1-5. Rotation number of compressor limitation by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
13°C
E zone
7°C
D zone
°C
C zone
B zone
A zone
-5
2
°C
-10°C
G zone
21°C
J zone
50°C
K zone
52°C
H zone
31°C
I zone
46°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
ASHH30KMTB
ASHH36KMTB
A zone
55 rps
B zone
52 rps
C zone
47 rps
D zone
39 rps
E zone
33 rps
F zone
25 rps
G zone
18 rps
H zone
20 rps
I zone
20 rps
J zone
21 rps
K zone
24 rps
1-5. Rotation number of compressor limitation by outdoor temperature
- (04-4) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS