3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
(Table 18 : Anti-freezing Protection Operation / Release Temperature)
Outdoor temperature
Over than 10°C
*1
or 12°C
*2
Less than 10°C
*1
or 12°C
*2
*1. When the temperature rises.
*2. When the temperature drops.
4°C
7°C
13°C
Temperature
Temperature
68°C
63°C
4. COOLING PRESSURE OVER RISE PROTECTION
On cooling mode, the compressor frequency is controlled as following based on the
detection value of the outdoor heat exchanger temperature sensor.
Outdoor heat exchange
temperature
Compressor is OFF
The compressor frequency is
decreased 7rps every 120seconds.
Release of protection
45,54LBTA
45,54LBTA
67°C
Outdoor heat exchange
temperature
Compressor is OFF (3 minutes stop)
Release of protection
30,36LBTA
After 60sec. temp detection starts
Ta : Outdoor Temperature
(Control / Release)
[ Cooling ]
850/800rpm 780/750rpm 750/700rpm 540/520rpm 360/340rpm 290/270rpm 480/ 0rpm
350/ 0rpm
280/ 0rpm
400/ 0rpm
50°C < Ta
=
12.5A/12.0A
5.0A/4.5A
6.5A/6.0A
11.0A/10.5A
8.0A/7.5A
12.5A/12.0A
12.5A/12.0A
12.5A/11.5A
14.5A/14.0A
14.5A/14.0A
17.5A/17.0A
19.0A/18.5A
11.5A/11.0A
13.5A/13.0A
16.5A/16.0A
19.0A/18.5A
19.5A/19.0A
9.0A/8.5A
10.0A/9.5A
10.0A/9.5A
15.5A/15.0A
15.5A/15.0A
15.0A/14.5A
16.0A/15.5A
9.0A/8.5A
6.0A/5.5A
10.0A/9.5A
16.5A/16.0A
10.5A/10.0A
13.0A/12.5A
13.5A/13.0A
13.5A/13.0A
Outdoor unit fan speed (UP / LO)
Ta < -15°C
46°C < Ta < 50°C
=
40°C < Ta < 46°C
=
38°C < Ta < 40°C
=
31°C < Ta < 38°C
=
19°C < Ta < 31°C
=
13°C < Ta < 19°C
=
0°C < Ta < 7°C
=
-5°C < Ta < -0°C
=
-10°C < Ta < -5°C
=
-15°C < Ta < -10°C
=
7°C < Ta < 13°C
=