7-3. Forced cooling operation
The outdoor unit may not operate depending on the room temperature.
When FORCED COOLING OPERATION button is pressed more than 10 seconds, forced cooling
operation starts as shown in the table below.
Operation mode
Cooling
Fan mode
HIGH
Timer mode
Continuous (no timer setting available)
Setting temperature
24°C
Horizontal louver setting
Standard
Vertical louver setting
According to memory position
SWING
Off
ECONOMY
Off
Human sensor
Off
• During the forced cooling operation, it operates regardless of room temperature sensor.
• The operation indicator lamp and the timer indicator lamp blink simultaneously during the forced
cooling operation.
They blink for 1 second ON and 1 second OFF on both the operation indicator lamp and the timer
indicator lamp (same as test operation).
By performing one of the following action, test operation will be canceled:
• Pressing the remote controller START/STOP button
• Pressing FORCED COOLING OPERATION button for 3 seconds
• 60 minutes passed after starting forced cooling operation
NOTE:
When HEAT operation is selected on the remote controller during forced cooling operation,
heating test run will begin in about 3 minutes.
7-4. 10 °C HEAT operation
10 °C HEAT operation performs as below setting when pressing 10 °C HEAT button.
Operation mode
Heating
Setting temperature
10°C
Fan mode
AUTO
LED display
Economy
Defrost operation
Operate as normal
7-5. ECONOMY operation
The ECONOMY operation starts by pressing ECONOMY button on the remote controller.
The ECONOMY operation is almost the same operation as below settings.
Mode
Cooling/Dry
Heating
Target temperature
Setting tempe1°C
Setting temperature -1°C
7-3. Forced cooling operation
- (04-23) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General AOHH30KMTB
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Страница 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Страница 36: ......
Страница 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Страница 94: ......
Страница 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...