En-2

2.3. Accessories

 WARNING

For installation purposes, be sure to use the parts supplied by the manufacturer or 

other prescribed parts. 

The use of non-prescribed parts can cause serious accidents such as the unit to fall, 

water leakage, electric shock, or 

fi

 re.

The following installation parts are furnished. Use them as required.

Keep the Installation Manual in a safe place and do not discard any other accessories 

until the installation work has been completed.

Do not discard any accessories needed for installation until the installation work has 
been completed.

Name and Shape

Q’ty

Description

Operating manual

1

Installation manual

1

(This book)

Hanger

4

For suspending the indoor unit 

from ceiling

Drain hose insulation

1

Insulates the drain hose and 

vinyl hose

Cable tie (large)

1

For 

fi

 xing the drain hose

Cable tie (small)

1

For remote controller and re-
mote controller cable binding

Cable tie

2

For electrical wiring
(22,24 model)

Wire clamper

1

For electrical wiring
(22,24 model)

Remote controller

1

For air conditioner operation

Remote controller cable
(*1)

1

For connecting the remote 
controller

Screw (M4 × 16)

2

For installing the remote 
controller

Coupler heat 
insulation (large)

1

For indoor side pipe joint (gas)

Coupler heat 
insulation (small)

1

For indoor side pipe joint 
(liquid)

Special nut A
(large 

fl

 ange) 

4

For suspending the indoor unit 
from ceiling

Special nut B
(small 

fl

 ange) 

4

For suspending the indoor unit 
from ceiling

(*1) Not supplied for ART series

2.4. Optional parts

Parts name

Model No.

Application

Wired remote controller

UTY-RNN*M

For air conditioner operation

Wired remote controller

UTY-RVN*M

For air conditioner operation

Simple remote controller

UTY-RSN*M

For air conditioner operation

Remote sensor unit

UTY-XSZX

Room temperature sensor

External connect kit

UTD-ECS5A

For control input/output port

Square 

fl

 ange

UTD-SF045T

Round 

fl

 ange

UTD-RF204

Long-life 

fi

 lter

UTD-LF25NA

Drain pump unit

UTZ-PX1NBA

3. INSTALLATION WORK

3.1. Selecting an installation location

Especially, the installation place is very important for the split type air conditioner be-
cause it is very dif

fi

 cult to move from place to place after the 

fi

 rst installation.

 

WARNING

Select installation locations that can properly support the weight of the indoor. Install 

the units securely so that they do not topple or fall.

 

CAUTION

Do not install the unit in the following areas:

•  Area with high salt content, such as at the seaside. 
  It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, 

such as a kitchen. 

  It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
•  Area that generates substances that adversely affect the equipment, such as 

sulfuric gas, chlorine gas, acid, or alkali. 

  It will cause the copper pipes and brazed joints to corrode, which can cause 

refrigerant leakage.

•  Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint thinner or gasoline. 

  If gas leaks and settles around the unit, it can cause a 

fi

 re.

•  Area where animals may urinate on the unit or ammonia may be generated.

Do not use the unit for special purposes, such as storing food, raising animals, growing 
plants, or preserving precision devices or art objects. 
It can degrade the quality of the preserved or stored objects.

Do not install where there is the danger of combustible gas leakage.

Do not install the unit near a source of heat, steam, or 

fl

 ammable gas.

Install the unit where drainage does not cause any trouble.

Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote 

controller cable at least 1 m away from a television or radio receivers. The purpose of 

this is to prevent TV reception interference or radio noise.

(Even if they are installed more than 1 m apart, you could still receive noise under 

some signal conditions.)

Take precautions to prevent the unit from falling.

Decide the mounting position with the customer as follows:

(1)  Install the indoor unit in a location having suf

fi

 cient strength to support the weight of 

the indoor unit.

