When function setting is “Forced stop” mode
– In the case of “Edge” input:
Function
setting
Rotary SW on External
input and output PCB
External input
Input signal
Command
46-02
1
External input and
output PCB
CN313
Off → On
Forced stop
On → Off
Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On
On
Indoor unit
On
CN313
– In the case of “Pulse” input:
Function
setting
Rotary SW on External
input and output PCB
External input
Input signal
Command
46-02
1
External input and
output PCB
CN313
Pulse
Forced stop
CN314
Pulse
Normal
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
CN313
CN314
On
On
On
Indoorunit
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
2-4. Details of function
- (05-17) -
2. External input and output
FIELD
WORKING
FIELD
WORKING