Fujitsu INDOOR UNIT Duct Type Скачать руководство пользователя страница 10

En-9

Press the set temperature buttons (

(3) 

) (

) to select the setting value. 

The display flashes as shown to the right during setting value selection.

Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a 

(4) 

few seconds until the setting value stops flashing.

 

If the setting value display changes or if “- -” is displayed when the flashing stops, 

the setting value has not been set correctly. (An invalid setting value may have been 

selected for the indoor unit.)

SU MO TU WE TH FR SA

Setting value

Repeat steps 2 to 5 to perform additional settings. Press the set temperature buttons 

(5) 

(

) (

) and fan control button simultaneously again for more than 5 seconds 

to cancel the function setting mode. In addition, the function setting mode will be 

automatically canceled after 1 minute if no operation is performed.

After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.

(

6

 

CAUTION

After turning off the power, wait 30 seconds or more before turning on it again. The 

FUNCTION SETTING doesn’t become effective if it doesn’t do so.

Function setting

8

1 21 

Filter Sign

The indoor unit has a sign to inform the user that it is time to clean the filter. Select the 

 

time setting for the filter sign display interval in the table below according to the amount 

of dust or debris in the room. If you do not wish the filter sign to be displayed, select the 

setting value for “No indication”. 

(The unit is factory-set to “03”.)

Setting Description

Function

Number

Setting 

Value

Standard (2500 hours)

11

00

Long interval (5000 hours)

01

Short interval (1250 hours)

02

No indication

03

Setting the Static Pressure

Select appropriate static pressure according to the installation conditions.  

 

(The unit is factory-set to “00”.)

Refer to the technical manual for details or follow the instructions of the duct designer.

 

Setting Description

Function

Number

Setting 

Value

Normal (60Pa)

21

00

static pressure 1 (100Pa)

02

static pressure 2 (150Pa)

03

static pressure 3 (200Pa)

04

static pressure 4 (250Pa)

05

Setting the Cooler Room Temperature Correction

Depending on the installed environment, the room temperature sensor may require a 

 

correction. The settings may be selected as shown in the table below.

(The unit is factory-set to “00”.)

Setting Description

Function

Number

Setting 

Value

Standard (No correction)

30

00

Low control (-1.0°C)

01

Slightly lower control (-0.5°C)

02

Slightly warmer control (+0.5°C)

03

Warmer control (+1.0°C)

04

Setting the Heater Room Temperature Correction

Depending on the installed environment, the room temperature sensor may require a 

 

correction. The settings may be selected as shown in the table below. 

(The unit is factory-set to “00”.)

Setting Description

Function

Number

Setting 

Value

Standard (No correction)

31

00

Low control (-1.0°C)

01

Slightly lower control (-0.5°C)

02

Slightly warmer control (+0.5°C)

03

Warmer control (+1.0°C)

04

Auto Restart

 

(The setting value is factory-set to “00”.)

Setting Description

Function

Number

Setting 

Value

Yes

40

00

No

01

Indoor Room Temperature Sensor Switching Function

(Wired remote controller only)

(The setting value is factory-set to “00”.)

Setting Description

Function

Number

Setting 

Value

Only the sensor of the indoor unit is used

42

00

The sensor of the wired remote controller is used

01

Cool Air Prevention

This setting is used to set the fan speed when the compressor stops once the room 

 

temperature has reached the set temperature during heating operation. 

(The unit is factory-set to “00”.)

Setting Description

Function

Number

Setting 

Value

Super low

43

00

Follow the setting on the remote controller  

(corresponding to ventilation)

01

External input control

“Operation/Stop” mode or “Forced stop” mode can be selected.

 

(The unit is factory-set to “00”.)

Setting Description

Function

Number

Setting 

Value

Operation/Stop mode

46

00

(Setting forbidden)

01

Forced stop mode

02

Room Temperature Control Switching

This setting is used to set the room temperature control method when the wired remote 

 

controller is selected by the Indoor Room Temperature Sensor Switching Function. 

(The unit is factory-set to “00”.)

Setting Description

Function

Number

Setting 

Value

Control by the sensors of both the indoor unit 

and the wired remote controller.

48

00

Control only by the sensor of the wired remote 

controller.

01

Setting record

Record any changes to the settings in the following table.

Jumper wire

Setting Value

Filter Sign

Static Pressure

Cooler Room Temperature Correction

Heater Room Temperature Correction

Auto Restart

Room Temperature Sensor Switching

Cool Air Prevention

External input control

Room Temperature Control Switching

After completing the FUNCTION SETTING, be sure to turn off the power and turn it on 

 

again. 