(2)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

9379127035-02_IM.indb   Sec1:2

9379127035-02_IM.indb   Sec1:2

23/01/2013   16:25:40

23/01/2013   16:25:40

Содержание INDOOR UNIT (Duct Type) AIR CONDITIONER

Страница 1: ... Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir PART NO 9379127035 02 AIR...

Страница 2: ... prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended to use a gauge manifold with a high pressure display range 0 1 to 5 3 MPa and a low pressure display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump...

Страница 3: ...portant for the split type air conditioner be cause it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install the unit in the following areas Area with high salt content such as at the seaside It will deter...

Страница 4: ... units and filter Maintenance hole Intake panel Control box Unit mm 3 3 Installation the unit WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with the panel frame o...

Страница 5: ... the round flange and square flange when con necting the duct CAUTION Check that duct work does not exceed the range of external static pressure of equipment Make sure to insulate ducts to avoid the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from ...

Страница 6: ...o 42 320 to 420 12 70 1 2 dia 49 to 61 490 to 610 15 88 5 8 dia 63 to 75 630 to 750 19 05 3 4 dia 90 to 110 900 to 1 100 Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter mm in Thickness mm 6 35 1 4 0 80 9 52 3 8 0 80 12 70 1 2 0 80 15 88 5 8 1 00 19 05 3 4 1 20 4 2 Pipe requirement CAUTION Refer to the Installation Manual of the outdoor unit for description of the length of connect...

Страница 7: ...nd so there are no rises or traps in the hose Use general hard polyvinyl chloride pipe VP25 outside diameter 38 mm and connect it with adhesive polyvinyl chloride so that there is no leakage When the hose is long install supporters Do not perform air bleeding Always heat insulate the indoor side of the drain hose Outlet air flow Drain hose Trap Arrange the drain hose lower than this portion Rise A...

Страница 8: ...a earth leakage breaker In addition install the earth leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result Always connect the earth cable Improper grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so ...

Страница 9: ...t Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than the other wires Power supply cable or connection cable 20 mm 50mm or more Earth ground wire Use a 4 core wire cable 6 3 Connection of wiring CAUTION Use care not to mistake the power supply cable and connection wires when installing Remove t...

Страница 10: ...en installing the front case connect the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote contro...

Страница 11: ... SET button to confirm the setting Press the TIMER SET button for a few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN ...

Страница 12: ...s remote controllers Factory setting Setting description Function number Setting value A 44 00 B 01 C 02 D 03 8 External input control Operation Stop mode or Forced stop mode can be selected Factory setting Setting description Function number Setting value Operation Stop mode 46 00 Setting forbidden 01 Forced stop mode 02 Setting record Record any changes to the settings in the following table Set...

Страница 13: ...main power 8 4 1 Group control system A number of indoor units can be operated at the same time using a single remote controller 1 Wiring method indoor unit to remote controller 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Indoor unit 1 Bus wire Remote controller cable Remote controller When ground wire is necessary Indoor unit 2 Indoor unit 3 Indoor unit 4 2 DIP switch setting Indoor unit Set the unit number of...

Страница 14: ...nnected the outdoor unit using a transmission cable is primary Connect the remote controller wire to the primary unit Twin type Outdoor unit Indoor unit Indoor unit Remote controller primary secondary DIP switch setting Indoor unit 2 Set the unit number of each indoor unit using the DIP switches on the indoor unit circuit board See the following table and figure The DIP switches are normally set t...

Страница 15: ...controller while the air conditioner is running Point the transmitter section of the wireless remote controller toward the air conditioner and press the TEST RUN button with the tip of a ball point pen etc Transmitter section TEST RUN button To end test operation press the wireless remote controller START STOP button When the air conditioner is run by pressing the TEST RUN button the OPERATION ind...

Страница 16: ...CB model information error 3 5 Manual auto switch error 4 1 Room temp sensor error 4 2 Indoor unit Heat Ex Middle temp sensor error 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper error 5 15 Indoor unit error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PC...

Отзывы: