1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
• If the room temperature is 6.0 °C lower than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
• If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
rotation number of compressor is controlled within the range shown below.
•
Rotation number range of compressor
Unit: rps
Model name
Minimum rotation number
Maximum rotation number
ASHG07KMCE
ASHG09KMCE
ASHG12KMCE
14
110
ASHG14KMCE
12
110
•
Limit of maximum speed based on outdoor temperature
In heating operation, maximum rotation number is defined by outdoor temperature and fan mode.
A zone
17°C
B zone
19°C
C zone
14°C
12°C
Outdoor
temperature rises
Outdoor
temperature drops
Unit: rps
Model name
Outdoor
temperature zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASHG07KMCE
ASHG09KMCE
A zone
110
110
103
90
B zone
110
110
96
84
C zone
103
103
84
52
ASHG12KMCE
A zone
110
110
90
78
B zone
110
110
84
73
C zone
103
103
73
46
ASHG14KMCE
A zone
110
110
96
77
B zone
110
110
89
72
C zone
96
96
77
38
1-2. Heating operation
- (04-3) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General AOHG07KMCC
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 02 03 SR_CH01_AS061EG_01 ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 02 03 SR_CH02_AS061EG_01 ...
Страница 41: ...3 TROUBLESHOOTING 2022 02 03 SR_CH03_AS061EG_01 ...
Страница 44: ......
Страница 97: ...4 CONTROL AND FUNCTIONS 2022 02 03 SR_CH04_AS061EG_01 ...
Страница 133: ...5 FILED WORKING 2022 02 03 SR_CH05_AS061EG_01 ...