9380441038_IM.indb   9

28/1/2556   13:44:42

Содержание INDOOR UNIT Duct Type

Страница 1: ...os Solo para personal autorizado MANUALE D INSTALLAZIONE UNITÀ INTERNA Tipo di condotto Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύποςαγωγού Гια εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO UNIDADE INTERIOR Tipo conduta Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ Канального типа Для yпoлнoмoчeнного персонала KURULU...

Страница 2: ... person responsible for their safety Children should be supervised to ensure that they do not play with the appliance ABOUT THE UNIT 222 Precautions for using R410A refrigerant 222222 WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and ...

Страница 3: ...s to fall or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasolin...

Страница 4: ...n of the indoor unit If maintenance work is to be done from the top keep the space of the more than 450 mm between the indoor unit and ceiling 800 or more 500 or more 30 or more 500 or more 200 or more Service access size of 3 2 1 Drain pan Unit mm Service access size of 3 2 2 Installation the unit 333333 WARNING Install the air conditioner in a location which can withstand a load of at least 5 ti...

Страница 5: ...than those indicated in the table even if they are available on the market Pipe outside diameter mm in Thickness mm 6 35 1 4 0 8 9 52 3 8 0 8 12 70 1 2 0 8 15 88 5 8 1 0 19 05 3 4 1 2 Pipe requirement 444444 CAUTION Refer to the Installation Manual of the outdoor unit for description of the length of connecting pipe or for difference of its elevation Diameter mm in Liquid 9 52 3 8 Gas 15 88 5 8 Us...

Страница 6: ...y side Flare nut Holding Wrench Flare nut mm in Tightening torque N m kgf cm 6 35 1 4 dia 16 to 18 160 to 180 9 52 3 8 dia 32 to 42 320 to 420 12 70 1 2 dia 49 to 61 490 to 610 15 88 5 8 dia 63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1 100 Installing heat insulation 444444 Install the heat insulation material after performing a refrigerant leak check see the Installation Manual for the out...

Страница 7: ...led electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Install a ground leakage breaker In addition install the ground leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire co...

Страница 8: ...und the remote controller if it has a earth ground wire 2 After wiring is complete secure the remote controller cable connection cable and power supply cable with the cable clamps Connection cable to outdoor unit Remote controller cable Cable tie Medium Accessory Control box 3 Seal the cable outlet or other gaps with putty to prevent dew condensation or insect from entering the electric control bo...

Страница 9: ...ing Refer to 11 3 Dual remote controllers 3 Cannot be used Do not change 4 Cannot be used Do not change 5 Cannot be used Do not change 6 Invalidity Validity Memory backup setting Set to ON to use batteries for the memory backup If batteries are not used all of the settings stored in memory will be deleted if there is a power failure Factory setting FUNCTION SETTING 888 CAUTION Confirm whether the ...

Страница 10: ... Setting Description Function Number Setting Value Standard No correction 30 00 Low control 1 0 C 01 Slightly lower control 0 5 C 02 Slightly warmer control 0 5 C 03 Warmer control 1 0 C 04 Setting the Heater Room Temperature Correction Depending on the installed environment the room temperature sensor may require a correction The settings may be selected as shown in the table below The unit is fa...

Страница 11: ...e control unit normal Is the drain normal Is there any abnormal noise and vibration during operation Do not operate the air conditioner in the running state for a long time Operation method For the operation method refer to the Operating Manual Stop the air conditioner operation Press the MODE button and the FAN button simultaneously for 2 seconds or more to start the test run Test run display Pre...

Страница 12: ...oller Indoor unit Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit R C address DIP switch setting Transmission cable Power supply cable Remote controller cable Bus wire Power supply cable Primary Secondary Function number 51 Refrigerant circuit address Function number 02 Simultaneous triple Make sure that the indoor unit with the R C address ...

Страница 13: ...ng for room temperature control setting When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 48 Room temperature setting to 01 Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indicated below Set Function Number 30 Cooler air temperature correction to 01 Set Function Numb...

Страница 14: ... 1 Indoor unit Indoor unit fan motor1 error 5 3 Indoor unit Drainage error 5 7 Damper error 5 9 Indoor unit Indoor unit fan motor2 error 5 15 Indoor unit Indoor unit error 6 2 Outdoor unit Outdoor unit model information error 6 3 Outdoor unit Inverter error 6 4 Active filter error PFC circuit error 6 5 Outdoor unit I P M error 6 10 Display PCB microcomputers communication error 7 1 Outdoor unit Di...

Отзывы: