En-3

(3)  Leave the space required to service the air conditioner.

(4)  Locate where the air can be distributed evenly throughout the room by the unit.

(5)  Install the unit where connection to the outdoor unit is easy.

(6)  Install the unit where the connection pipe can be easily installed.

(7)  Install the unit where the drain pipe can be easily installed.

(8)  Install the unit where noise and vibration is not ampli

fi

 ed.

(9)  Take servicing, etc., into consideration and leave the spaces. Also install the unit 

where the 

fi

 lter can be removed.

(10)  Providing as much space as possible between the indoor  unit and the ceiling will 

make work much easier.

(11)  If installing in a place where its humidity exceeds 80%, use heat insulation to prevent 

condensation.

3.2. Installation dimension

Provide the space around the unit as shown in the following 

fi

 gure.

Floor

Unit : mm

2500 or more 
(When no 
ceiling)

300 
or more

150 
or more

Maintenance hole dimensions:

It shall be possible to install and remove the control box.

Maintenance hole

Control box

Unit : mm

It shall be possible to install and remove the control box, fan units and 

fi

 lter.

Maintenance hole

Intake panel

Control box

Unit : mm

3.3. Installation the unit

 

WARNING

Install the air conditioner in a location which can withstand a load do at least 5 times the 
weight of the main unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

If the job is done with the panel frame only, there is a risk that the unit will come loose. 

Please take care.

3.3.1. Installing the hangers

 

WARNING

When fastening the hangers, make the bolt positions uniform.

Hanging bolt installation diagram.

(Example)

(Top side)

(Left side)

Unit : mm

The distance of   is adjustable according to the place of the hanging bolts.

(MAX : 550 mm, MIN : 410 mm)

Slide the unit in the arrow direction and fasten it.

Hanging bolt M10 
(Obtained locally)

Special nut A

Washer 
(Obtained locally)

Special nut B

Hanger

Bolt Strength [N·m (kgf·cm)]

9.81 to 14.71 (100 to 150)

 

CAUTION

Fasten the unit securely with special nuts A and B.

3.3.2. Leveling

Base vertical direction leveling on the unit (right and left).

(Left side)

Lever meter

AIR

AIR

Base horizontal direction leveling on top of the unit.

Drain hose

0-5 mm

Give a slight tilt to the side to which the drain hose is connected.

The tilt should be in the range of 0 mm to 5 mm.

9379127035-02_IM.indb   Sec1:3

9379127035-02_IM.indb   Sec1:3

23/01/2013   16:25:41

23/01/2013   16:25:41

Содержание INDOOR UNIT (Duct Type) AIR CONDITIONER

Страница 1: ... Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir PART NO 9379127035 02 AIR...

Страница 2: ... prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended to use a gauge manifold with a high pressure display range 0 1 to 5 3 MPa and a low pressure display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump...

Страница 3: ...portant for the split type air conditioner be cause it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such as at the seaside It will deter...

Страница 4: ... units and filter Maintenance hole Intake panel Control box Unit mm 3 3 Installation the unit WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with the panel frame o...

Страница 5: ... the round flange and square flange when con necting the duct CAUTION Check that duct work does not exceed the range of external static pressure of equipment Make sure to insulate ducts to avoid the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from ...

Страница 6: ...o 42 320 to 420 12 70 1 2 dia 49 to 61 490 to 610 15 88 5 8 dia 63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1 100 Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter mm in Thickness mm 6 35 1 4 0 80 9 52 3 8 0 80 12 70 1 2 0 80 15 88 5 8 1 00 19 05 3 4 1 20 4 2 Pipe requirement CAUTION Refer to the Installation Manual of the outdoor unit for description of the length of connect...

Страница 7: ...nd so there are no rises or traps in the hose Use general hard polyvinyl chloride pipe VP25 outside diameter 38 mm and connect it with adhesive polyvinyl chloride so that there is no leakage When the hose is long install supporters Do not perform air bleeding Always heat insulate the indoor side of the drain hose Outlet air flow Drain hose Trap Arrange the drain hose lower than this portion Rise A...

Страница 8: ...a earth leakage breaker In addition install the earth leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result Always connect the earth cable Improper grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so ...

Страница 9: ...t Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than the other wires Power supply cable or connection cable 20 mm 50mm or more Earth ground wire Use a 4 core wire cable 6 3 Connection of wiring CAUTION Use care not to mistake the power supply cable and connection wires when installing Remove t...

Страница 10: ...en installing the front case connect the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote contro...

Страница 11: ... SET button to confirm the setting Press the TIMER SET button for a few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN ...

Страница 12: ...s remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 8 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operation Stop mode 46 00 Setting forbidden 01 Forced stop mode 02 Setting record Record any changes to the settings in the following table Set...

Страница 13: ...main power 8 4 1 Group control system A number of indoor units can be operated at the same time using a single remote controller 1 Wiring method indoor unit to remote controller 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Indoor unit 1 Bus wire Remote controller cable Remote controller When ground wire is necessary Indoor unit 2 Indoor unit 3 Indoor unit 4 2 DIP switch setting Indoor unit Set the unit number of...

Страница 14: ...nnected the outdoor unit using a transmission cable is primary Connect the remote controller wire to the primary unit Twin type Outdoor unit Indoor unit Indoor unit Remote controller primary secondary DIP switch setting Indoor unit 2 Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set t...

Страница 15: ...controller while the air conditioner is running Point the transmitter section of the wireless remote controller toward the air conditioner and press the TEST RUN button with the tip of a ball point pen etc Transmitter section TEST RUN button To end test operation press the wireless remote controller START STOP button When the air conditioner is run by pressing the TEST RUN button the OPERATION ind...

Страница 16: ...CB model information error 3 5 Manual auto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PC...

Отзывы: