

Match the terminal board numbers and connection cable colors with those of the 

outdoor unit. Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the 

cables with wiring holders. Improper connections, either in the wiring or at the ends of 

the wiring, can cause a malfunction, electric shock, or fire.

Always fasten the outside covering of the connection cable with the cable clamp. (If 

the insulator is chafed, electric leakage may occur.)

Securely install the electrical box cover on the unit. An improperly installed electrical 

box cover can cause serious accidents such as electric shock or fire through exposure 

to dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 

could result.
Install a ground leakage breaker. In addition, install the ground leakage breaker so 

that the entire AC main power supply is cut off at the same time. Otherwise, electric 

shock or fire could result.

Install a ground leakage breaker.  

If a ground leakage breaker is not installed, it may cause electric shock or fire.

Always connect the earth (ground) cable. 

Improper earthing (grounding) work can cause electric shocks.
Install the remote control cables so as not to be direct touched with your hand.

 

WARNING

Perform wiring work in accordance with standards so that the air conditioner can be 

operated safely and positively.

Connect the connection cable firmly to the terminal board. Imperfect installation may 

cause a fire.

 

CAUTION

Ground the unit.

Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 

telephone earth (ground) cable. 

Improper earthing (grounding) may cause electric shock.

Do not connect power supply cables to the transmission or remote control terminals, 

as this will damage the product.
Never bundle the power supply cable and transmission cable together. Bundling these 

cables together will cause miss operation.
When handling PCB, static electricity charged in the body may cause malfunction of 

the PCB. Follow the cautions below:

Establish a ground for the indoor and outdoor units and peripheral devices.

 

Cut power (breaker) off.

 

Touch metal part of the indoor and outdoor units for more than 10 seconds to 

 

discharge static electricity charged in the body.

Do not touch terminals of parts and patterns implemented on PCB.

 

Electrical requirement

6

1

Cable

Cable size (mm

2

)

Type

Remarks

Connection cable

1.5 (MIN.)

Type 60245 IEC57

Earth (Ground), 

1φ230V

Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage 

drop is 2% or more.

Perform all electrical work according to the standard.

 

Install circuit breakers, which have the terminal spacing of more than 3 mm, in a place of 

 

near the indoor unit and outdoor unit.

 

CAUTION

Be sure to execute the electrical work according to the Laws of each country and the 

Installation Instructions. In addition, be sure to set as exclusive line and use the rated 

voltage and circuit breaker.

 Wiring method

6

1 21 

Connection diagrams

6

1 21 

1

Connection cable (to outdoor unit)

 

Control line

Power line

Indoor unit

side

Wired remote controller cable

 

*

Indoor unit

side

White

Red

Black

*Gound the remote controller if it has a earth (ground) wire.

9380441038_IM.indb   6

28/1/2556   13:44:39

Содержание INDOOR UNIT Duct Type

Страница 1: ...os Solo para personal autorizado MANUALE D INSTALLAZIONE UNITÀ INTERNA Tipo di condotto Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύποςαγωγού Гια εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO UNIDADE INTERIOR Tipo conduta Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ Канального типа Для yпoлнoмoчeнного персонала KURULU...

Страница 2: ... person responsible for their safety Children should be supervised to ensure that they do not play with the appliance ABOUT THE UNIT 222 Precautions for using R410A refrigerant 222222 WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and ...

Страница 3: ...s to fall or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasolin...

Страница 4: ...n of the indoor unit If maintenance work is to be done from the top keep the space of the more than 450 mm between the indoor unit and ceiling 800 or more 500 or more 30 or more 500 or more 200 or more Service access size of 3 2 1 Drain pan Unit mm Service access size of 3 2 2 Installation the unit 333333 WARNING Install the air conditioner in a location which can withstand a load of at least 5 ti...

Страница 5: ...than those indicated in the table even if they are available on the market Pipe outside diameter mm in Thickness mm 6 35 1 4 0 8 9 52 3 8 0 8 12 70 1 2 0 8 15 88 5 8 1 0 19 05 3 4 1 2 Pipe requirement 444444 CAUTION Refer to the Installation Manual of the outdoor unit for description of the length of connecting pipe or for difference of its elevation Diameter mm in Liquid 9 52 3 8 Gas 15 88 5 8 Us...

Страница 6: ...y side Flare nut Holding Wrench Flare nut mm in Tightening torque N m kgf cm 6 35 1 4 dia 16 to 18 160 to 180 9 52 3 8 dia 32 to 42 320 to 420 12 70 1 2 dia 49 to 61 490 to 610 15 88 5 8 dia 63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1 100 Installing heat insulation 444444 Install the heat insulation material after performing a refrigerant leak check see the Installation Manual for the out...

Страница 7: ...led electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Install a ground leakage breaker In addition install the ground leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire co...

Страница 8: ...und the remote controller if it has a earth ground wire 2 After wiring is complete secure the remote controller cable connection cable and power supply cable with the cable clamps Connection cable to outdoor unit Remote controller cable Cable tie Medium Accessory Control box 3 Seal the cable outlet or other gaps with putty to prevent dew condensation or insect from entering the electric control bo...

Страница 9: ...ing Refer to 11 3 Dual remote controllers 3 Cannot be used Do not change 4 Cannot be used Do not change 5 Cannot be used Do not change 6 Invalidity Validity Memory backup setting Set to ON to use batteries for the memory backup If batteries are not used all of the settings stored in memory will be deleted if there is a power failure Factory setting FUNCTION SETTING 888 CAUTION Confirm whether the ...

Страница 10: ... Setting Description Function Number Setting Value Standard No correction 30 00 Low control 1 0 C 01 Slightly lower control 0 5 C 02 Slightly warmer control 0 5 C 03 Warmer control 1 0 C 04 Setting the Heater Room Temperature Correction Depending on the installed environment the room temperature sensor may require a correction The settings may be selected as shown in the table below The unit is fa...

Страница 11: ...e control unit normal Is the drain normal Is there any abnormal noise and vibration during operation Do not operate the air conditioner in the running state for a long time Operation method For the operation method refer to the Operating Manual Stop the air conditioner operation Press the MODE button and the FAN button simultaneously for 2 seconds or more to start the test run Test run display Pre...

Страница 12: ...oller Indoor unit Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit R C address DIP switch setting Transmission cable Power supply cable Remote controller cable Bus wire Power supply cable Primary Secondary Function number 51 Refrigerant circuit address Function number 02 Simultaneous triple Make sure that the indoor unit with the R C address ...

Страница 13: ...ng for room temperature control setting When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 48 Room temperature setting to 01 Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Cooler air temperature correction to 01 Set Function Numb...

Страница 14: ... 1 Indoor unit Indoor unit fan motor1 error 5 3 Indoor unit Drainage error 5 7 Damper error 5 9 Indoor unit Indoor unit fan motor2 error 5 15 Indoor unit Indoor unit error 6 2 Outdoor unit Outdoor unit model information error 6 3 Outdoor unit Inverter error 6 4 Active filter error PFC circuit error 6 5 Outdoor unit I P M error 6 10 Display PCB microcomputers communication error 7 1 Outdoor unit Di...

Отзывы: